SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: (F/G)9MXE

Specifications  subject to change without notice.

440 04 4311 08

5

Adjustments

FIRE HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.

This can result in unregulated manifold pressure and result

in excess overfire and heat exchanger failures.

!

WARNING

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reduced furnace

life.
DO NOT redrill orifices. Improper drilling (burrs,

out

of

round holes, etc.) can cause excessive burner

noise and misdirection of burner flames. This can result in

flame impingement of heat exchangers, causing failures.

(See 

Figure 2

)

CAUTION

!

Figure 2

Orifice Hole

A93059

BURNER

ORIFICE

For proper operation and long term reliability the furnace input

rate must be /

2  percent of input rate on furnace rating

plate, or as adjusted for altitude.

NOTICE

The NATURAL GAS manifold pressure adjustments in 

Table 3

compensate for BOTH altitude AND gas heating value. DO

NOT apply an additional de

rate factor to the pressures shown

in 

Table 3

. The values in this Table and NOT referenced to sea

level; they are AS

MEASURED AT ALTITUDE.

The heating content of natural gas at altitude may already

provide for a reduction in capacity or altitude. Refer to 

Table 3

.

No adjustments to the furnace may be necessary at altitude for

certain gas heating values.
Refer to the instructions provided in the factory-specified

LP/Propane conversion kit for instructions for setting gas

manifold pressures for LP/Propane applications.

In the USA, the input rating for altitudes above 2000 ft. (610 M)

must be reduced by 2 percent for each 1000 ft. (305 M) above

sea level refer to 

Table 1

. The natural gas manifold pressures

in 

Table 3

 adjust for BOTH altitude and natural gas heating

value.

In Canada, the input rating must be reduced by 5 percent for

altitudes of 2000 ft. to 4500 ft. (610 to 1372 M) above sea level.

The natural gas manifold pressures in 

Table 3

 adjust for BOTH

altitude and natural gas heating value.

Table 1

Altitude Derate Multiplier for U.S.A.

ALTITUDE

FT. (M)

PERCENT

OF DERATE

DERATE MULTIPLIER

FACTOR*

0–2000

(0

610)

0

1.00

2001–3000

(610

914)

4

6

0.95

3001–4000

(914

1219)

6

8

0.93

4001–5000

(1219

1524)

8

10

0.91

5001–6000

(1524

1829)

10

12

0.89

6001–7000

(1829

2134)

12

14

0.87

7001–8000

(2134

2438)

14

16

0.85

8001–9000

(2438

2743)

16

18

0.83

9001–10,000

(2743

3048)

18

20

0.81

* Derate multiplier factors are based on midpoint altitude for altitude range.

NOTE

:  

For Canadian altitudes of 2000 to 4500 ft. (610 to

1372 M), use USA altitudes of 2001 to 3000 ft. (610 to 914

M)

 in 

Table 3

.

To adjust manifold pressure to obtain the proper input rate, first,

determine if the furnace has the correct orifice installed. At

higher altitudes or different gas heat contents, it may be

necessary to change the factory orifice to a different orifice.

Tables have been provided in the furnace Service and

Technical Manual to match the required orifice to the manifold

pressure to the heat content and specific gravity of the gas. To

do this:

1. Obtain average yearly gas heat value (at installed

altitude) from local gas supplier.

2. Obtain average yearly gas specific gravity from local gas

supplier.

3. Find installation altitude range for your installation in the

manifold pressure tables in 

Table 3

.

4. Find closest natural gas heat value and specific gravity in

Table 3

. Follow heat value and specific gravity lines to

point of intersection to find orifice size and low-and

high-heat manifold pressure settings for proper

operation.

5. Check and verify burner orifice size in furnace. NEVER

ASSUME ORIFICE SIZE. ALWAYS CHECK AND

VERIFY.

NOTICE

If orifice hole appears damaged or it is suspected to have been

redrilled, check orifice hole with a numbered drill bit of correct

size. Never redrill an orifice. A burr

free and squarely aligned

orifice hole is essential for proper flame characteristics.

6. Replace orifice with correct size, if required by 

Table 3

.

Use only factory

supplied orifices. See EXAMPLE 1.

EXAMPLE 1:

0 - 2000 ft. (0 - 609.6M) altitude

Heating value = 1050 Btu/cu ft.

Specific gravity = 0.62

Therefore: Orifice No. 44

(Furnace is shipped with No. 44 orifices. In this example, all

main burner orifices are the correct size and do not need to be

changed to obtain proper input rate.)

