1.  Device configuration 

 

1.1. Physical Address. 

KNX physical address of the device in the network

 

 

1.2. Extended Addresses. 

Enables usage of KNX Extended addresses (range from 16/0/0 to 32/7/255).

 

 

2.  Operating Mode.

 

Settings related to KNX interface for control and feedback of AC unit’s operating mode.

 

 
2.1. KNX DPT for HVAC operation mode comm object. Base DPT. 

Base DPT to use for control/monitor the 

operating mode. Following DPT types are offered: 
 

o

 

DPT_20.105. DPT_HVACContrMode: 0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry 

o

 

DPT_5.x (non-standarized): 0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool 

 

2.2. KNX DPT for HVAC operation mode comm object. Extra DPT. 

Additional DPT to use for control/monitor 

the operating mode. 
 

o

 

DPT_1.100. DPT_Heat/Cool: 0-Cool, 1-Heat. 

o

 

DPT_5.001. DPT_Scaling: Enables objects “Control_  Heat Mode & On” and “Control_ Cool Mode & 
On”. Their type is DPT_Scaling (0..100%), and their ending is to be able to control parameters On/Off, 
Cool/Heat of indoor unit from a single percentage object. They are meant to provide compatibility with 
certain thermostats oriented to the operation of valves for Heating/Cooling. Whenever a value > 0% is 
received at each of these two objects, the corresponding operating mode and ON operation is sent to 
the indoor unit. Whenever both values are 0%, indoor unit is set to OFF 

 

2.3. Use of 1-bit Operating Modes.

 

1-bit Control Objects.

 Enables a bit-type object for the control of each 

operating mode. 
 

2.4.  Use  of  1-bit  Operating  Modes.

 

1-bit  Status  Objects.

  Enables  a  bit-type  object  for  monitoring  each 

operating mode. 

 

3.  Temperature Sensor.  

 

3.1. Ambient temperature provided from KNX.

 Enables object Control_ KNX ambient temperature. 

 
 
 
 

 
 
 
 

NOTE: 

Indoor unit does not accept, by itself, that an ambient temperature for control of operation 

of the indoor unit is provided. To allow regulation of indoor unit according to a temperature reference 
from KNX, what IntesisBox does is passing a different temperature setpoint to the indoor unit than 
the one required by the user. The passed setpoint is such that the difference ‘Ambient temperature 
reported  by  Hitachi  IU 

–  AC  setpoint’  is  equal  to  ‘Ambient  temperature  reported  by  KNX  –  AC 

setpoint required by KNX’, using the following formula: 
 
“AC Setp. Temp” = “AC Ret. Temp” - (“KNX Amb. Temp.” - “KNX Setp. Temp”) 
 
Where: 

AC Setp. Temp: AC indoor unit setpoint temperature 

AC Ret. Temp: AC indoor unit return temperature 

KNX Amb. Temp.: Ambient temperature provided from KNX 

KNX Setp. Temp: Setpoint temperature provided from KNX 

 
 
Consequently,  when  using  this  feature  (Ambient  temp  provided  from  KNX),  setpoint  at  AC  and 
setpoint in KNX will not necessarily be the same (actually, user will not be able to operate setpoint 
from AC System controllers as the remote controller). 

Содержание IBKNXHIS016O000

Страница 1: ...IntesisBox KNX Hitachi VRF Air Conditioning User Manual Issu Date 01 2019 r1 1 EN...

Страница 2: ...r a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval syst...

Страница 3: ...ior notice IntesisBox is a registered trademark of Intesis Software S L U email info intesisbox com web www intesisbox com phone 34 938047134 Gateway for the integration of Hitachi VRF systems into KN...

Страница 4: ...installation 10 Connection to KNX 10 Connection to the configuration tool 10 4 Set up process and troubleshooting 11 Pre requisites 11 IntesisBox MAPS Configuration monitoring tool for IntesisBox KNX...

Страница 5: ...s integration is to monitor and control your Hitachi air conditioning system from your KNX TP 1 installation To do it so IntesisBox performs as a one more KNX device sending and receiving telegrams to...

Страница 6: ...ntinuously monitors Hitachi VRF network for all configured signals and keeps the updated status of all of them in its memory It triggers updates on configured group addresses to KNX network on value c...

Страница 7: ...047134 Capacity of IntesisBox Element Max Notes Number of indoor units 64 Number of indoor units that can be controlled through IntesisBox There are different models of IntesisBox KNX Hitachi VRF each...

Страница 8: ...flags configured for the communication object See details below Points definition Every group object in configuration has following KNX properties Property Description Description Descriptive informat...

Страница 9: ...plying any other device Ethernet Connect the cable coming from the IP network to the connector ETH of the gateway Use an Ethernet CAT5 cable If communicating through the LAN of the building contact th...

Страница 10: ...ve terminal connected to earth The use of AC power supplies only if they are floating and not powering any other device Connect to Hitachi installation Use the Port B connector of the IntesisBox devic...

Страница 11: ...ation are IntesisBox gateway Link to download the configuration tool USB Console cable to communicate with IntesisBox Product documentation IntesisBox MAPS Configuration monitoring tool for IntesisBox...

Страница 12: ...34 938047134 4 2 3 Configuration tab Select the Configuration tab to configure the connection parameters Three subsets of information are shown in this window General Gateway general parameters KNX KN...

Страница 13: ...eceived at each of these two objects the corresponding operating mode and ON operation is sent to the indoor unit Whenever both values are 0 indoor unit is set to OFF 2 3 Use of 1 bit Operating Modes...

Страница 14: ...merated values 4 4 Use of 1 bit Fan Speed 1 bit Control Objects Enables a bit type object for control of fan speed 4 5 Use of 1 bit Fan Speed 1 bit Status Objects Enables a bit type object for monitor...

Страница 15: ...nfiguration section you need to enter for each unit Active If it s active checkbox at Unit xx ranging from 1 to 64 indoor units that will be integrated maximum number of units will depend on IntesisBo...

Страница 16: ...Error window will appear if there is a problem in the connection with H Link bus units not powered bus not connected A progress bar will appear during the scan which will take up to a few minutes Afte...

Страница 17: ...ark of Intesis Software S L U email info intesisbox com web www intesisbox com phone 34 938047134 Figure 4 7 IntesisBox MAPS Hitachi configuration tab after importing scan results 4 2 6 Signals All av...

Страница 18: ...tion file to the IntesisBox using the Send button in the Receive Send section 4 2 8 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some spe...

Страница 19: ...t to change without prior notice IntesisBox is a registered trademark of Intesis Software S L U email info intesisbox com web www intesisbox com phone 34 938047134 Figure 4 10 Diagnostic More informat...

Страница 20: ...nd or any other equipment connected to it we strongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive ter...

Страница 21: ...HDD connection not allowed Power 1 x Plug in screw terminal block 3 poles 9 to 36VDC 10 Max 140mA 24VAC 10 50 60Hz Max 127mA Recommended 24VDC Push Button Button A Check the user manual Button B Check...

Страница 22: ...ox is a registered trademark of Intesis Software S L U email info intesisbox com web www intesisbox com phone 34 938047134 6 Dimensions Recommended available space for its installation into a cabinet...

Страница 23: ...registered trademark of Intesis Software S L U email info intesisbox com web www intesisbox com phone 34 938047134 7 AC Unit Types compatibility A list of Hitachi unit model references compatible with...

Страница 24: ...wout of Fuse Outdoor Unit Power OFF 04 Abnormality between lnverter PCB and Outdoor PCB lnverter PCB Outdoor PCB Transmission Failure Loose Connector Wire Breaking Blowout of Fuse 04 Abnormality betwe...

Страница 25: ...nit Combination lndoor Unit is Designed for R22 38 Abnormality of Picking up Circuit for Protection in Outdoor Unit Failure of Protection Detecting Device lncorrect Wiring of Outdoor PCB 39 Compressor...

Страница 26: ...rature Fin Thermistor Failure Heat Exchanger Clogging Fan Motor Failure 5b Activation of Overcurrent Protection Fan Motor Failure 5C Abnormality of Fan Controller Sensor Failure of Current Sensor lnst...

Страница 27: ...NIT SIGNALS COMM ERROR Status_Communication Error OU 1 bit DPT_Alarm 1 005 R T 0 No error 1 Error TEMPERATURES Status_Outdoor Air Temperature C 2 byte DPT_Value_Temp 9 001 R T 50 99 C Status_Compresor...

Страница 28: ...ch 1 001 R T 1 Dry mode active 0 Dry mode not active Control_Fan speed enumerated 1 byte Non standarized 5 x W 1 Low 2 Mid 3 High 4 High FAN SPEED Status _Fan speed enumerated 1 byte Non standarized 5...

Страница 29: ...bit DPT_Switch 1 001 W 1 Vane position 3 active 0 Vane position 3 not active Control_Vane position position 4 1 bit DPT_Switch 1 001 R T 1 Set position 4 vane Status_Vane position position 4 1 bit DP...

Страница 30: ...l_Setpoint Remote controll disablement 1 bit DPT_Bool 1 002 W 0 No disabled 1 Disabled Status_Setpoint Remote controll disablement 1 bit DPT_Bool 1 002 R T 0 No disabled 1 Disabled Control_Fan Remote...

Отзывы: