Drainage pipe installation
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note:
Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
58
Installation
Содержание ICS0629C21
Страница 1: ...SERVICE MANUAL IOS629C2V01 IOS736C2V01 IUS0736C21 ICS0629C21 ICS0736C21 AIR CONDITIONER i ...
Страница 2: ......
Страница 4: ......
Страница 9: ...Part 2 Indoor Units Four way Cassette Type 6 Ceiling Floor Type 20 5 ...
Страница 13: ......
Страница 16: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12 Four way Cassette Type ...
Страница 17: ...Wiring Diagrams 4 Wiring Diagrams ICS0629C21 ICS0736C21 Four way Cassette Type 13 ...
Страница 23: ...Field Wiring 11 Field Wiring ICS0629C21 ICS0736C21 Four way Cassette Type 19 ...
Страница 27: ...Service Space 3 Service Space Ceiling Floor Type 23 ...
Страница 28: ...Wiring Diagrams 4 Wiring Diagrams IUS0736C21 24 Ceiling Floor Type ...
Страница 35: ...Field Wiring 11 Field Wiring IUS0736C21 Ceiling Floor Type 31 ...
Страница 40: ...Wiring Diagrams 3 Wiring Diagrams IOS629C2V01 36 Outdoor Unit ...
Страница 41: ...Wiring Diagrams IOS736C2V01 Outdoor Units 37 ...