MAXIM Installation Instructions
Page 32
© Mass Electronics Pty Ltd 2011
Edition 2.0 dated 20/11/2013
3-3.2 MiniMAX Controllers (MM01 / MM02)
This section of the manual provides wiring information for the MiniMAX MM01 and MM02 controllers.
Information is provided on wiring a power source and all associated inputs and outputs.
The general layout of the input and output terminals for each of these controllers is illustrated in
Figure 3-7 below.
3-3.2.1 Power Input
The MiniMAX controllers are powered by a 24VAC power source. The operating voltage must meet the
requirements of Safety Extra Low Voltage (SELV) to EN60730. The transformer used must be a Class 2
safety transformer in compliance with EN60742 and be designed for 100% duty. It must also be sized
and fused in compliance with local safety regulations. Power input specifications for the MiniMAX
controllers are detailed in Table 3-5 below.
Figure 3-7:
MiniMAX (MM01 & MM02) Controller Terminal Connection Layout
Table 3-5:
MiniMAX Power Source Specifications
Power Source
Rating
24VAC ±10%, 50/60 Hz, Nominal Transformer rating with maximum TRIAC load:
35VA
24VAC ±10%, 50/60 Hz, Nominal Transformer rating with no TRIAC load:
10VA
Содержание MAXIM 1010
Страница 1: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Страница 9: ...Chapter 1 Preliminary Information MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Страница 15: ...MAXIM Series Controllers INSTALLATION INSTRUCTIONS Chapter 2 Mechanical Installation...
Страница 23: ...Chapter 3 Electrical Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Страница 41: ...Chapter 4 Network Installation MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Страница 43: ...Chapter 5 Commissioning MAXIM Series Controllers INSTALLATION INSTRUCTIONS...
Страница 53: ...Appendix A Using the CT01 Commissioning Tool MAXIM Series Controllers INSTALLATION INSTRUCTIONS...