WIRING DIAGRAM

TROUBLESHOOTING

SYMPTOM

1. Time Switch will not keep

time but dial is turning.

2. Time Switch Dial stops

at ON or OFF tripper.

3. Load is ON at all times -

dial is turning.

4. Dead clock motor. (Clock

motor gears do not rotate)

5. Filter Pump will not operate

as scheduled.

CAUSE(S)

1a. Frequent power outages
1b. Wrong voltage/cycle
1c. Loose clock motor connections

2a. Loose tripper
2b. Bent dial
2c. Defective motor

3a. Welded contacts
3b. Two ON trippers and 

no OFF tripper on dial

3c. Defective mechanism

4a. Defective clock motor

(open coil due to lightning or surge)

4b. Loose clock motor connections
4c. Wrong voltage

5a. Time switches are out-of-sync
5b. One time switch is defective
5c. Faulty wiring
5d. Power outage

CORRECTIVE ACTION

Reset dial
Change clock motor
Check connections

Check/change tripper
Check/change mechanism
Change clock motor

Change mechanism
Change tripper

Change mechanism

Change clock motor

Check connections
Change clock motor

Reset time switches
Replace time switch
Check wiring
Reset time switches