Warning notices concerning the electrical installation
DANGER
Danger to life – electrocution
Improper electrical installation can cause life-threatening electric shocks or damage to the Pallet
Control.
4
Only have an electrician undertake electrical installation work.
4
Observe national regulations for electrical installation. Within the EU, IEC 60204-1 must be
met at a minimum.
4
Before installing, wiring or removing the Pallet Control, switch it off and ensure that it cannot
be started accidentally.
4
The Pallet Control may be operated only with AC voltage at a nominal voltage of 400 V 50
Hz and 24 V DC and a maximum permissible deviation according to the technical data.
4
Proceed with caution when connecting the Pallet Drive to avoid damaging the magnetic
sensor on the printed circuit board.
4
Ensure that the control systems, motors and power sources connected to the Pallet Control,
as well as the entire conveyor system, are correctly grounded. Incorrect grounding can result
in the build-up of a static charge, causing the Pallet Control to malfunction or fail
prematurely.
4
Ensure that the existing electrical installation does not interfere with the Pallet Control.
4
Use only cables that are sufficiently dimensioned for the specific operating conditions.
4
Do not forget to observe the calculations for voltage drop on electrical lines.
4
Observe the regulations for routing cables.
4
Use suitable switching equipment and protective devices to ensure safe operation.
4
Only apply operating voltages when all cables have been connected.
4
Do not apply too much tension or pressure to the plug. When bending the cable at the plug,
the insulation of the cable may be damaged and the Pallet Control may fail.
4
Install a suitable protection mechanism so that the Pallet Control and the line are not
overloaded.
4
The protective mechanism must be arranged in a suitable manner and easily accessible.
4
The protective mechanism must be identified as disconnect device for the PC 6000.
4
Have an electrician undertake the dimensioning of the protection mechanism.
4
Observe the technical specifications!
4
When selecting the circuit protection, pay particular attention to the maximum short circuit
current of the voltage supply.