CLS 24.1/SV
Montage- und Betriebsanleitung
CLS 24.1/SV
Mounting and Operating Instructions
41
10.4. Programming
The module is programmed via the serial interface in the
CLS system with a one-to-one cable and a terminal pro-
gram, such as HyperTerminal from Microsoft. To do this,
the RTG/RS232 switch must be set to RS232 in the CLS.
After launching
HyperTerminal
(Start
Programs
Accessories
Communications)
the first thing to
do is create a new
connection.
In the following dia-
log window, select
the serial interface
under "Connect
using", which is used
to communicate with
the InoWeb mod-
ule. You will need a
1-to-1 modem cable
to do this.
Then establish the
connection settings
to communicate
with the InoWeb
module. Enter the
following values:
Bits per second = 9600
Data bits
= 8
Parity
= None
Stop bits
= 1
Flow control
= None
10.4. Programmierung
Die Programmierung des Moduls erfolgt über die serielle
Schnittstelle im CLS-System mit einem eins-zu-eins Kabel
und einem Terminalprogramm wie beispielsweise Hyper-
Terminal von Microsoft. Dabei muss der Schalter RTG/
RS232 in der CLS auf RS232 gestellt werden.
Nach dem Start von
HyperTerminal
(Start
Pro-
gramme
Zubehör
Kommunikation)
muss als erstes eine
neue Verbindung
angelegt werden.
Im folgenden
Dialog wird im
Auswahlfeld “Ver-
binden über“ die
serielle Schnittstelle
ausgewählt, die für
die Kommunikation
mit dem InoWeb-
Modul genutzt
wird. Dazu wird ein
1-zu-1 Modemka-
bel benötigt.
Anschließend wer-
den die Anschlus-
seinstellungen für
die Kommunikation
mit dem InoWeb-
Modul eingestellt.
Folgende Werte
sind einzutragen:
Bits pro Sekunde = 9600
Datenbits
= 8
Parität
= Keine
Stoppbits
= 1
Flusssteuerung = Kein