Manifold pressure: 3.4-in. w.c. (847 Pa).

NOTE

:  To convert gas manifold Table pressures to Pascals,

multiply the in.w.c. value by 249.1 Pa/in. w.c. (1 in. wc. = 249.1

Pa).

Содержание F9MXE0401410A

Страница 1: ...uct labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury TABLE OF CONTENTS START UP ADJUSTMENT AND SAFETY CHECK 4 PRIME CONDENSATE TRAP WITH WATER 4 PURGE GAS LINES 4 ADJUST TEMPERATURE RISE 10 ADJUST BLOWER OFF DELAY HEAT MODE 11 AD...

Страница 2: ...death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to carefully read and follow this w...

Страница 3: ...stream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5 and 6 90 120 150 180 Calculated Input BTU Rate See Checks and Adjustments Section Heating Check Measured Line Pressure During Heat Measured Manifold Pressure Heat Temperature of Supply Air Heat T...

Страница 4: ... switch CAUTION Before operating furnace check flame rollout manual reset switch for continuity If necessary press button to reset switch EAC 1 115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could result in personal...

Страница 5: ...T M PERCENT OF DERATE DERATE MULTIPLIER FACTOR 0 2000 0 610 0 1 00 2001 3000 610 914 4 6 0 95 3001 4000 914 1219 6 8 0 93 4001 5000 1219 1524 8 10 0 91 5001 6000 1524 1829 10 12 0 89 6001 7000 1829 2134 12 14 0 87 7001 8000 2134 2438 14 16 0 85 8001 9000 2438 2743 16 18 0 83 9001 10 000 2743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range NOTE For Canadi...

Страница 6: ...ove regulator adjustment cap from gas valve pressure regulator See Figure 3 and turn adjusting screw 3 16 or smaller flat tipped screwdriver counterclockwise out to decrease input rate or clockwise in to increase input rate NOTICE DO NOT set low heat manifold pressure less than 2 8 in w c 697 Pa or more than 3 8 in w c 947 Pa for natural gas If required manifold pressure is outside this range chan...

Страница 7: ...4VAC CONNECTIONS EAC TERMINAL 115 VAC 1 0 AMP MAX COOL SPARE2 SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINAL 24 VAC 0 5 AMP MAX 3 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 24VAC RED BLOWER SPEED SELECTION TERMINALS BL 1 XFMR Y1 DHUM HEAT OFF DELAY 120 180 90 150 ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ ÏÏ NEUTRAL L2 115 VAC L1 CONNECTIONS L1 IND P2 HOT SURFACE IGNITOR HSI INDU...

Страница 8: ...0 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 ...

Страница 9: ... 3 42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3 3 42 3 4 42 3 5 42 3 6 4001 775 43 3 7 43 3 8 42 3 3 42 3 4 1220 800 43 3 5 43 3 6 43 3 7 43 3 8 825 44 3 8 43 3 4 43 3 5 43...

Страница 10: ...n may result in S Overheating the heat exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating plate Recommended operation is at midpoint of rise range or slightly above CAUTION Jumper R to W to check gas heat temperature rise Do not exceed temperature rise...

Страница 11: ...ected to thermostat sub base terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat i...

Страница 12: ...OTTOM or TWO SIDES 4 5 Gray 2290 2225 2155 2090 2015 1930 1845 1750 1640 1515 Yellow 1810 1760 1725 1685 1640 1600 1555 1520 1480 1415 Blue 1385 1340 1285 1240 1200 1140 1090 1050 995 950 Orange 1560 1520 1475 1430 1385 1335 1295 1240 1200 1150 Red 1055 985 910 860 795 750 680 615 565 495 1002120 BOTTOM or TWO SIDES 4 5 Gray 2340 2295 2250 2195 2110 2030 1935 1835 1725 1605 Yellow 1950 1900 1855 1...

Страница 13: ... to follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil refrigerant control board etc before unit final disposal CAUTION ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death or property damage Before installing modifying or servicing system main electrical disconnect switch mus...

Страница 14: ...ooting Status codes can be viewed at the indicator in blower door The green furnace control LED is either ON heartbeat off or a code composed of 1 or 2 digits The first digit is the number of short flashes the second digit is the number of long flashes Figure 7 Heating and Cooling Application Wiring Diagram with Single Stage Thermostat 115 V FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL ...

Страница 15: ...ing thermostat setting below room temperature 7 Verify that furnace restarts by raising thermostat setting above room temperature Care and Maintenance FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property damage Never store flammable or combustible materials on near or in contact with the furnace such as 1 Spray or aerosol cans rags brooms du...

Страница 16: ...lectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory specified media...

Страница 17: ...rientation and cutoff plate location to ensure proper reassembly d Remove screws securing cutoff plate and remove cutoff plate from housing e Remove bolts holding motor mounts to blower housing and slide motor and mounts out of housing f Remove blower wheel from housing g Clean wheel per instructions on degreaser cleaner Do not get degreaser in motor 8 Reassemble motor and blower wheel by reversin...

Страница 18: ...forming any maintenance or service Follow the operating instructions on the label attached to the furnace WARNING Refer to Figure 9 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at external shut off or gas meter 3 Remove control door and set aside 4 Turn electric switch on gas valve to OFF 5 Disconnect the gas pipe from gas valve and remove pipe from the furnace ...

Страница 19: ...rature Only check resistance when the igniter is at room temperature a Using an ohm meter check resistance across both igniter leads in connector b Cold reading should be between 40 ohms and 70 ohms 5 Remove igniter assembly a Using a 1 4 in driver remove the two screws securing the igniter mounting bracket to the burner assembly See Figure 9 b Carefully withdraw the igniter and bracket assembly t...

Страница 20: ...ric switch on gas valve and at external shut off or meter 10 Turn power on at external disconnect fuse or circuit breaker 11 Run the furnace through two complete heating cycles to check for proper operation 12 Install control door when complete Checking Heat Pad Operation If Applicable In applications where the ambient temperature around the furnace is 32_F 0_C or lower freeze protection measures ...

Страница 21: ...erty or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result of the heat transfer process Therefore once it has been operated it cannot be turned off and left off for an extended period of time when temperatures will reach 32_F 0_C or lower unless winterized Follow these procedures to winterize your furnace UNIT COMPONENT DAMA...

Страница 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXE Specifications subject to change without notice 22 440 04 4311 08 Figure 14 Service Label 338312 2 Rev F ...

Страница 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MXE Specifications subject to change without notice 440 04 4311 08 23 Figure 15 Wiring Diagram 338312 2 Rev F ...

Страница 24: ... Sequence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individually hot surface igniter blower speeds FAN if present HEAT COOL Was there a previous status code Go to section below for the flashed status code Does the control respond to W Y1 Y Y2 and G 24V thermo...

Страница 25: ...wer start the component test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTRAL L2 on the control Was 115V present for the 15 second period Check connections and retry If current is near typical value 4 0 6 0μA DC nominal and burners will not stay on replace ...

Страница 26: ...ate the inducer motor IDM until flame is no longer proved e Blower On Delay If the burner flame is proven the blower motor is energized on HEAT speed 25 seconds after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 AMP is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermostat is satisfied the R to W ...

Страница 27: ... When the R to G circuit is opened the blower motor BLWM will continue operating for an additional 5 seconds if no other function requires blower motor BLWM operation 5 Heat pump See Figure 17 Figure 23 for thermostat connections When installed with a heat pump the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles When the R to W ...

Страница 28: ...4 4311 08 Figure 17 ECM Single Stage Furnace with Single Stage Air Conditioner NOTE 9 Figure 18 ECM Single Stage Furnace with Two Stage Air Conditioner NOTE 9 Figure 19 ECM Single Stage Furnace with Two Stage Heat Pump Dual Fuel NOTE 9 Figure 20 ECM Single Stage Furnace with Single Stage Heat Pump Dual Fuel NOTE 9 ...

Страница 29: ...ment Installation Instructions for additional information and setup procedure 2 Outdoor Air Temperature Sensor must be attached in all dual fuel application 3 Refer to ICP thermostat Installation Instructions for additional information and setup procedure 4 When using a Humidity Sensing Thermostat set DEHUMIDIFY OPTIONS to H DE ENRGZD FOR DEHUM 5 HUM 24VAC terminal is 24 VAC and is energized when ...

Страница 30: ...lector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation personal injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions...

Страница 31: ...riable Speed X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 040 40 000 BTU hr 060 60 000 BTU hr 080 80 000 BTU hr 100 100 000 BTU hr 120 120 000 BTU hr INPUT HEAT 14 14 3 16 17 17 1 2 21 21 24 24 1 2 CABINET WIDTH 10 1000 CFM max 14 1400 C...

Отзывы: