Additional refrigerant charge
8. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ6.35
Φ9.52
Formula
V=15g/m×(L-5)
V=30g/m×(L-5)
V: Additional refrigerant charge volume (g).
L : The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged. Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
60
Installation
Содержание ICS0629C21
Страница 1: ...SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i ...
Страница 2: ......
Страница 4: ......
Страница 9: ...Part 2 Indoor Units Four way Cassette Type 6 Ceiling Floor Type 20 5 ...
Страница 13: ......
Страница 16: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12 Four way Cassette Type ...
Страница 17: ...Wiring Diagrams 4 Wiring Diagrams ICS0629C21 ICS0736C21 Four way Cassette Type 13 ...
Страница 23: ...Field Wiring 11 Field Wiring ICS0629C21 ICS0736C21 Four way Cassette Type 19 ...
Страница 27: ...Service Space 3 Service Space Ceiling Floor Type 23 ...
Страница 28: ...Wiring Diagrams 4 Wiring Diagrams IUS0736C21 24 Ceiling Floor Type ...
Страница 35: ...Field Wiring 11 Field Wiring IUS0736C21 Ceiling Floor Type 31 ...
Страница 40: ...Wiring Diagrams 3 Wiring Diagrams IOS629C2V01 36 Outdoor Unit ...
Страница 41: ...Wiring Diagrams IOS736C2V01 Outdoor Units 37 ...