INSTALLATION INSTRUCTIONS
Gas Furnace: (F/G)9MVT, (F/G)9MXT, (F/G)9MXE
8
440 01 4001 05
Specifications subject to change without notice.
Figure 3
Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
L12F010
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal in-
jury, death and/or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least
18
−
in. (457 mm) above the floor. The furnace must be
located or protected to avoid damage by vehicles. When
the furnace is installed in a public garage, airplane
hangar, or other building having a hazardous atmo-
sphere, the furnace must be installed in accordance with
the NFPA 54/ANSI Z223.1
−
2012 or CAN/CSA
B149.1
−
2010. (See
Figure 4
)
Figure 4
Installation in a Garage
A93044
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal in-
jury, death and/or property damage.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control
operation will be adversely affected. Never connect re-
turn
−
air ducts to the back of the furnace. (See
Figure 5
)
Figure 5
Prohibit Installations
BACK POSITIONED
DOWNWARD
AIR
RETURN
CUT IN
BACK
BACK POSITIONED
UPWARD
L12F011
Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers
or other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the full
−
heat or full
−
cool position.