background image

26

nection pipe with insulating pipe, and

insulating pipe

1. Connect the drain hose to the outlet pipe of

outlet

pipe

drain hose

drain hose

tape

outlet pipe

drain hose

insulating pipe

Add insulating pipe in the indoor

The plastic expansion particles are

1. Open the panel, remove the screw

on the wiring cover and then take

wiring cover

screw

panel

Step seven: connect wire of indoor unit

4. Wrap the indoor pipe and joint of con-

    then wrap it with tape.

Step six: install drain hose

Installation of indoor unit

torque wrench

open-end 
wrench

indoor pipe

pipe

union nut

Hex nut diameter Tightening torque (N.m)

Φ 6

Φ 9.52

Φ 12
Φ 16

Φ 19

30~40
45~55
60~65
70~75

15~20

indoor unit.

2. Bind the joint with tape.

Note:

drain hose in order to prevent
condensation.

not provided.

down the cover.

©2015 Innovair Corporation.  All Rights Reserved.

www.innovair.com

Содержание VWM10H25

Страница 1: ...osing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please contact the local agent or visit www innovair com or sent email to info innovair com for electronic version 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 2: ...ection of installation location 22 Requirements for electric connection 23 Installation Installation of indoor unit 24 29 Check after installation 29 Test and operation Test operation Attachment 30 Pipe expanding method Configuration of connection pipe 32 Content Wired Controller 33 This appliance is not intended for use by persons including children with reduced physical sensory or mental capabil...

Страница 3: ...d could result in death or serious injury Indicates a hazardous situation that if not avoided may result in minor or moderate injury Indicates important but not hazard related information used to indicate risk of property damage Indicates a hazard that would be assigned a signal word WARNING or CAUTION 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 4: ...enance shall not be made by children without supervision years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Do not wash the air conditioner with water to avoid electric shock After removing the filter ...

Страница 5: ...tioner and disconnect power immediately and then If the air conditioner operates under abnormal conditions it may cause malfunction electric shock or fire hazard Do not spill water on the remote controller otherwise the electric shock or damage Please contact dealer when you need to repair air conditioner Do not repair air conditioner by yourself It may cause objects It may cause damage or persona...

Страница 6: ...tioner An all pole disconnection switch having a contact separation Must follow the electric safety regulations when installing the unit grounding wire of power socket Properly connect the live wire neutral wire and any work related to electricity and safety Be sure to cut off the power supply before proceeding Including an circuit break with suitable capacity please Air Conditioner should be prop...

Страница 7: ...nal wiring regulations requirement of NEC and CEC by authorized personnel only Precautions WARNING wire which can t be used for other purposes The grounding resistance should comply with national electric safety regulations The air conditioner is the first class electric appliance It keep the interconnection cable away from the copper tube The temperature of refrigerant circuit will be high please...

Страница 8: ...another must be installed in the line For the air conditioner without plug an circuit break Select a location which is out of reach for children and For the air conditioner with plug the plug should be Working temperature range NOTICE 5 Indoor side DB WB Outdoor side DB WB Maximum cooling 26 7 19 4 46 1 23 9 Maximum heating 26 7 23 9 18 3 The temperature range for operating the unit with electric ...

Страница 9: ...let panel aux button horizontal louver air outlet heating indicator temp indicator cooling indicator power indicator receiver window drying indicator display remote controller NOTICE Actual product may be different from above graphics please refer to actual products 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 10: ... TEMP button TURBO button LIGHT button SLEEP button TIMER ON TIMER OFF button CLOCK button Send signal Turbo mode Set temperature Set time TIMER ON TIMER OFF Child lock Up down swing Set fan speed X fan mode Light Temp display type Set temp Outdoor ambient temp Indoor ambient temp Sleep mode Clock Heat mode Fan mode Dry mode Cool mode Auto mode Operation mode 2015 Innovair Corporation All Rights R...

Страница 11: ... Press or button to adjust set temperature Press FAN button to adjust fan speed Press button to adjust fan blowing angle Cooling only unit won t receive heating mode signal If setting heat mode with remote controller press ON OFF button can t start up the unit Note For preventing cold air after starting up heating mode indoor unit will delay 1 5 minutes to blow air actual delay time is depend on i...

