background image

508 01 1603 01

Specifications subject to change without notice.

31

Pulley and Drive Adjustment

To obtain desired fan speed, refer to the fan motor and drive

data in Tables 20-42 and adjust fan motor pulley as follows:
1. Remove belt from fan motor pulley after loosening

motor from motor base.

2. Loosen setscrew in moveable flange of pulley. Screw

moveable flange toward fixed flange to increase the

fan speed and away from fixed flange to reduce

speed. Before tightening setscrew, make certain that

setscrew is over nearest flat surface of pulley hub

(Fig. 26).

Condensate Drains

Keep condensate drains free of dirt and foreign matter.

Return-Air Filters

Refer to Replacing Filters section for filter accessibility and

removal. Replace with clean filters of the sizes listed in

Tables 4-11.

• After draining as much water as possible from coils,

add sufficient antifreeze to prevent residual water in

the coil from freezing.

• Add a sufficient quantity of non-corrosive antifreeze

to the entire system to prevent all water within the

system from freezing.

Coil Removal

Remove unit panels and corner posts as required. Discon-

nect coil connections and remove fastening screws. Re-

move coil through end or side sections of unit.

Cleaning Cooling Coil

Remove return-air filters. Remove any heavy dirt that may

have accumulated on underside of coil. Coil can be cleaned

more easily with a stiff brush, vacuum cleaner, or com-

pressed air when coil is dry. If coil is wet or if water is to be

used for cleaning, guard against splashing water on electri-

cal components or damaging surrounding area. Clean coil

baffles as applicable and check for tight fit to be sure air

does not bypass coil.

Cleaning Insulation

The insulation contains an immobilized antimicrobial agent

that helps prevent the growth of bacteria and fungi. Clean

the inner surface of the insulation according to the separate

maintenance instructions shipped with the unit.

Replacing Filters

Filters can be removed and installed from either side of the

unit. Install new filters in units that have one fan as follows:
1. Remove the side access panel (retain screws).

2. Remove the filter retainer clip (see Fig. 27).

3. Remove old filters by lifting and tilting them out of the

filter track. See Fig. 15 and 28. Use the factory-sup-

plied filter hook to slide filters within reach for

removal. The filter hook is shipped inside the unit in

the filter track.

4. Reverse the procedure to install new filters.
To install new filters in larger units that have 2 fans, follow

the preceding steps, but use the factory-supplied filter hook

to slide filters within reach for removal. The filter hook is

shipped inside the unit in the filter track.

Fig. 27 — Remove Filter Retainer Clip

Fig. 28 — Filter Removal/Replacement

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment

damage.
Increasing fan speed produces a greater load on motor.

Do not exceed rated capacity of motor.

SLIDE

FILTER
RETAINER
CLIP

Содержание FAS Series

Страница 1: ...ations Have fire extinguisher available for all brazing operations It is important to recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructi...

Страница 2: ...ine unit for shipping damage If shipping damage is evident file claim with transportation agency Remove base skid just pri or to actual installation Check nameplate information against available power...

Страница 3: ...Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Rows Fins in 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 2 11 8 DX Coil Liquid Refrigera...

Страница 4: ...ea sq ft 19 88 24 86 29 83 No of Splits 2 2 2 No of Circuits per Split 18 20 24 Split Type Percentage Face 50 50 Rows Fins in 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 1...

Страница 5: ...93 1 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Rows Fins m 4 591 4 591 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF...

Страница 6: ...q m 1 85 2 30 2 77 No of Splits 2 2 2 No of Circuits per Split 18 20 24 Split Type Percentage Face 50 50 Rows Fins m 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 11 8 2...

Страница 7: ...1 1 2 2 No of Circuits per Split 15 12 12 9 10 Split Type Percentage Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 1 11 8 2 11...

Страница 8: ...a sq ft 19 9 No of Splitsno 2 No of Circuits per Split 2 Split Type Percentage Face 50 50 Rows Fins in 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 11 8 DX Coil Liquid Refrigerant OD...

Страница 9: ...of Circuits per Split 15 12 12 9 10 Split Type Percentage Face 50 50 Rows Fins m 3 591 4 591 4 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 1 11 8 2 11 8 2 11...

Страница 10: ...ea sq m 1 85 No of Splits 2 No of Circuits per Split 2 Split Type Percentage Face 50 50 Rows Fins m 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 2 11 8 DX Coil Liquid Refrigerant ODF 2...

Страница 11: ...508 01 1603 01 Specifications subject to change without notice 11 Fig 1 Unit Dimensions 6 10 Ton Units...

