Page 3

DS 15.12 - 

GENII MZS REM - Multi-zone Station After Hours Remote Expansion Module

August 2013

Program Functions On The GENII MZSAH REM

Start Programming Mode

To enter Programming Mode depress and hold the 

 and 

ON

OFF

 buttons for 5 seconds. The display will become blank 

indicating that you are in the Programming Mode. Release both 

keys and the display will show parameter 0. 

Whilst in the programming mode the following buttons are 

active:

ON

OFF

 

Change to the next parameter.

 

Increase the current parameters value.

 

Decrease the current parameters value.

Parameter 0: Rem Address

This parameter is only available for Zone 0.

The display will show the current REM Address of the device.

•  The range of address is 0 to 15

•  The default address is 0

Parameter 1: Maximum Input Value

The display will show the Maximum Input Value to which the 

module’s input can be set.

•  The range of Maximum Input Value is 0.0 to 99.9

•  The factory default setting is 30.0

Parameter 2: Minimum Input Value

The display will show the Minimum Input Value to which the 

module’s input can be set.

•  The range of Minimum Input Value is 0.0 to 99.9

•  The factory default setting is 15

Parameter 3: Decimal Position

The display will show the position of the decimal point.

•  The range of Maximum Input Value is 0.0 to 2.0

•  The factory default setting is 1.0

Parameter 4: Zone Enable

The display will show whether the zone is enabled.

•  1 - Zone Enabled

•  0 - Zone Disabled

Exit Programming Mode

To exit the Programming Mode depress the 

ON

OFF

 and 

       

buttons and the new setting will be saved.

Start Up Default Settings

The GENII MZSAH REM Module can be set to start in any mode of 

operation. 

1. To set the start up default, adjust the GENII MZSAH REM Module to 

the desired settings and then press and hold the 

ON

OFF

  and 

 

buttons for 5 seconds. 

2. The display will become blank indicating that the new settings 

have been saved.

Each Zone can have individual settings.

OPERATING FUNCTIONS ON THE GENII MZSAH REM

Numerical Output

The GENII MZSAH REM Module will display a 3 digit, single decimal place 

analogue output value during normal operation.

Numerical Input

The GENII MZSAH REM Module will provide a 3 digit, single decimal 

place analogue input value to the GENESIS Controller during normal 

operation.

This value can be modified by pressing the 

 button to increase 

or the 

 button to decrease the value. The value will increase or 

decrease by the least significant digit as set by Parameter 3.

Momentary Digital Input Value

The 

ON

OFF

 button on the GENII MZSAH REM Module provides a digital 

input value to the GENESIS II Digital Controller during normal operation.

This operates as a standard momentary switch, i.e. Pressing the 

ON

OFF

 

button produces a momentary digital input to the Genesis II Digital 

Controller for the selected zone.

Digital Run Led

The GENII MZSAH REM displays a digital state via the On/Off led during 

normal operation.

Select Button And Zone Led

The 

Select

 button is used to increment the current zone to the next ena-

bled zone. The zone led indicates which zone is current. 

Each zone has its own set of parameters.