© MASS ELECTRONICS Pty Ltd 2006
Models:
GENII MZSAH REM:
Multi-zone Station After Hours
Remote Expansion Module
DS 15.12
August 2013
GENII MZSAH REM
Multi-zone Station After Hours
Remote Expansion Module
Applications
Expands GENESIS Controller capabilities by providing a numeric output
display, numerical value input, a single toggle digital input switch and
single LED display output for distributed control via RS485. The GENII
MZSAH REM Module provides a visual display of up to 6 control values
and a means to set up to 6 parameters.
Application Notes
A GENESIS Controller must have version 4 firmware installed to support
REM Modules. Version 4.1 or higher Config Software must be used to
configure a GENESIS Controller that has REM Modules connected to it.
One GENESIS Controller can have up to 15 GENII MZSAH REM Modules*
connected to it via the REM comms bus.
For detailed connection information to the pre version 5 GENESIS Digital
Controller Family, please refer to DS 99.03
Overview
The Innotech GENII MZSAH REM Multi-Zone Station Module is an
expansion device for the GENESIS range of Digital Controllers.
The module is powered by 24VAC and provides a limited User
Interface to the GENESIS Controller. There are no physical
connections between field equipment and the GENII MZSAH
REM, all input/output values are edited and viewed on the wall
unit.
The GENII MZSAH REM may be located remotely from the
GENESIS Controller providing a distributed User Interface for the
system.
The GENII MZSAH REM is configured via the wallplate and
programmed via the GEN2Config Software.
The GENII MZSAH REM communicates with the Genesis
Controller via the REM Comms port. The remote link uses RS-485
at a baud rate of 38400. For pre-version 5 controllers, a Gen II
RMI Remote Module Interface is required.
Please refer to DS 15.01 for further information.
Features
• One three decimal place numerical value input
• One three decimal place numerical output
• One momentary digital input
• One LED digital display output
• One ‘current zone’ input
• Housed in a switchplate that mounts in standard electrical
wall plates
• RS485 interconnection between REM Modules
• 24VAC operation
• Wiring Diagrams for modules generated by GEN2Config
Software
• Adjustable user input range
• Configurable power on settings
• LED indication of network traffic on rear to ease debugging &
setup
Approvals
The GENII MZSAH REM conforms to:
• EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM
Labelling
• FCC Title 47 CFR, Part 15 Class A for FCC Marking
• UL listed to UL916, File Number E242628