background image

www.intertec.info

Operating Instructions SL BLOCKTHERM DB.A

Page 6 / 8

HOM146759307Ien-5

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   [email protected]

short-circuit  protection.  When  using  a  heater  without  in-
tegrated thermostat, the fuse protection can be selected
according to the cross-section of the supply cable.

Additional  equipotential  bonding  is  required.  The  ter-
minal  block  designated  for  this  purpose  has  the  ground
sign.

In  a  TT  or  TN  system,  a  residual  current  device  (RCD)
must  be  used  where  the  measured  triggering  residual
current  does  not  exceed  100  mA.  Residual  current
devices with a measured triggering residual current of 30
mA are preferable. In an IT system, an insulation monit-
oring  device  needs  to  be  used  which  switches  off  the
supply as soon as the insulation resistance is no greater
than  50  Ω  per  Volt  of  the  rated  voltage  (refer  also  to
ABNT NBR IEC 60079-14:2009).

ATTENTION:

Never remove the

adapter/ cable gland!

Illustration 4: 

Example heater with KLE connection

 CAUTION

NOTICE: Do not remove adapter/ cable connec-
tion to connect up the heater!

This would cause irreversible damage to the heater and
this would mean that the explosion protection can no
longer be warranted.

The illustration may deviate from the heater.

1

2

L

N

PE

J

J

Junction

box

Heater

TAE

bn

bl

ye/gn

bk

gy

Option AM

bn=brown bl=blue ye/gn=yellow/green bk=black gy=grey

Illustration 5: 

SL...THERM with TAE

Содержание SL BLOCKTHERM DB.A

Страница 1: ...Operating Instructions SL BLOCKTHERM DB A HOM146759307Ien 5 05 02 2020...

Страница 2: ...e 3 3 Special conditions for safe use 3 4 Explanation of symbols for warnings and signal words 3 5 Safety information 4 6 Technical Data 4 7 Option BLOCKTHERM ADA with aluminium plate 4 8 Installation...

Страница 3: ...sfer coefficient is not less not better than 0 5 W K 2 The connecting cable must have a fixed installation and must be protected mechanically 3 If connection is made in the potentially explosive area...

Страница 4: ...60 to 180 C Switching capacity of fault alarm AM 10 A 275 V AC Connecting cable Silicone hose cable notch and oil resistant 3 x 1 5 mm Connecting cable AM Silicone hose cable notch and oil resistant...

Страница 5: ...NOT exceed the trigger temperature of the limiter The operating temperatures must be adhered to The connection cable must be permanently installed up to the inlet into the on site junction box taking...

Страница 6: ...ent devices with a measured triggering residual current of 30 mA are preferable In an IT system an insulation monit oring device needs to be used which switches off the supply as soon as the insulatio...

Страница 7: ...the manufacturer in the factory All components have to be kept clean and free of dust and harmful substances that could lead to excessive temperature rise In the dust Ex area the applicable requireme...

Страница 8: ...9 Vers o Corrigida 2 2011 ABNT NBR IEC 60079 31 2014 ABNT NBR IEC 60529 2005 Vers o Corrigida 2 2011 IEC 61000 6 4 2007 A1 2011 Designation NCC 17 0104 X Ex tb IIIC T85 C T100 C T135 C T200 C Db Ex db...

Отзывы: