14.04-4
CAUTION: Dangerous voltages may be present. The 2100-D has no user serviceable parts.
Protective enclosure only to be opened by qualified personnel.
Remove ALL power sources before removing protective cover.
2100-D
Rev1C
Specifications.
Inputs:
12 Individually Isolated Inputs with LED Indication of Each Input.
-Input Voltage
5~30Vdc.
-Threshold
4.6V typical.
-Load
@ 5V
1.1mA per Channel.
@ 12Vdc
4.2mA per Channel.
@ 24Vdc
9.6mA per Channel.
-Frequency -Low
0~20Hz. Debounce - 50msec.
-High
0~500Hz. Debounce - 2msec.
Outputs:
12 Individually Isolated Relays with LED Indication of Each Output.
-Functions
12 Relay Contact - 10 Change Over; 2 Normally Open.
-Contact Material
Silver Alloy
-Relay Ratings
Maximum Rating
Approved to Standard
250Vac, 2A
UL
125Vac, 2A
CSA
110Vdc, 0.3A
30Vdc, 2A
1/6hp, 250Vac
1/10hp, 125Vac
-Number of Operations
2 x 10
5
Min, at 1A, 250Vac Resistive Load.
Comms:
-Protocols
-Baud Rate
-Format
RS422
or
RS485.
Selectable 2400, 4800, 9600. (Default = 9600).
8 bit, No Parity, 1 Stop.
Power :
-H
-M
85~264Vac/dc; 50/60Hz; 10VA.
23~90Vdc; 10VA.
Refer to ‘
2100-D H1 Power Supply Settings’
for voltage selection instructions.
Safety and EMC Compliances:
EMC Compliances
Emissions EN 55022-A. Immunity EN 50082-1.
Safety Compliance
EN 60950.
Mains Isolation
250Vac.
Mains Isolation Test Voltage
-To all Inputs & Outputs:
3000Vac 50Hz for 1min.
-To Earth
1500Vac 50Hz for 1 min.
Input/Output Isolation Test Voltages
-Between Inputs
1000Vdc for 1min.
-Comms to Inputs
1000Vdc for 1min.
-Relay Outputs to All Other Terminals:
3000Vac 50Hz for 1min.
-Between Relay Outputs
1500Vac 50Hz for 1min.
General Specifications:
(Unless otherwise stated in other input specifications.)
RF Immunity
<±1% Effect FSO Typical.
Operating Temperature
0~60C.
Storage Temperature
-20~80C.
Operating Humidity
5~85%RH Max. Non-Condensing.
Housing
-Material
ABS Inflammability V0 (UL94)
-Dimensions
L=195, W=120, H=70mm.
-Mounting
35mm Symmetrical Mounting Rail.
-Weight
900g. Includes Packaging.
Note 1. Contact INTECH INSTRUMENTS for more detailed programming information.
Product Liability.
This information describes our products. It does not constitute guaranteed properties and is not intended to affirm the suitability
of a product for a particular application. Due to ongoing research and development, designs, specifications, and documentation are subject to
change without notification. Regrettably, omissions and exceptions cannot be completely ruled out. No liability will be accepted for errors, omis-
sions or amendments to this specification. Technical data are always specified by their average values and are based on Standard Calibration
Units at 25C, unless otherwise specified. Each product is subject to the ‘Conditions of Sale’.
Warning: These products are not designed for use in, and should not be used for patient connected applications. In any critical installation
an independant fail-safe back-up system must always be implemented.