10
Specifications subject to change without notice.
508 01 1603 01
LEGEND
Table 11 — Physical Data (SI) — 70 kW Heat Pump Units (FHS)
FHS UNIT
240
NOMINAL CAPACITY (kW)
70
OPERATING WEIGHT (kg)
Base Unit with TXV
326
Plenum
44
FANS
Qty...Diam. (mm)
2...381
Nominal Airflow (L/s)
3775
Airflow Range (L/s)
2831-4719
Nominal Motor kW (Standard Motor)
208/230-3-60 and 460-3-60
3.73
575-3-60
3.73
Motor Speed (r/s)
208/230-3-60 and 460-3-60
29.1
575-3-60
29.1
REFRIGERANT
R-410A
Operating charge (kg) (approx per circuit)*
1.59/1.59
DIRECT-EXPANSION COIL
Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag)
4482
Face Area (sq m)
1.85
No. of Splits
2
No. of Circuits per Split
2
Split Type...Percentage
Face...50/50
Rows...Fins/m
591
PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF)
2...1
1
/
8
DX Coil — Liquid Refrigerant (ODF)
2...
5
/
8
Steam Coil, In (MPT)
1...2
1
/
2
Steam Coil, Out (MPT)
1...1
1
/
2
Hot Water Coil, In (MPT)
1...2
Hot Water Coil, Out (MPT)
1...2
Condensate (PVC)
1...1
1
/
4
ODM/1 IDF
FILTERS
Throwaway — Factory Supplied
Quantity...Size (mm)
4...406 x 610 x 51
4...406 x 508 x 51
Access Location
Right or Left Side
STEAM COIL†
Max Working Pressure (kPag at 126°C)
138
Total Face Area (sq m)
1.24
Rows...Fins/m
1...394
HOT WATER COIL†
Max Working Pressure (kPag)
1034
Total Face Area (sq m)
1.24
Rows...Fins/m
2...335
Water Volume
(L)
52.6
(m
3
)
0.052
DX
—
Direct Expansion
TXV
—
Thermostatic Expansion Valve
*
Units are shipped without refrigerant charge.
† Field-installed accessory only.
Содержание FAS Series
Страница 11: ...508 01 1603 01 Specifications subject to change without notice 11 Fig 1 Unit Dimensions 6 10 Ton Units...
Страница 12: ...12 Specifications subject to change without notice 508 01 1603 01 Fig 2 Unit Dimensions 12 5 to 20 tons...
Страница 13: ...508 01 1603 01 Specifications subject to change without notice 13 Fig 3 Unit Dimensions 25 and 30 tons...