Connection of accessories
Ingeteam
ABS2011IQM01_G - Installation and Operation Manual
7.4. Connecting the voltage-free auxiliary relays
These inverters have two voltage-free outputs which can have several functions:
•
Closing the relay in the event of an insulation fault (default option).
•
Closing the relay in the event of a grid, voltage or frequency out of range alarm.
•
Closing the relay in the event of any alarm in the inverter.
•
Closing the relay upon connection of the inverter to the grid.
For the connection, keep in mind the relays' characteristics:
Specifications
Rated voltage
250 VAC
Rated current
5 A
7.4.1. Cabling requirements
The section of cables used must be between 0.25 and 2.5 mm
2
.
The cable must pass to the inside of the unit through one of the two M16 holes available in the accessory supply
area.
7.4.2. Connection process
To insert the cable into the unit, use one of the precut holes protected with a cap. Remove the cap and fit the
corresponding M16 packing gland. Use a multi-pole hose.