Страница 12: ...12 Specifications subject to change without notice 508 01 1603 01 Fig 2 Unit Dimensions 12 5 to 20 tons...

Страница 13: ...508 01 1603 01 Specifications subject to change without notice 13 Fig 3 Unit Dimensions 25 and 30 tons...

Страница 14: ...and FHS 072 120 units with a M voltage designation are triple voltage i e 208 230 460 3 60 FAS 180 units are also triple voltage in the M configuration unless the High Static motor option is used M v...

Страница 15: ...efore unit is placed in final position The direct expansion units have internal factory installed thermostatic expansion valves TXVs distributors and nozzles for use with R 410A See Table 12 for part...

Страница 16: ...pecifications subject to change without notice 508 01 1603 01 Fig 7 Preferred Suspension Technique UNIT SIZES 6 10 TON UNIT SIZES 12 5 30 TON A A 7 11 1 2 2426 20 Ton 8 9 1 2 2680 25 30 Ton 4 7 1 2 14...

Страница 17: ...E Access hole knockouts 1 4 are factory supplied LEGEND TXV Thermostatic Expansion Valve NOTE Component location arrangemetshown for field installation of sight glasses solenoid valves filter driers a...

Страница 18: ...2 1178408 2 1135 9 1 4 2 1178409 2 G3 FHS120 4 Row 2 1178405 2 BBIZE 5 GA 2 1178407 2 1113 9 3 16 2 1178409 2 G3 FAS150 4 Row 2 1178405 2 BBIZE 5 GA 2 1178407 2 1113 12 3 16 2 1178409 2 G3 FAS180 4 Ro...

Страница 19: ...bow FHS120 1 Suction Lower 2 11 8 Street Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 51 2 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street Elbow 5 8 Nipple 101 2 L 5 8 Long Radius Elbow 4 Suctio...

Страница 20: ...Upper 5 8 Nipple 27 8 L 5 8 45 Elbow 5 8 Nipple 41 4 L 5 8 Long Radius Elbow 7 Suction Upper 11 8 Nipple 5 L 11 8 45 Elbow 11 8 Nipple 83 4 L 11 8 Long Radius Elbow FAS300 1 Suction Lower 13 8 Street...

Страница 21: ...e pan should have a pitch of at least 1 4 in over its length toward the drain connection Fig 12 Condensate Drains Fig 13 Drain Pan Slope Adjustment Fan Motors and Drives Motor and drive packages are f...

Страница 22: ...o the 24 v control circuit terminal block located in the side of the fan contactor control box according to Fig 17 or the unit label diagram If the air handler is part of a split system complete the w...

Страница 23: ...632 7 5 5 59 10 0 13 0 20 FAS336 208 230 3 60 187 253 10 0 7 46 32 0 40 0 70 460 3 60 414 506 10 0 7 46 16 0 20 0 35 575 3 60 518 632 10 0 7 46 13 0 17 0 25 Table 15 Electrical Data Alternate Motors S...

Страница 24: ...3 60 518 632 2 4 1 79 3 5 5 0 15 FHS120 208 230 3 60 187 253 1 7 1 27 5 8 8 0 15 460 3 60 414 506 1 7 1 27 2 9 4 0 15 575 3 60 518 632 1 7 1 27 2 8 4 0 15 FAS150 208 230 3 60 187 253 2 9 2 16 8 6 11 0...

Страница 25: ...8 230 3 60 187 253 3 7 2 76 10 6 14 0 20 460 3 60 414 506 3 7 2 76 5 3 7 0 15 575 3 60 518 632 3 7 2 76 4 5 6 0 15 FAS150 208 230 3 60 187 253 3 7 2 76 10 8 14 0 20 460 3 60 414 506 3 7 2 76 4 9 7 0 1...

Страница 26: ...d Power Wiring between the heater TB1 and the FAS FHS indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclosure and FAS FHS power entry location Install wire...

Страница 27: ...ductwork route return air duct to the unit s return air inlet near the filter rack using a canvas con nection to prevent transmission of unit vibration If the duct blocks off the unit s access panel...

Страница 28: ...turn the stem counterclock wise Do not turn the stem more than one full turn 3 Wait until suction pressure and superheat stabilize This may take more than 30 minutes 4 Continue adjustment until superh...

Страница 29: ...and Fan Wheel Typical Centering Fan Wheel If fan and fan shaft assembly are not properly centered blades may scrape against the blower side scroll plate or may create an objectionable whistling noise...

Страница 30: ...orrect deflection is 1 8 in 3 2 mm See Fig 24 If complete belt replacement is required during servicing loosen the motor plate mounting bolts see Fig 24 move motor plate assembly towards fan pulley an...

Страница 31: ...tiff brush vacuum cleaner or com pressed air when coil is dry If coil is wet or if water is to be used for cleaning guard against splashing water on electri cal components or damaging surrounding area...

Страница 32: ...cal Manufacturers Association Table 21 Fan Motor Data Alternate Motor Single Speed English UNIT FAS072 FHS072 FAS091 FHS091 FAS120 FHS120 FAS150 FAS180 FHS180 FAS240 FHS240 FAS300 FAS336 208 230 1 60...

Страница 33: ...56HZ 56HZ 56HZ 184T S213T S215T Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 28 6 34 9 34 9 NEMA National Electrical Manufacturers Association Table 24 Fan Motor Data Alternate Motor Single Speed SI UNIT FA...

Страница 34: ...Electrical Manufacturers Association Table 26 Fan Motor Data FAS Alternate Motor Two Speed English UNIT FAS072 FAS091 FAS120 FAS150 FAS180 FAS240 FAS300 FAS336 208 230 3 60 and 460 3 60 Speed rpm 1750...

Страница 35: ...2 76 2 76 3 73 5 59 7 46 Frame NEMA 56HY 56HY 56HY 56HZ 56HY 184T S213T S215T Shaft Dia mm 15 9 15 9 15 9 22 2 22 2 28 6 34 9 34 9 Table 29 Fan Motor Data FAS Alternate Motor Two Speed SI UNIT FAS072...

Страница 36: ...t Dia in 5 8 5 8 5 8 7 8 11 8 Table 31 Fan Motor Data FHS Alternate Motor Two Speed English UNIT FAS072 FAS091 FAS120 FAS180 FAS240 208 230 3 60 and 460 3 60 Speed rpm 1750 1750 1725 1755 1760 Hp 3 7...

Страница 37: ...28 00 27 75 28 50 29 25 Shaft kW 1 79 1 79 1 79 2 76 3 73 Frame NEMA 56HY 56HY 56HY 56HY 184T Shaft Dia mm 15 9 15 9 15 9 22 2 28 6 Table 34 Fan Motor Data FHS Alternate Motor Two Speed SI UNIT FAS072...

Страница 38: ...able Speed rpm 1200 1200 1200 1200 1200 1200 1100 1100 Change per 1 2 Turn of Moveable Motor Pulley Flange 19 6 19 6 19 7 19 1 19 1 15 3 13 1 13 1 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 5 6 6 6 S...

Страница 39: ...0 11 2 13 9 Max Allowable Speed r s 20 0 20 0 20 0 20 0 20 0 20 0 18 3 18 3 Change per 1 2 Turn of Moveable Motor Pulley Flange 0 327 0 327 0 328 0 318 0 318 0 255 0 218 0 218 MAX FULL TURNS FROM CLOS...

Страница 40: ...917 2 23 967 2 45 1014 2 67 4 500 786 1 99 815 2 12 873 2 39 929 2 65 980 2 90 1028 3 16 1073 3 41 5 000 867 2 70 893 2 84 946 3 14 997 3 43 1046 3 72 1092 4 00 1135 4 28 FAS150 3 750 410 0 43 467 0 5...

Страница 41: ...00 1018 2 26 1065 2 48 1111 2 70 1156 2 93 3 750 1057 2 69 1101 2 92 1144 3 15 1186 3 39 FAS120 FHS120 3 000 961 1 78 1012 1 98 1062 2 19 1111 2 41 1158 2 64 3 500 1005 2 27 1052 2 49 1098 2 71 1142 2...

Страница 42: ...0 07 3 000 0 11 3 750 0 15 FAS120 FHS120 3 000 0 11 4 000 0 17 5 000 0 23 FAS150 3 750 0 06 5 000 0 10 6 250 0 13 FAS180 FHS180 4 500 0 08 6 000 0 12 7 500 0 17 FAS240 FHS240 6 000 0 12 8 000 0 19 10...

Страница 43: ...pan to confirm proper drainage Y N ______________ Are proper air filters in place Y N ______________ Have fan and motor pulleys been checked for proper alignment Y N ______________ Do the fan belts ha...

Страница 44: ...temp ______________ ____________ Discharge pressure ______________ ____________ Discharge line temp ______________ ____________ Entering outdoor unit air temp ______________ ____________ Leaving outdo...

Отзывы: