 4 OPERATION

Before connecting to the load for the first time the LSU80A has to be set to the nominal voltage of
the load system it is going to supply. The following steps must be followed prior to connecting to
the load. 

Apply   power   to   the   LSU80A   with   load   unconnected.   Power   switch   pressed   to   the   down
position.
Press the RUN button and check the output state RUN LED is lit GREEN and the STOPPED LED
is not lit.
The VOLTAGE display will show the value of output voltage that is currently set.
Use the OUTPUT TRIM  

  

push buttons to set the output voltage display to the load

voltage required. This setting will be remembered when power is removed. Note if you press
and hold either the 



 push buttons the adjustment will be continuous.

Press the stop button and check the RUN LED is not lit and the STOPPED LED is lit.
The voltage display will slowly reduce to zero, or will fall to zero very rapidly if the load is
connected.

At this point the load can be connected.

If any residual voltage is shown on the VOLTAGE display this will reduce very rapidly to zero.
If the load already has a voltage present, such as a battery maintained system then the
VOLTAGE display will show this value.

The following steps are followed upon equipment connection.

Press the START push button and verify the RUN LED is lit and the STOPPED LED is not lit.
The VOLTAGE display will show the output voltage.
The CURRENT display will show the output amps being drawn from the unit.
When the output voltage is no longer required press the STOP push button.

At very high currents the voltage drop in the leads may not provide enough voltage at the
equipment. 

To   overcome   this  high  voltage   drop   the  output  voltage   can   be   trimmed  by   pressing   the
OUTPUT TRIM 



 push buttons to set the desired output. This setting will be remembered

when   power   is   removed.   Note   if   you   press   and   hold   either   the  



  push   buttons   the

adjustment will be continuous.

On battery maintained systems caution must be observed when using the trim feature as not
to overcharge the battery as high voltages will cause some of the current to be passed to the

Doc: DWG1061-11-R2 LSU80A Operators manual.odt

Page 8 of 17

Copyright Material of Intelligent Charging Limited © 2018

Printed On : 17/07/19

Содержание LSU80A

Страница 1: ...oad Support Unit Operators Manual Doc DWG1061 11 R2 LSU80A Operators manual odt Page 1 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 LSU80A LOAD SUPPORT UNIT OPERATORS MANUAL ...

Страница 2: ...panel 7 4 OPERATION 8 5 CALIBRATION 10 5 1 CHECKING PROCEDURE 12 5 1 1 Voltage validation 12 5 1 2 Current validation 12 5 2 ADJUSTMENT PROCEDURE 13 5 2 1 Voltage adjustment 13 5 2 2 Current adjustment 13 6 SPECIFICATIONS 15 7 PRODUCT DISPOSAL INSTRUCTIONS 16 8 PRODUCT WARRANTY 17 Doc DWG1061 11 R2 LSU80A Operators manual odt Page 2 of 17 Copyright Material of Intelligent Charging Limited 2018 Pri...

Страница 3: ...ON HISTORY Rev Date Description 1 14 07 2014 First write 2 21 07 2015 Rewritten with correct drawings and formatting changes Doc DWG1061 11 R2 LSU80A Operators manual odt Page 3 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 ...

Страница 4: ...egment displays continuously shows both set voltage and current draw Voltage output can be trimmed in approximately 0 1V steps during operation to offset cable drops and or variations in demand which create excessive demand on the backup batteries Output is enabled or disabled by run and stop buttons Internal variable speed fans are employed to ensure the LSU80A operates at a reasonable temperatur...

Страница 5: ... two rubber insulated cables 3m in length The cables are supplied fitted with 8mm ring crimps and keyed mating connectors for connection to the LSU80A The cable has a cross section of 25mm2 per conductor While operating the unit at very high currents the leads should be laid out in such a manner as to aid cooling Doc DWG1061 11 R2 LSU80A Operators manual odt Page 5 of 17 Copyright Material of Inte...

Страница 6: ...se the output voltage to be increased Pressing while the unit is stopped will cause the display brightness to be increased Pressing while the unit is running and providing output power will cause the output voltage to be reduced Pressing while the unit is stopped will cause the display brightness to be increased J Voltage indication While the unit is switched on it will show the voltage present at...