Страница 12: ... be available When air conditioner receives this signal the air conditioner will blow fan automatically button no display horizontal louvers stops at current position button 3 Press or button once increase or decrease set temperature 1 Holding or button 2s later set temperature on remote controller will tor on indoor unit will change accordingly Temperature can t be adjusted under auto mode When s...

Страница 13: ...ime resumes displaying Cancel TIMER ON Under the condition that TIMER ON is started up press TIMER ON button to cancel it TIMER OFF button TIMER OFF button can set the time for timer off After pressing this button icon disappears and the word OFF on remote controller blinks Press or button to adjust TIMER OFF setting After each pressing or button TIMER OFF setting will increase or decrease 1min Ho...

Страница 14: ... the unit There is no display in the remote controller Only for the models whose indoor unit has dual 8 display When selecting displaying of indoor or outdoor ambient temperature indoor temperature indicator displays corresponding temperature and automatically turn X FAN button 8 Press this button under cool and dry mode to start up x fan function and icon on remote controller will be displayed Pr...

Страница 15: ...press and MODE buttons simultaneously to switch temp erature display between and Introduction for buttons on remote controller Press this button to turn off display light on indoor unit icon on remote controller disappears Press this button again to turn on display light icon is displayed Under COOL HEAT or DRY mode press this button to start up sleep function icon is displayed on remote controlle...

Страница 16: ...ry batteries and make sure the position of polar and polar are correct 3 Reinstall the cover of battery box signal sender battery Cover of battery box remove reinstall NOTICE During operation point the remote control signal sender at the receiving window on indoor unit The distance between signal sender and receiving window should be no more than 8m and there should be no obstacles between them or...

Страница 17: ...ration in details are as below WARNING NOTICE Turn off the air conditioner and disconnect the power before cleaning the air conditioner to avoid electric shock Do not wash the air conditioner with water to avoid electric shock Do not use volatile liquid to clean the air conditioner Clean surface of indoor unit When the surface of indoor unit is dirty it is recommended to use a soft dry cloth or we...

Страница 18: ... certain Use dust catcher or water to the water below 45 to clean it and then put it in a shady and cool place to dry panel cover tightly 15 operation environment clean frequency can be increased WARNING 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 19: ...inlets and air outlets are blocked 2 Check whether air switch plug and socket are in good condition 4 Check whether mounting bracket for outdoor unit is damaged or corroded If yes please contact dealer 5 Check whether drainage pipe is damaged 1 Disconnect power supply 3 Check whether mounting bracket for outdoor unit is damaged or corroded If yes please contact dealer NOTICE Checking before use se...

Страница 20: ...e plug after about 3min and then turn on the unit again Signal receiving range is 8m Remove obstacles Select proper angle and point the remote controller at the re ceiving window on indoor unit Check the batteries If the power of batteries is too low please replace them Take the remote controller close to indoor unit Turn off the fluoresent lamp and then try it again Check whether remote cont roll...

Страница 21: ... high Because indoor air is cooled rapidly After a while indoor temperature and humidity will be decrease and mist will disappear Phenomenon Check items Solution Set temper ature can t be adjusted Unit is operating under auto mode Temperature can t be adju sted under auto mode Please switch the operation mode if you need to adjust temperature Your required temperature exceeds the set temperature r...

Страница 22: ...ting mode is turned on During defrosting under he ating mode it may generate vapor which is a normal phenomenon Water flowing noise Air conditioner is turned on or turned off just now The noise is the sound of refrigerant flowing inside the unit which is a normal phenomenon Cracking noise Air conditioner is turned on or turned off just now This is the sound of friction caused by expansion and or c...

Страница 23: ... restarting the unit If not please Means defrosting status It s the normal phenomenon Heating indicator ON 10s OFF 0 5s It can be eliminated after restarting the unit If not please contact qualified professionals for service When below phenomenon occurs please turn off air conditioner and discon for service Power cord is overheating or damaged There s abnormal sound during operation Air switch tri...

Страница 24: ...At least 250cm At least 15cm At least 300cm Space to the floor Space to the ceiling Space to the obstruction At least 15cm At least 15cm Space to the wall Space to the wall 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 25: ...all the indoor unit right above the electric appliance Indoor unit 1 The place with strong heat sources 8 Please try your best to keep way from fluorescent lamp or volatile objects spread in the air 2 The place with high frequency devices such as welding machine medical equipment 3 The place near coast area 4 The place with oil or fumes in the air 5 The place with sulfureted gas 6 Other places wit...

