background image

1

Neutral

120VAC 

Input

Hot

2

3

4

Timer Power

Load

Install jumper 

only if timer input 

and load voltage 

are the same

ET1705 configured for SPST, 120 VAC load

1

L2/N

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Load 

2

Timer Power

ET1715 configured for SPDT load switching

1

Line 2

240VAC Input

Line 1

2

3

4

5

6

Line 1

Line 2

Install jumper only if timer input 

and load voltage are the same

Timer Power

Load

ET1725 configured for 240 VAC DPST load 

with jumper set to SIM

1

L2/N

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

ON

Install jumper only if timer input 

and load voltage are the same

OFF

Timer Power

ET1725 configured for pulse SPST load 

with jumper set to PUL

1

L2/N

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Timer Power

Load 

2

ET1725 configured for 2 SPST loads 

with jumper set to IND

1

L2/N

120/208/240/277

VAC Input

Line 1

2

3

4

5

6

Load 

1

Timer Power

Load 

2

ET1725 configured for DPST loads 

with jumper set to SIM

Wiring Diagrams

Programming Overview

By pressing the 

MODE

 button, the Time Switch will cycle through the 

menus necessary for programming the current time, date, and timed 
events.
The basic procedure is to use the 

MODE

 button to move from one 

menu to the next (e.g., DATE, TIME, etc.), the 

+

 or 

– 

buttons for the 

first part of a setting (e.g., MONTH), the 

ENTER

 button to move to the 

next part of the setting (e.g., YEAR), then 

MODE

 to exit and move to 

the next menu. To skip a menu, press 

MODE

 to move ahead.

If you make a mistake, press the 

MODE

 button repeatedly to 

cycle back around to the error, then make the correct entry. 
NOTE:

 DATE and TIME must be set before you can access any 

other programming menus.

Setting Date

1. Press the 

MODE

 button repeatedly until the words SET and

DATE appear in the upper area of the display.

2. Press the 

+

 or 

 buttons to enter the current Month.

3. Press the 

ENTER

 button when the Month is correct to save the

setting. The screen advances to current Date.

4. Again press the 

+

 or 

– 

buttons to enter the current Date,

followed by the 

ENTER

 button.

5. Repeat to set the correct Year.
6. Press the 

MODE

 button to exit and advance to setting the time.

Knockouts

Mounting holes

Mounting

Holes

Knockouts

Mounting

Hole

9.  Insert the wire ends under the proper terminal plates (see

wiring diagrams elsewhere on this page) and tighten the
screws firmly.

10. Connect ground wire to grounding terminal at bottom of enclosure.
11. Replace the plastic insulator on the retaining post.
12.  Remove the battery case by sliding it down as shown by the

arrows, then install 2 AAA alkaline batteries. Make sure the
batteries are pointing in the direction shown.

13. Verify that the display is 

ON

 to make sure the batteries are OK.

 If the display shows scrambled information, press the RESET
button to clear it up.

14. Apply power to the Time Switch.

IMPORTANT:

 Press and hold the 

ENTER

 button, then press the 

RESET

 button. The screen will flash 12:00 AM and MON, and 

timer status is Manual Mode.

NOTE: You must reset the time switch using this procedure 
whenever you change the jumpers.

The Time Switch is now ready for programming.

5.  Mount the enclosure in the desired location using the 3 mounting 

holes provided.

 Position at eye level if possible, providing space to the left of the 
enclosure for the cover to swing open fully, as shown.

6. Replace the mechanism in the enclosure.
7.  Lift the left side of the plastic insulator off the retaining post and

pivot it up and away to expose the terminal strip.

8.  Strip the supply and load wires to 1/2”. 

Use #18 -

#10 AWG wires, rated at least 75°C - COPPER
conductors ONLY.

Отзывы: