EN-IEC 62040-1: EXTERNAL BACKFEED PROTECTION 

 

In case back-feed protection is required, an automatic external protection circuitry must be installed to provide this kind of protection to 

comply with EN-IEC 62040-1. This external protection device is not included with this product. External back-feed device must be rated to 

drive maximum UPS current. 

 

Back-feed protection system must be automatic and must assure to avoid internal voltage of the UPS can feed input AC lines under battery 

mode. Under normal conditions, UPS internal design avoids this kind of situations happens. However, a failure in the UPS internal Bypass 

Switch could allow output voltage of the UPS inverter could be driven to the AC input lines through internal bypass lines. In battery mode, 

an operator working on input AC terminals does not expect to find voltage in input lines of the UPS so that a back-feed failure could 

represent an electrical shock risk for the operator.  

 

An effective back-feed design must be able to open automatically all UPS AC input lines when AC main is power-off. 

 

*** External Back-feed protection device is not included with this product. 

 

In below figure a typical automatic back-feed protection design is described. 

 

 

 

C:

   2 Poles Contactor. Normally Open. Coil voltage same tan UPS input AC voltage. Max. current similar to max. UPS input current. 

R: 

  AC Relay. Normally Open.  

F:

   General purpose AC fuses. Operating voltage similar to UPS input AC voltage. 

 

 

WARNING LABEL: 

We strongly recommend to place warning labels in all electrical boards related to UPS circuit lines to indicate an UPS is connected to the 

board. This is because a dangerous voltage could be feed by the UPS on the electrical board even AC main service is out of order. 

 

Label design should include following information: 

 

 

VOLTAGE BACKFEED RISK 

 UPS CONNECTED TO THIS CIRCUIT 

 Before working on this circuit: 

 * Isolate UPS 

 * Check for dangerous voltage in all circuit terminals.

 

 

 

 

Содержание (UL)

Страница 1: ...10K UL www xmart ups com VER 190731 GA2UL ENG 1 VER 1907 31 ENGLISH USER MANUAL OPTIMA T10 6K 10K UL UPS ONLINE DOUBLE CONVERSION TOWER OPTIMA T10 06K 230V UL OPTIMA T10 10K 230V UL OPTIMA T10 06K IS...

Страница 2: ...d or distributed totally or partially without written approval of XMART XMART can introduce modifications in their products or manuals without further notice XMART is not responsible of mistakes or mi...

Страница 3: ...SAFETY QUALITY AND PERFORMANCE STANDARDS 3 PRODUCT DESCRIPTION 4 INSTALLATION 5 OPERATION MODES 6 OPERATION INTERFACE KEYBOARD LCD 7 UPS CONFIGURATION 8 START UP 9 ERROR ALARMS CODES TROUBLESHOOTING 1...

Страница 4: ...Bracelets etc because they could contact conductive parts and components inside the UPS and this might cause discharges and or short circuits Make sure using tools properly isolated to avoid electric...

Страница 5: ...TRANSPORTATION IEC EN 300019 2 2 Class 2 3 WARNING Modifications made on the product or the use of this product as a part of a more complex system not expressly approved by the party responsible for c...

Страница 6: ...cations This product has been designed to operate under hostile electrical conditions but offering a reliable performance with outstanding features and characteristics It is 100 compatible to operate...

Страница 7: ...f electrical shock because high DC voltage External battery banks must be revised before connecting them to UPS to confirm their DC voltage is compatible with this UPS DC polarity of the Battery bank...

Страница 8: ...to find voltage in input lines of the UPS so that a back feed failure could represent an electrical shock risk for the operator An effective back feed design must be able to open automatically all UPS...

Страница 9: ...rise over 35 C Batteries life shortens over 25 C Installation site must be dry fresh free of dust fibers and any other objects conductors or not suspended in the air that could get into the UPS thru...

Страница 10: ...with the UPS DC voltage before making DC connections In case electrical information given by this manual does match with information provided by product labels user must consider information on labels...

Страница 11: ...tput 3000W 6 KVA Max Nominal Current 33A Output Voltage 120Vac Output Voltage 120Vac ISOTX Wiring min 10AWG 6mm2 AC Breaker 80A Curve D Breaker per Output 40A Curve D Max Nominal Current 60A Max Nomin...

Страница 12: ...s provide 3KVA maximum AC lines must be connected to electrical board using cables with required gauge INPUT OUTPUT CONNECTIONS First of all connect ground terminals to system earth Ground must always...

Страница 13: ...parate 120Vac outputs that can be wired in 3 different configurations 2 individual outputs120V Each output can drive 50 of total UPS power 1 output 120V By connecting 2 separate outputs in parallel Th...

Страница 14: ...rallel connection also allows system can grow in power by adding extra units For working parallel as a parallel system all units must share same AC input and AC output Some control cables must be also...

Страница 15: ...ommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all UPS of the par...

Страница 16: ...UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since...

Страница 17: ...RTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always since neutral is an important electrical reference for all...

Страница 18: ...rd UPS must be connected following same principle IMPORTANT It is recommendable all output neutral lines are connected directly without breakers It is important neutral lines are connected always sinc...

Страница 19: ...GA2UL ENG 19 CONTROL CABLES CONNECTION DIAGRAM Parallel system requires all UPS share some important control information by parallel control cables There are 2 kind of control cables SHARED CURRENT P...

Страница 20: ...AC input on its terminals If bypass mode is not enabling UPS will simply light its LCD Outputs will keep powered off 2 Bypass mode is adopted as soon as a problem is detected in its internal circuitr...

Страница 21: ...s powered by AC input service so any problem in main service will affect directly to the load PROCEDURE FOR ACTIVATING EXTERNAL BYPASS 1 Confirm bypass mode is allowed in UPS configuration Check input...

Страница 22: ...feeds rectifier input UPS output is generated by inverter BATTERY MODE A Input indicator at bottom left corner A shows Battery voltage since there is no valid AC input detected B Output indicator dis...

Страница 23: ...UPS will not turn on ENTER When UPS is in configuration mode this key operates as ENTER OFF ESCAPE UPS TURN OFF Press for 2 seconds to turn UPS off SCAPE When UPS is in configuration mode this key ope...

Страница 24: ...INFORMATION It displays AC output voltage Output frequency in Hz ALARMS ERRORS This section of the LCD displays active alarms and errors providing codes and descriptive symbols This section also show...

Страница 25: ...ed 5 BYAPSS internal static line active 6 ECO mode active 7 Audible alarm beep muted OUTPUT POWER METER This area displays graphically by a 4 segments bar the power supplied by the UPS 25 Supplied Pow...

Страница 26: ...y to navigate or changing parameters value ON ENTER Used as ENTER key to confirm modifications MUTE DOWN Used as key to navigate or changing parameters value AVAILABLE FUNCTIONS UNDER EACH OPERATION M...

Страница 27: ...put frequency If ATO is selected output frequency will be set by input frequency read when UPS started by first time from 46 to 54 Hz will set to 50Hz from 56 to 64 Hz will set to 60Hz IMPORTANT 1 If...

Страница 28: ...r any condition PAR 03 ENA Enable Bypass allowed in both manual and automatic DIS Disable Automatic Bypass allowed but manual is prohibited Set values with keys 09 MAXIMUM RUNTIME This function sets m...

Страница 29: ...or increasing SUB for decreasing Set values with keys THIS FUNCTION ONLY WORKS IF UPS IS CONNECTED IN PARALLEL 17 CHARGER CURRENT ADJUSTMENT BOTTOM PARAMETER Charging current can be selected 1A 2A 3A...

Страница 30: ...nci n de Convertidor de Frecuencia Desactivado ON ON Encendido OFF OFF Apagado ENA Enable Habilitado DIS Disable Des habilitado ATO Auto mode Modo Autom tico SUB Subtract Disminuir ADD Add Aumentar PA...

Страница 31: ...Power input lines ON at electrical board by setting Circuit Breaker to ON 3 Put Battery Bank breaker to ON in case UPS has XBAT connected 4 Put AC INPUT Breaker to ON in UPS rear panel 5 LCD of UPS mu...

Страница 32: ...ARALLEL UPS Check all previous requirements are complied If not do nott try to start ups parallel UPS 1 Check parallel UPS are powered OFF and turned OFF 2 Check all input breakers are in OFF position...

Страница 33: ...tery backup of remaining UPS could not be enough to keep system running before reconnecting removed unit External breakers could be activated randomly during operation so system could be tripped 3 The...

Страница 34: ...consequence of detecting 3 overloads in less than 30 minutes OR MBS cover REMOVED 1 beep s ALARMS ALARM CODES Battery Disconnected 01 Battery overvoltage 07 Los Battery 08 Overload at UPS output 09 F...

Страница 35: ...etected at inverter output 24 COMMUNICATION CAN error 31 DESBALANCED CURRENT IN PARALLEL SYTEM 36 OVER TEMPERATURE 41 CPU COMMUNICATION ERROR 42 OVERLOAD Detected at UPS output 43 Overload on inverter...

Страница 36: ...SOLUCION 01 02 03 04 11 12 13 24 6A 6B 6C 60 63 Turn off and power off UPS Disconnect all equipment connected to UPS Restart UPS with no loads connected to its output If UPS starts up without problems...

Страница 37: ...e Batteries are located inside of the UPS or in external battery cabinets Original batteries must be replaced by new batteries with same technology VRLA and specifications 12VDC and similar capacity i...

Страница 38: ...tion service partners reserve the right to charge handling fee if returned product is free of failure or it is out of warranty because any of the reasons described in this warranty 6 If product is out...

Страница 39: ...uxiliary output IEC 220Vac 9 Parallel Control Ports Shared Current 3 AC Input Breaker 10 Parallel Control Ports Parallel Control 4 Maintenance Bypass Switch MBS 11 FAN Power stage 5 DC connector for e...

Страница 40: ...recarga 90 Charging VDC Voltaje del cargador Floating Temperature Compensation Compensaci n Temp Shutdown battery Voltage Voltaje DC Apagado 50 mV 12V 9AH x 40 pcs 20pcs x 2 240VDC 4 H 90 3 5 H 90 12...

Страница 41: ...CF function is activated El modo bypass se anula automaticamente cuando se activa la funci n CF N5 Recharing time based on previous full discharging cycle 10 to 20 min Tiempo de recarga basado en cic...

Страница 42: ...INDEX USER MANUAL OPTIMA T10 6K 10K UL www xmart ups com VER 190731 GA2UL ENG 42 NOTAS...

Страница 43: ......

Страница 44: ...USA Headquarters 10540 NW 26th St Doral FL 33172 USA EUROPE Headquarters Ave Can Bordoll 60 Nave 4 Sabadell 08202 Spain Latin America Headquarters Santiago de Chile 8330669 Chile CHILE...