DK-RC-MBS-1
User’s Manual r3.3
EN
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
Phone
http://www.intesisbox.com
[email protected]
+34 938047134
8/23
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
6
7
R/W
Window Contact
▪
0: Closed (Default)
▪
1: Open
7
8
R/W
DK-RC-MBS-1 Disablement
4
▪
0: DK-RC-MBS-1 enabled (Default value)
▪
1: DK-RC-MBS-1 disabled
8
9
R/W
AC Remote Control Disablement
4
▪
0: Remote Control enabled (Default value)
▪
1: Remote Control disabled
9
10
R/W
AC unit Operation Time
4
▪
0..65535 (hours). Counts the time the AC
unit is in “On” state.
10
11
R
AC unit Alarm Status
▪
0: No alarm condition
▪
1: Alarm condition
11
12
R
Error Code
5
▪
0: No error present
▪
65535(-1 if it is read as signed value): Error
in the communication of DK-RC-MBS-1 with
the AC unit.
▪
Any other error present, see the table at the
end of this document.
22
23
R/W
Indoor unit´s ambient temperature from
external sensor (at Modbus side)
1,2,3,6,7
▪
-32768: (Initialization value). No
temperature is being provided from an
external sensor.
▪
Any other: (ºC/x10ºC/ºF)
23
24
R
AC Real temperature setpoint
1,2,3,6
▪
When no external temperature is provided,
this read-only register will have the same
value as register 5 (PLC addressing). In all
cases, it will show the current setpoint in the
indoor unit.
▪
16..31ºC (ºC/x10ºC)
▪
60..90ºF
26
27
R/W
AC unit Horizontal Vane Position
1
▪
0: Auto (Default Value)
▪
10: Swing
55
56
R/W Under voltage counter
1
▪
0..300
97
98
R/W
Block Periodic Sendings
4,8,9
▪
0: Non-blocked (Default value)
▪
1: Blocked
4
This value is stored in non-volatile memory
5
See section 7 for possible error codes and their explanation
6
See section 4.2.3 for more information
7
This register is available in firmware version 0.8 onwards
8
If the register is configured as “0:
Non-
blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”,
commands from Modbus will only be sent to the AC system if they differ from the previous value.
9
This register applies to firmware version 1.6 onwards