Страница 7: ...f Intelligent Charging Limited 2018 Printed On 17 07 19 SERIAL No INTELLIGENT CHARGING CasC Systems Ltd Ford House Dewing Road Rackheath Ind Est Norwich Norfolk NR13 6PS ENGLAND TEL 44 1603 722770 FAX 44 1603 722771 MAIL sales intelligent charging com CHARGING INTELLIGENT FROM MODEL P N MADEINENGLAND CASC SY STEMS LTD MAINS 115V 240V 50Hz 60Hz 16AMaximum L ...

Страница 8: ...own on the VOLTAGE display this will reduce very rapidly to zero If the load already has a voltage present such as a battery maintained system then the VOLTAGE display will show this value The following steps are followed upon equipment connection Press the START push button and verify the RUN LED is lit and the STOPPED LED is not lit The VOLTAGE display will show the output voltage The CURRENT di...

Страница 9: ...ans will reduce to a low setting and then stop Press the START push button the display will show the voltage that was set It will be noted that the fans will then start up again and run slowly while the PSU units are cooled Once the fans have stopped it is safe to remove power from the unit by moving the switch to the up off position Doc DWG1061 11 R2 LSU80A Operators manual odt Page 9 of 17 Copyr...

Страница 10: ...ibrated ammeter capable of reading up to 80A to one significant digit or a calibrated ammeter shunt and millivoltmeter combination The equipment will need to be connected as shown in the following figures VOLTAGE MEASUREMENT Doc DWG1061 11 R2 LSU80A Operators manual odt Page 10 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 1705 TRUE RMS PROGRAMMBLE MULTIMETER VE...

Страница 11: ...ch will give a steady 50A connected to the LU80A switch on and press the START push button Doc DWG1061 11 R2 LSU80A Operators manual odt Page 11 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 MADE INENGLAND SERIAL No INTELLIGENT CHARGING from CasC Systems Ltd Ford House Dewing Road Rackheath Ind Est Norwich Norfolk NR13 6PS ENGLAND TEL 44 1603 722770 FAX 44 1603 ...

Страница 12: ...age measured on the calibrated voltmeter connected to the output terminals Note if you press and hold either the push buttons the adjustment will be continuous Once complete press the START push button once and verify that it stops flashing and remains steady Press the STOP push button Calibration voltage adjustment is complete 5 2 2 Current adjustment With a load which will give a steady 80A conn...

Страница 13: ...ush button once and verify that it stops flashing and remains steady Press the STOP push button Calibration current adjustment is complete Doc DWG1061 11 R2 LSU80A Operators manual odt Page 13 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 ...

Страница 14: ... voltage then output shuts down recycle AC to reset SHORT CIRCUIT PROTECTION Output latches off recycle AC to reset METER ACCURACY Voltage accuracy 0 2V Current Accuracy 1 0A ENVIRONMENTAL Temp Operating 0 C 40 C Temp Storage 10 C 60 C Humidity 20 90 Non condensing Altitude 0 to 3000 Metres IP Rating Operating IP33 Doc DWG1061 11 R2 LSU80A Operators manual odt Page 14 of 17 Copyright Material of I...

Страница 15: ...s substances and avoid the increasing landfill Product disposal instructions for residential users When you have no further use for it please remove any batteries and dispose of them and the product as per your local authority s recycling processes For more information contact your local authority or the retailer where the product was purchased Product disposal instructions for business users Busi...

Страница 16: ...ully comply with all procedures shown in the literature and product training familiarisation sessions as misuse or failure to follow the instructions may render this warranty void This warranty is not transferable and excludes routine maintenance consumables parts subject to normal wear and tear service maintenance kits and damage caused by misuse or negligence Warranty claims attributable to impr...

Страница 17: ...Load Support Unit Operators Manual This page is intentionally left blank Doc DWG1061 11 R2 LSU80A Operators manual odt Page 17 of 17 Copyright Material of Intelligent Charging Limited 2018 Printed On 17 07 19 ...

Отзывы: