INSTALLATION INSTRUCTIONS
Gas Furnace: (F/G)9MVT, (F/G)9MXT, (F/G)9MXE
34
440 01 4001 05
Specifications subject to change without notice.
Table 11 Electrical Data
(F/G)9MVT TWO
−
STAGE, VARIABLE SPEED FURNACES
UNIT SIZE
VOLTS
−
HERTZ
−
PHASE
OPERATING
VOLTAGE
RANGE*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)
}
MAXIMUM
FUSE OR CKT
BKR
AMPS
{
Max*
Min*
0401410
115-60-1
127
104
7.5
10.3
14
36
(11.0)
15
0601714
115-60-1
127
104
9.2
12.4
14
29
(8.8)
15
0801716
115-60-1
127
104
9.2
12.4
14
29
(8.8)
15
0802120
115-60-1
127
104
11.7
15.5
12
37
(11.3)
20
1002120
115-60-1
127
104
11.8
15.6
12
36
(11.0)
20
1202422
115-60-1
127
104
11.8
15.6
12
36
(11.0)
20
(F/G)9MXT TWO
−
STAGE, ECM BLOWER FURNACES
UNIT SIZE
VOLTS
−
HERTZ
−
PHASE
OPERATING
VOLTAGE
RANGE*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)
}
MAXIMUM
FUSE OR CKT
BKR
AMPS
{
Max*
Min*
0401410
115-60-1
127
104
7.5
10.3
14
36
(11.0)
15
0401712
115-60-1
127
104
7.5
10.3
14
36
(11.0)
15
0601412
115-60-1
127
104
7.6
10.3
14
36
(10.7)
15
0601714
115-60-1
127
104
9.2
12.4
14
29
(8.8)
15
0801716
115-60-1
127
104
9.2
12.4
14
29
(8.8)
15
0802120
115-60-1
127
104
11.7
15.5
12
37
(11.3)
20
1002120
115-60-1
127
104
11.8
15.6
12
36
(11.0)
20
1202422
115-60-1
127
104
11.8
15.6
12
36
(11.0)
20
(F/G)9MXE SINGLE
−
STAGE, ECM BLOWER FURNACES
UNIT SIZE
VOLTS
−
HERTZ
−
PHASE
OPERATING
VOLTAGE
RANGE*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)
}
MAXIMUM
FUSE OR CKT
BKR
AMPS
{
Max*
Min*
0401410
115-60-1
127
104
7.4
10.3
14
36
(11.0)
15
0401712
115-60-1
127
104
7.4
10.3
14
36
(11.0)
15
0601412
115-60-1
127
104
7.5
10.4
14
35
(10.7)
15
0601714
115-60-1
127
104
9.1
12.4
14
30
(9.1)
15
0801716
115-60-1
127
104
9.1
12.4
14
30
(9.1)
15
0802120
115-60-1
127
104
11.6
15.5
12
37
(11.3)
20
1002120
115-60-1
127
104
11.7
15.6
12
36
(11.0)
20
1202422
115-60-1
127
104
11.7
15.6
12
36
(11.0)
20
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
Time
−
delay type is recommended.
Length shown is as measured one way along wire path between unit and service panel for maximum 2 percent voltage drop.
Figure 39
Isolation Relay for Humidifiers with Internal Power Supply
24 V
Coil
To Humidifier Leads
To Com/24V Screw Terminal
on Thermostat Strip
To HUM 24 VAC Terminal
On Furnace Control Board
To Humidifier Leads