GENII MZS REM - Multi-zone Station After Hours Remote Expansion Module
August 2013
Program Functions On The GENII MZSAH REM
Start Programming Mode
To enter Programming Mode depress and hold the
and
ON
OFF
buttons for 5 seconds. The display will become blank
indicating that you are in the Programming Mode. Release both
keys and the display will show parameter 0.
Whilst in the programming mode the following buttons are
active:
ON
OFF
Change to the next parameter.
Increase the current parameters value.
Decrease the current parameters value.
Parameter 0: Rem Address
This parameter is only available for Zone 0.
The display will show the current REM Address of the device.
• The range of address is 0 to 15
• The default address is 0
Parameter 1: Maximum Input Value
The display will show the Maximum Input Value to which the
module’s input can be set.
• The range of Maximum Input Value is 0.0 to 99.9
• The factory default setting is 30.0
Parameter 2: Minimum Input Value
The display will show the Minimum Input Value to which the
module’s input can be set.
• The range of Minimum Input Value is 0.0 to 99.9
• The factory default setting is 15
Parameter 3: Decimal Position
The display will show the position of the decimal point.
• The range of Maximum Input Value is 0.0 to 2.0
• The factory default setting is 1.0
Parameter 4: Zone Enable
The display will show whether the zone is enabled.
• 1 - Zone Enabled
• 0 - Zone Disabled
Exit Programming Mode
To exit the Programming Mode depress the
ON
OFF
and
buttons and the new setting will be saved.
Start Up Default Settings
The GENII MZSAH REM Module can be set to start in any mode of
operation.
1. To set the start up default, adjust the GENII MZSAH REM Module to
the desired settings and then press and hold the
ON
OFF
and
buttons for 5 seconds.
2. The display will become blank indicating that the new settings
have been saved.
Each Zone can have individual settings.
OPERATING FUNCTIONS ON THE GENII MZSAH REM
Numerical Output
The GENII MZSAH REM Module will display a 3 digit, single decimal place
analogue output value during normal operation.
Numerical Input
The GENII MZSAH REM Module will provide a 3 digit, single decimal
place analogue input value to the GENESIS Controller during normal
operation.
This value can be modified by pressing the
button to increase
or the
button to decrease the value. The value will increase or
decrease by the least significant digit as set by Parameter 3.
Momentary Digital Input Value
The
ON
OFF
button on the GENII MZSAH REM Module provides a digital
input value to the GENESIS II Digital Controller during normal operation.
This operates as a standard momentary switch, i.e. Pressing the
ON
OFF
button produces a momentary digital input to the Genesis II Digital
Controller for the selected zone.
Digital Run Led
The GENII MZSAH REM displays a digital state via the On/Off led during
normal operation.
Select Button And Zone Led
The
Select
button is used to increment the current zone to the next ena-
bled zone. The zone led indicates which zone is current.
Each zone has its own set of parameters.