Страница 26: ...ounding device by a professional Please make sure it is always grounded effectively otherwise it may cause electric shock 2 The yellow green wire in air conditioner is grounding wire which can t be used for other purposes 3 The grounding resistance should comply with national electric safety regulations 4 The appliance must be positioned so that the plug is accessible 5 An all pole disconnection s...

Страница 27: ...he direction of outlet pipe The position of piping hole should be a little lower than the wall mounted frame shown as below Step three open piping hole 2 Open a piping hole with the diameter of Φ55 on the selected outlet pipe position In order to drain smoothly slant the piping hole on the wall slightly downward to the outdoor side with the gradient of 5 10 Left Wall Φ55mm Right Mark in the middle...

Страница 28: ...ight please cut off the corresponding hole on the bottom case cut off the hole left right 1 The pipe can be led out in the direction of right rear right left or rear left left rear left right rear right Step four outlet pipe Installation of indoor unit union nut pipe joint pipe Note Pay attention to dust prevention and take relevant safety measures when opening the hole The plastic expansion parti...

Страница 29: ...ake wiring cover screw panel Step seven connect wire of indoor unit 4 Wrap the indoor pipe and joint of con then wrap it with tape Step six install drain hose Installation of indoor unit torque wrench open end wrench indoor pipe pipe union nut Hex nut diameter Tightening torque N m Φ 6 Φ 9 52 Φ 12 Φ 16 Φ 19 30 40 45 55 60 65 70 75 15 20 indoor unit 2 Bind the joint with tape Note drain hose in ord...

Страница 30: ... the back of indoor unit and then pull it out from the front side 2 3 N 1 Outdoor unit connection L2 L1 2 3 N 1 cord according to the color tighten the screws and then fix the power connection cord fixed by the wire clip inside of the electric box first before connecting the power connection cord If there is no wired controller in the product you bought you should put the wire installation For the...

Страница 31: ...wer cord and control wire can t be crossed or winding The drain hose should be bound at the bottom drain hose band connection pipe indoor power cord Step nine hang the indoor unit 1 Put the bound pipes in the wall pipe and then make them pass through the wall hole 2 Hang the indoor unit on the wall mounting frame 3 Stuff the gap between pipes and wall hole with sealing gum 4 Fix the wall pipe 5 Ch...

Страница 32: ...cause electric leakage Does the power cord follow the speci fication It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and outlet It may cause insufficient cooling heating capacity The dust and sundries caused during installation are removed It may cause malfunction or damaging the parts The gas valve and liquid valve of connection pipe are open completely It...

Страница 33: ...er meter is different according to the diameter of liquid pipe See the following sheet Additional refrigerant charging amount prolonged length of liquid pipe additional refrigerant charging amount per meter Cooling capacity Cooling capacity 5000Btu h 1465W 24000Btu h 7032W 7000Btu h 2051W 28000Btu h 8204W 9000Btu h 2637W 36000Btu h 10548W 12000Btu h 3516W 42000Btu h 12306W 18000Btu h 5274W 48000Bt...

Страница 34: ...pipe mm Gas pipe mm Φ6 Φ6 or Φ9 52 Φ9 52 or Φ12 Φ12 Φ16 Φ19 Φ22 2 Φ16 or Φ19 Φ19 or Φ22 2 Φ25 4 or Φ31 8 _ _ Cooling only g m Cooling and heating g m 15 15 30 60 250 250 350 350 120 120 50 20 Outdoor unit throttle Configuration of connection pipe 2015 Innovair Corporation All Rights Reserved www innovair com ...

Страница 35: ...on the union nut Remove the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe union pipe pipe E Expand the port Expand the port with expander Note A is different according to the diameter please refer to the sheet below expander hard mold pipe F Inspection Check the quality of expanding port If there is any blemish expand the port again according to the st...

Страница 36: ...Innovair Corporation 11490 NW 39th Street Miami FL 33178 www innovair com 2015 Innovair Corporation All Rights Reserved www innovair com ...

Отзывы: