Warning
:
When changing the A16 or 2300 station number (Polling Address), the inputs do not automatically
reconfigure. They will still poll the old address.
So if you change the modbus polling address under Device, you need to also refresh the input settings.
The quickest way to do that is to simply go to each input, change of the inputs to another input (under “Input
Location” on the
Ezeio), - Click on ‘Save Changes’ - change back and save again.
This will refresh the setting, and it will poll the correct A16 station.
Calibration Offset adjustment during a calibration survey
Instructions for applying an offset (zero) adjustment :
Example 1.
In this example, the temperature on the Eze is reading 0.5°C low.
A +0.5°C offset needs to be applied to correct the error :
------------------------------------------------------------------------------------------------------------------------------------
Type +0.5 as shown here, , to the
end of the existing calibration value.