AC LINES: CONNECTION DIAGRAM
OPTIMA-T10 & RT10 230 and OPTIMA-T10 & RT10 with optional ISOTX.
OPTIMA-T10 RT10 6K/10K
UPS with 220V output directly from inverter
IMPORTANT:
It is recommendable all output neutral lines are connected directly without breakers. It is important neutral
lines are connected always since neutral is an important electrical reference for all UPS of the parallel system. In battery
mode the lack of connection of output neutrals could generate synchronization errors between UPS. In case neutral lines
are connected through breakers, there is a possibility of a wrong operation of breakers that forces error states.