background image

© MASS ELECTRONICS Pty Ltd  2006

Page 2

DS 15.12 - GENII MZS REM - Multi-zone Station After Hours Remote Expansion Module

August 2013

Specifications

Power Supply

•  Voltage: 24VAC ±10% @ 50/60Hz

•  Power Consumption: 3VA max

The operating voltage must meet the requirements of Safety Extra Low 
Voltage (SELV) to EN60730. The transformer used must be a Class 2 safety 
transformer that has the energy and voltage limiting characteristics as 
described in the National Electrical Code, ANSI/NFPA70. It must also be sized 
and fused in compliance with local safety regulations.

Inputs

•  Push buttons for adjusting control values

•  Push button for toggling of “digital function”

•  Push button for zone selection

Outputs

•  No physical outputs

•  Display of Temperature and Setpoint

Terminal Identification

1  

24VAC Supply

2  

0VAC Supply

3 Earth

TERMINAL 3 is for the protection of the Comms circuitry and 

must be connected to a good electrical bonded Earth.

COMMS Connection

SHLD 1   Shield from incoming Comms Cable.

+  

RS 485 (+) signal.

-  

RS 485 (-) signal.

SHLD 2   Shield from outgoing Comms Cable.

Temperature Ratings

•  Storage  

0 to 50°C non-condensing

•  Operating  

0 to 40°C non-condensing

Enclosure

The GENII MZSAH REM Modules are housed in switchplate that 

mounts in standard electrical wall plates.

Colour:    

White

Mounting:  

Wall mounted

Installation

•  The Cable run between the GENII MZSAH REM and the GENII RMI 

should not exceed 500 mtrs. The Comms wiring requires cable 

especially suited for RS485. Other shielded cable is not suitable 

and may cause spasmodic Comms failures.

•  Strictly follow the guidelines when installing the Comms wiring as 

outlined in the Genesis II Installation Manual.

•  Mount the GENII MZSAH REM in a dry and clean location free of 

excess vibration.

The REM address must be set by programming Parameter 0. 

Please refer to the Program Functions section of this data 

sheet for more specific information regarding this.

Wiring

•  The cable used for RS485 Comms must be shielded single 

twisted pair, 120 ohms character impedence, 36 to 45pF per 

metre capacitance between conductors.

•  The Comms cable must be organised as a bus topology. That is, 

starting at one end, devices are connected to it until the other 

end of the cable is reached. No “stubs” are allowed. To connect 

a device to the cable, as cut is made in the cable at the point 

where the device is to be situated along it. Then, the two new 

ends of the cable are wired into the device. The shields from the 

two new ends are then terminated into the terminals marked 

SHLD1 and SHLD2.

•  Refer to the Genesis Network Installation Instructions for more 

information.

FCC Class A Notice

This device complies with Part 15 of the FCC Rules. Operation is 

subject to the following two conditions:

•  This device may not cause harmful interference.

•  This device must accept any interference received, including 

interference that may cause undesired operation.

Note – This equipment has been tested and found to comply with the limits for a Class A 

digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide 

reasonable protection against harmful interference when the equipment is operated 

in a commercial environment. This equipment generates, uses and can radiate radio 

frequency energy and, if not installed and used in accordance with the instruction 

manual, may cause harmful interference to radio communications. Operation of this 

equipment in a residential area is likely to cause harmful interference in which case the 

user will be required to correct the interference at his own expense. Modifications to this 
device, may void the authority granted to the user by the FCC to operate this equipment.

Отзывы: