INMES Industrial Ltda – IM-30 MM
10
5.2 - Motor Specification for Exhaust Cabinet
Motor Induction three phase or single phase.
Available in: Consumed Power kw/h: 50Hz - 60Hz Amps: 50Hz - 60Hz
115 V Single phase
1,20 kw/h
10,40 A
208-230V Single Phase
0,80kw/h - 1,12 kw/h
3,64 A - 5,10 A
Rotation: 3535
rpm
Power:
0,75
hp
Frequency: 60Hz
50Hz
5.3 - Chart with specification for thermo magnetic circuit breaker
Inmes Industrial recommends installing a thermo magnetic circuit breaker on the electrical source,
preferably IEC Curve C standard (For inductive equipments) before connecting the machine to the electrical
source and make sure the circuit is properly grounded using the green/yellow wires for this purpose. This
service must be performed by a qualified staff.
In order to select an appropriate circuit breaker for your equipment use the chart below:
Tension
Frequency
Nominal current for motor Recommended circuit breaker
110V Single phase
60Hz
11A
Bipolar 16A
220V Single phase
60Hz
5,55A
Bipolar 10A
For the cabinet base with dust collector motor is also recommended to use a thermo magnetic circuit
breaker on the electrical source, preferably IEC Curve C standard (For inductive equipments) before
connecting the machine to the electrical source and make sure the circuit is properly grounded using the
green/yellow for this purpose. This service must be performed by a qualified staff.
In order to select an appropriate circuit breaker for the cabinet base use the chart below:
Tension
Frequency
Nominal current for motor Recommended circuit breaker
110V Single phase
60Hz
10,4A
Bipolar 16A
220V Single phase
60Hz
5,1A
Bipolar 10A