background image

OPERATING MANUAL and INSTALLATION INSTRUCTIONS for

 

Form HW+3250 rev 7.2

 

IntelliCon

®

-

HW+

 

HOT-WATER HEATING SYSTEM ECONOMIZER 

For boilers which also supply domestic hot water through an internal coil, plug in a 
second sensor to 

the ‘Domestic Water Sensor’ connector and mount the sensor on 

the domestic  hot  water outflow-pipe  at the storage  tank, if  present,  or  at the  boiler 
domestic  water  coil  outlet-pipe,  if  no  storage  tank  is  used.    Follow  the  same 
procedure to attach the sensor as used above for the ‘Heating Water Sensor’.  This 
sensor should not be used if the boiler does not heat the domestic hot water. 

In the event that a sensor fails, the controller automatically goes into bypass mode 
and  returns  full  control  of  the  burner  to  the  boiler

’s  operating-control,  the 

‘Power/Normal’ indicator  will  blink, and the  following message  will be displayed  to 
identify the faulty sensor: 

“H SENSOR FAULT” and/or “D SENSOR FAULT”, “SYSTEM BYPASSED” 

If this message appears check and replace the faulty sensor. 

IMPORTANT - READ CAREFULLY 

1.

Failure to follow these instructions may result in damage to the 
system or cause a hazardous condition.

2.

Installer  must  be experienced,  qualified,  and  in  certain  locations,
licensed to work on the system that this control is being installed on. 

3.

After  installation  is  complete, follow  the  check-out  procedure  as 
provided in these instructions to confirm proper system operation.

4.

Intellidyne  is  not  responsible  for  improper  installation  or  any  damages
that may result from improper installation.

5.

Actual wiring may differ from that shown in the diagrams.

6.

Equipment may have controls not shown.

7.

Because the 

IntelliCon

 can operate with different voltages for the power

and control circuits, it has separate common wires for these circuits.  It 
is necessary  that these wires are connected to the proper commons or
the  unit  will  not  function  properly.   

See  the  wiring  diagrams  on  the

reverse side of this sheet for details.

IMPROPER VOLTAGE SELECTION MAY DAMAGE THE UNIT AND VOID THE 
WARRANTY. 

Checkout 

Recheck  wiring  one  last  time  and  make  sure  that  the  temperature  sensor(s)  is 
plugged  into  the  proper  connector(s).    The  sensor(s)  are  only  detected  during 
power-up.    Set  the 

controller’s  switch  to  ‘Off/Bypass’  and  restore  power  to  the 

boiler.    Reset  the  co

ntroller’s switch to ‘On’.  After a brief check of the electronics 

and  displaying  various  parameters  of  the  controller,  the  sensor(s)  will  be  detected 
and the green ‘Power/Normal’ indicator should light continuously.  It is important to 
verify  recognition  of  the  sensors  by  viewing  the  temperature  reading(s),  on  the 
display.  If the installed sensor(s) are not detected, the  IntelliCon controller will not 
function  properly.   If the green indicator is blinking  or if  the display  does not  verify 
the  installed  sensor(s),  turn  the  controller 

‘Off’  and  check  the  sensor  installation.  

After  the  sensor-check,  depending  upon  the  temperature  of  the  boiler  water  at 
power-up, the controller will go into one of its various modes.  If the controller went 
into  ‘STANDBY  MODE’; 

note  the  operating-control  setting

  and  force  a  burner 

call  by  temporarily  adjusting  the  operating-control  higher  and  verifying  the  change 
of  mode  of  the  controller 

to  the  ‘ECONOMIZER  MODE’,  ‘HEATING  MODE’  or 

‘HEATING/LOLIM’ mode. If the controller went in to the ‘ECONOMIZER MODE’ you 
can  either  wait  for  the  water  temperature  to  drop  and  for  the  controller  to  go  into 
‘HEATING  MODE’  or  ‘HEATING/LOLIM’,  or  by  removing  a  sensor  plug,  the 
controller will go into bypass mode, and the burner should fire shortly thereafter.  If, 
after  adjusting  the  operating-control,  the  controller  went  directly  into 

‘HEATING 

MODE

’  or  ‘HEATING/LOLIM’  the  burner  should  fire  shortly  thereafter.  The  burner 

should  run  continuously  until  the  call  from  the  operating-control  is  satisfied.  Once 
satisfied,  the  burner  should  stop  firing  and  the  controller  should  go  into  the 
‘STANDBY  MODE’.  The  controller  and  burner  following  the  above  sequence 
indicates  a  properly  wired  and  functioning  control.   

Make  sure  that  if  the 

operating-

control was previously adjusted, to return it to its’ previous setting.

  

If the burner fires for a brief second then stops (even though the operating-control is 
calling  for  the  burner  to  run)  is  likely  caused  by  the  Yellow  and  Red  wires  being 
reversed.    If  the  controller  does  not  come  out  of 

“STANDBY  MODE”  when  the 

boiler’s operating-control is calling for the burner to run, the unit is wired incorrectly. 
The  likely  cause  in  this  situation  is  either  a  reversed  Yellow  and  Red  wire  or  an 
improperly  connected 

‘common’  connection  for  the  control  circuit.    See  the 

IMPORTANT note (number 7) above. 

Service and Troubleshooting 

After  Installation  and  Checkout,  the  controller  does  not  require  maintenance  and 
will provide years of trouble free operation.  The unit may be taken out of the circuit 
at  any  time  by  placing the switch  to 

the ‘Off/Bypass’ position.  In this position, the 

unit has no effect on the system and  the burner is controlled  as it was prior to the 
IntelliCon 

controller’s installation.  This allows service personnel to troubleshoot or 

work on the system without the controller intervening. 

If  at  any  time  the  Power/Normal  light  on  the  front  panel  blinks  continuously,  a 
sensor  is  not  operating  properly  and  The 

IntelliCon

®

  controller  has  automatically 

gone into ‘bypass mode’. 

If  the  message  “TIMER  FAULT”  is  displayed  the  switch  should  be  placed  into  the 
OFF/Bypass position and service called. 

If the burner is running and the control is in “STANDBY MODE” a problem exists and 
service should be contacted. 

PROGRAMMING 

The following parameters may be changed in the field by following these instructions. 

Pre-Purge time, Temperature indication in either degrees F or C, Heating Water 
Low-Limit,  Domestic  Water  Low-Limit,  Maximum  Economizer  Hold-Off  Time, 
Standby-Timer  Override,  and  whether  or  not  Standby  Time,  Economizer  Time, 
Burner  Run-Time,  and  A  SAVINGS  are  Displayed. 

  The  system  may  also  be 

returned  to  factory  default  values  and  the  Average  Savings,  Economizer  Time,  and 
Run-Time accumulators may be cleared. 

All  of  the  default  values  have  been  carefully  selected  to  result  in  the  greatest 
savings  for  the  broadest  scope  of  heating  system  applications.    Individual 
system  requirements  may  require  changes.    Please  note  that  all  of  these 
programmable  parameters  will affect the amount of savings.   Prudent changes 
are strongly advised. 

It  is  very  important  that  if  there  is  any  kind  of  a  delay    (more  than  fifteen  (15) 
seconds),  from  the  time  that  the  Operating-control  calls  for  the  burner  to  start 
and  the  burner  actually  starts,  that  this  time  delay  value  be  entered  into  the 
controller  as  a  Pre-Purge  time  (e.g.  actual  pre-purge  timer,  Flue  Damper 
interlock, etc.). If there is a delay and the correct value is not programmed into 
the controller, the savings calculations will be incorrect. 

ALL  PROGRAMMING  IS  ACHIEVED  BY  PLUGGING  AND  UN-PLUGGING  A 
WATER  TEMPERATURE  SENSOR  INTO  THE  APPROPRIATE  SENSOR-JACK. 
THE  SENSOR  MUST  BE  CONNECTED  TO  THE  CABLE  OR  THIS  WILL  NOT 
WORK!  

THIS  SOFTWARE  REVISION  HAS  A  MORE  ADVANCED  PROGRAMMING 
METHOD.    THE  UPPER  (HEATING  WATER)  SENSOR  JACK  IS  USED  TO 
ANSWER “YES” OR TO INCREASE A VALUE. THE LOWER (DOMESTIC WATER) 
SENSOR JACK IS USED TO ANSWER 

“NO” OR TO DECREASE A VALUE.  ALL 

“YES/NO”  QUESTIONS  ARE  ENDED  WITH  A  “?”.    ENTERING  A  “YES”  TO  A 
QUESTION, WILL CHANGE THE ITEM FROM ITS CURRENT SETTING. TO THAT 
WHICH IS SHOWN ON THE SCREEN. 

ANSWERING “NO” OR ALLOWING THE 7 

SECOND  DELAY  TO  EXPIRE  WILL  ADVANCE  YOU  TO  THE  NEXT  SELECTION.  
WHEN  CHANGING  A  TIME  OR  TEMPERATURE  VALUE  YOU  WILL  PLUG  INTO 
THE  TOP  JACK  TO  INCREASE  THE  VALUE  OR  THE  LOWER  JACK  TO 
DECREASE  THE  VALUE.    REMOVE  THE  SENSOR  PLUG  WHEN  THE  DESIRED 
VALUE IS REACHED, AND THE VALUE WILL BE SAVED. IF YOU DO NOTHING, 
AND  ALLOW  THE  7  SECOND  DELAY  TO  EXPIRE,  THE  PROGRAM  WILL 
ADVANCE YOU TO THE NEXT PROGRAMMABLE PERAMETER.   

YOU  HAVE  SEVEN  (7)  SECONDS  TO  RESPOND  TO  ANY  OF  THE 
DISPLAY PROMPTS.  

PROGRAMMING MAY  BE  STOPPED  OR  ABORTED  AT  ANY  TIME  BY 
TURNING THE CONTROLLER OFF.  ANY PARAMETERS THAT WERE 
CHANGED WILL REMAIN CHANGED. 

Entering Configuration Mode: 
To  enter  configuration  mode,  the  controller  must  be  powered  up  without 
any sensors connected. When prompted insert a water sensor plug into the 
TOP sensor  jack  (HEATING WATER).  To confirm,  remove  the  plug  when 
prompted.    The  unit  will  then  indicated  that  i

t  has  entered  “**Config 

Mode**”.  After  a  4  second  delay  the  display  will  advance  to  the  first 
programmable parameter. 

Any  changes  made  to  a  programmable  parameter  will  be  confirmed 
by indicating “ **DATA SAVED**”. 

 This is a Yes/No type of parameter

This parameter will reset all of the programmable parameters to factory defaults. It will 
not clear any of the timer/counter accumulators. Plug into the top jack to perform the 
desired  function,  or  plug  into  the  lower  jack  to  answer  NO  (and  proceed  to  the  next 
parameter, or allow the 7 second delay to expire and proceed to the next parameter). 

 This is a Yes/No type of parameter 

This parameter  will  allow  you  to view  all of the time  and counter  accumulators. Plug 
into the top jack to perform the desired function, or plug into the lower jack to answer 
NO  (and  proceed  to  the  next  parameter,  or  allow  the  7  second  delay  to  expire  and 
proceed to the next parameter). 

 

RESET DEFAULTS? 

 

VIEW COUNTERS? 

Intellidyne LLC  •  5507 Nesconset HWY STE10 PMB148  •  Mount Sinai, NY 11766, USA  •  Email [email protected]

Отзывы: