22
Specifications subject to change without notice.
508 01 1603 01
Fig. 14 — Disconnect Switch and Unit
Install disconnect switch and power wiring in accordance
with all applicable local codes. See Fig. 14-16 and the
unit label diagram. Connect power wiring with
1
/
4
-in. ring
terminal.
The FAS/FHS size 072-180 units that have motors wired for
460-v, 3-ph, 60 Hz operation can be field-converted to 208/
230-v, 3-ph, 60 Hz operation. Rewire the motor according to
the diagram plate on the motor. After reconfiguring the mo-
tor, mark the motor specifying 208-v or 230-v operation re-
placing the 460-v sticker information on the units’ corner
post.
Fan motors are factory-installed on all units. Indoor-fan con-
tactors are located in the fan contactor box behind the side
access panel (see Fig. 15 and 16). Wire the thermostat to
the 24-v control circuit terminal block located in the side of
the fan contactor control box, according to Fig. 17 or the unit
label diagram. If the air handler is part of a split system,
complete the wiring from the condensing unit to the thermo-
stat shown in Fig. 17.
Fig. 15 — Wiring and Service Access (Side Panel
Removed)
Fig. 16 — Fan Contactor Box and Terminal Block
(Cover Removed) (Typical)
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal in-
jury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and unit. Use only copper wire.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
FILTER
ELEMENTS
FILTER
RETAINER
CLIP
FAN SCROLL
CONDENSATE
DRAIN
CONNECTION
(HORIZONTAL)
MOTOR
AND DRIVE
FAN
CONTACTOR
BOX
WIRE
ACCESS
COIL
FAN DRIVE
PULLEY
TXV BULB
ACCESS
REFRIGERANT
PIPING ACCESS
CONDENSATE
DRAIN
CONNNECTION
(VERTICAL)
LEGEND
TXV —
Thermostatic Expansion Valve
2 3
2 2
2 1
1 3
1 2
1 1
1
0
5
°
C
6
0
0
V
R
J
A
W
FAN
CONTACTOR
24V
TERMINAL
BLOCK
POWER
WIRING
KNOCKOUT