background image

© Intatec Ltd 2009

7

Commissioning

2. Commissioning the temperatures must be carried out using a suitably calibrated thermometer – 

preferably a digital thermometer. The sensing part of the thermometer probe must be fully submerged in
the water when testing.

3. The valve must be commissioned taking into consideration any fluctuations, which may occur within 

the system due to simultaneous demands.  It is advisable that any outlets which are connected to the 
same supply as the shower valve are open during setting of the mixed water temperature. It is 
advisable to ensure that the water temperatures are established before any attempt to commission.

4. Once the supply temperatures are stable and the normal operating conditions are established, the 

shower valve can be commissioned. The following sequence should be followed when commissioning 
the valve;

4.1 The first step in commissioning a thermostatic shower valve is to check the following:

• The designation of the thermostatic shower valve matches the application
• The supply pressures are within the valve’s operating range.
• The supply temperatures are within the valve’s operating range.
• Isolating valves (and ‘Y’ strainers preferred) are provided.

4.2 If all these conditions are met, proceed to set the temperature as stipulated in the manufacturer’s 

installation instructions.

4.3 Measure and record the temperature of the hot and cold water supplies at the connection to the 

valve.

4.4 Measure and record the temperature of the water discharging from the valve. 

4.4 Isolate the cold water supply to the valve and monitor the mixed water temperature.

4.6 Measure and record the maximum mixed water temperature and the final temperature.  The final 

temperature found during the test should not exceed the values quoted.

4.7 Record all the equipment used during the commissioning. 

4.8 The mixed water temperature at the terminal fitting must never exceed 2˚C above the set 

temperature.

5. If the mixed water temperature exceeds the recommended temperature of 41˚C by 2˚C or does not 

reach 41˚C the shower valve can be adjusted as follows:

5.1 With stable supply conditions remove the temperature control knob. 

5.2 Rotate the temperature control knob by one spline clockwise to increase the temperature and one 

spline anticlockwise to reduce it.

5.3 Measure the water discharging from the shower.

5.4 Repeat 5.2 until the desired temperature is stablised and record the temperature.

5.5 Repeat 4.4 and 4.5

5.6 Secure the temperature control knob with the retaining screw and re-fit the cover.

6. The above information must be recorded and updated on every occasion when any 

work is carried out on the valve.

Содержание 10019CP

Страница 1: ...tion as accurate as possible We cannot accept any responsibility should it be found that in any respect the information is inaccurate or incomplete or becomes so as a result of further developments or...

Страница 2: ...ters and unbalanced supplies i e cold mains tank fed hot They are not suitable for non modulating combination boilers Designated Pressure LP HP Max Static Pressure 10 bar Temperature Stability 2 C Inl...

Страница 3: ...o a solid wall Cut a channel into the wall for the supply pipes allowing sufficient depth to position the concealing plates to as shown on the finished tiled surface Connect the supply pipes to the va...

Страница 4: ...out of the body If any of the O ring seals or the thermostatic element is blocked or damaged they must be replaced Using neutral silicon grease re lubricate the internal moving components of the valve...

Страница 5: ...on is required when the thermostatic shower valve is used in a TMV2 Applications under the requirements of BS EN 1111 1999 Sanitary tapware Thermostatic Mixing Valve PN 10 General Technical Specificat...

Страница 6: ...nstaller of the thermostatic shower valve must comply with the requirements of the Water supply Water Fittings Regulations 1999 and also be aware of their responsibility and duty of care to ensure tha...

Страница 7: ...s and strainers 9 The fitting of isolation valves is required as close as is practicable to the water supply inlets of the thermostatic shower valve 10 The fitting of strainers is recommended as close...

Страница 8: ...are met proceed to set the temperature as stipulated in the manufacturer s installation instructions 4 3 Measure and record the temperature of the hot and cold water supplies at the connection to the...

Страница 9: ...no significant change to the set outlet temperature 2 C or less from the original settings and the fail safe shut off is functioning then the valve is working correctly and no further service work is...

Отзывы: