Programming the SmartLink-GP
41
Programming manual
3.10.6 Implement constraint after event
Figure 13 - Events table - Constraint
Each event can implement constraint and generate commands. For
example, a
No GSM Service
event will switch dialing to the land line
(PSTN).
OFF
Check boxes corresponding to
the Inputs/Outputs configured in
the
Outputs
table. If selected,
they will deactivate the
respective output. The output
description appears when you
mouse over the respective
number on the tooltip bar.
Deactivation of a pulse
output ends any
ongoing pulse signal,
otherwise, it has no
effect.
Parameter
Description
Note
Options
Folder containing Constraint
parameters. Double click to open:
columns containing the successive
parameters will appear. Double click
to close.
=no
parameter has
been set
=some
parameters have
been set.
Land line
(PSTN)
constraint
If selected, all outgoing calls (voice
messages and Contact ID reports)
generated by the event will be sent
on the land line (PSTN), thus
ignoring the SmartLink-GP reserve
line feature and
GSM network
priority
option.
If this option is
selected, the
device will be
unable to make
any calls
associated with
the event during
'land-line down'
conditions.
Parameter
Description
Note