background image

Air2-FD100 | © 2020 Inim Electronics S.r.l.

9

4.1  Wireless terminal parameters

4.  Programming wireless terminal

The programming of a wireless terminal can only be done through the control panel programming software.

On  accessing  the  software,  it  is necessary to  open a  solution,  configuration  of  the  real system  to  be  

designed. Successively a terminal previously configured or to be configured as “wireless” must be selected.

After which it will be possible to access the device programming in order to select or change the device type 

and its parameters.

4.1  Wireless terminal parameters

Use detector 
LED

The red LED on the device provides visual signalling of alarm or tamper conditions on the device itself.

Bypass tamper

This option disables open/dislodgement tamper signalling.

Disable wireless
monitoring

Enabling this option (disabled at default), disables wireless monitoring on the detector.

In the event of the loss of the specific detector, no event will be generated and no fault signal will be signalled 

on the keypad.

Disable detector
on partition dis-
arming

In order to increase battery life, the PIR detector will deactivate when the partitions it belongs disarm and 

activate when the partitions it belongs to arm.

When the detector is deactivated it will not generate alarms.

From the moment the partitions arm, there may be a delay of up to 3 minutes before the detector receives the 

activation command.

Alarm pulses

This is the number of pulses (each lasting as long as the programmed “Alarm pulse duration”) necessary to 

generate a zone alarm event.

If this value is more than 1, you must also program the “Multi-pulse time” parameter.

Multi-pulse time

This parameter applies only when the “Alarm pulse num.” is higher than 1.

This is the window during which a number of alarm pulses must be detected (each lasting as long as the pro-

grammed “Alarm pulse duration”) equal to the value programmed for “Alarm pulses” in order for the system 

to generate an alarm.

This time window can be expressed in seconds or minutes.

Alarm pulse dur-
ation

This is the length of time (after detection of alarm conditions) the zone will allow before generating an alarm.

Expressed in multiples of 15 milliseconds or minutes.

Detector sens-
itivity

from 0.08 dB/m to 0.15 dB/m (default)

4.2  Real-time

For each configured device the software provides a direct software-to-device connection which allows visu-

alization of the real-time values of the following features of the wireless sounder:

Reading level

The value read by each detector of the device is displayed on a bar which indicates the alarm threshold by

means of a colour change from green to red.

Signal recep-
tion

The series of notches represent the reception level of the wireless signal of the device as received by the trans-

ceiver Air2-BS200.

Battery
charge level

Percentage of the device battery charge.

RF analysis

Function to monitor the variation of the signal transmitted by the device and the background noise detected 

through time.

Содержание Air2-FD100

Страница 1: ... JS 8JSFMFTT TNPLF EFUFDUPS E EN 50131 1 EN 50131 5 3 EN 50130 4 EN 50130 5 INCERT CEB T031 OTUBMMBUJPO BOE QSPHSBNNJOH NBOVBM ...

Страница 2: ...FD100 7 3 1 Enrolling a wireless device 7 3 2 Battery replacement 8 4 Programming wireless terminal 9 4 1 Wireless terminal parameters 9 4 2 Real time 9 5 General information 10 5 1 About this manual 10 5 2 Manufacturer s details 10 5 3 Notes from the Manufacturer 10 5 4 Simplified EU Declaration of Conformity 10 5 5 Documents for the users 11 5 6 WEEE 11 2 Installation and programming manual 100 ...

Страница 3: ...white or brown Air2 FD100 smoke detector Air2 Aria W keypad with graphic display Air2 Hedera outdoor sounder in white or chrome effect Air2 Smarty W indoor sounderflasher Air2 DT200T dual technology curtain detector in white or brown Air2 XIR200W PIR detector 12 m Air2 XDT200W dual technology curtain detector Air2 UT100 universal transceiver Air2 ODI100W outdoor wireless dual infrared detector Air...

Страница 4: ...ow to the sampling chamber UUFOUJPO Air2 FD100 is a smoke detector that can be used exclusively for the detection of smoke in the protected area With the use of Air2 FD100 the intrusion control system INIM cannot be considered a fire detection system The operating parameters of detectors can be changed and adapted to the environmental conditions either from the control panel orvia the programming ...

Страница 5: ...arts LJ Detector LJ LED red yellow green LJ Battery LJ Tampermicroswitch LJ ENROLL microswitch LJ Base LJ Mounting screw hole 2 2 Air2 FD100 technical specifications Battery type Lithium CR17450 3V estimated life 3 years Low battery fault voltage Less than 2 4V Current draw during standby 70µA ...

Страница 6: ...e included 114mm Weight base and battery included 182 g 2 3 LED signallings from Air2 FD100 The tricolourLED 360 visibility indicates the detectorstatus Green one flash every 15 seconds detector operating properly Green one flash every 40 seconds low battery Yellow On solid fault present Yellow flashing sampling chamber contaminated with dust etc Red On solid detector in alarm status 6 Installatio...

Страница 7: ...tector to the base turn it still further until notch A aligns with notch C in order to allow the base to close the tamper microswitch 7 Enroll the device 3 1 Enrolling a wireless device The enrolling procedure allows you to associate a wireless device INIM with the transceiver Air2 BS200 which acts in conjunction with the intrusion control panel This procedure varies depending on the control panel...

Страница 8: ...ceiver 3 Set the device as Wireless 4 Start the learning phase from the control panel 5 Press the ENROLL button on the wireless device 3 2 Battery replacement When changing the battery it is advisable to press the ENROLL button in order to be sure that the device is synchronized with the wireless transceiver 8 Installation and programming manual 100 DRAFT ...

Страница 9: ...the activation command Alarm pulses This is the number of pulses each lasting as long as the programmed Alarm pulse duration necessary to generate a zone alarm event If this value is more than 1 you must also program the Multi pulse time parameter Multi pulse time This parameter applies only when the Alarm pulse num is higher than 1 This is the window during which a number of alarm pulses must be ...

Страница 10: ... or replace the parts of this system have authorization to work only on devices marketed underthe brand Inim Electronics 5 3 Notes from the Manufacturer The devices Air2 are certified by IMQ Sistemi di sicurezza Italian certification body The information relating to the power supply batteries required by the devices Air2 are provided in the fol lowing Technical Specification table The manufacturer...

Страница 11: ...g new equipment of the same type You are also entitled to convey for disposal small electronic waste products with dimensions of less than 25cm to the premises of electronic retail outlets with sales areas of at least 400m2 free of charge and without any obligation to buy Appropriate differentiated waste collection for the subsequent recycling of the discarded equipment its treatment and its envir...

Страница 12: ...info inim biz _ www inim biz Via dei Lavoratori 10 Loc Centobuchi 63076 Monteprandone AP ITALY Tel 39 0735 705007 _ Fax 39 0735 704912 DCMIINE0A2FD1008E 100 20200525 DRAFT ...

Отзывы: