Screen 1
Pout
Power (W) delivered by the inverter to the Electric Grid.
Vac
Output voltage (V) of the inverter at the Electric Grid connection.
Iac
Inverter output current (A).
Fac
Current output frequency to the Electric Grid (Hz).
PhiCos
Cosine of phi. This is the cosine of the phase angle existing between the grid voltage and the current
delivered by the inverter.
If there is no phase angle (0º), the cosine of phi is 1; cos 0º = 1.
Screen 2
Vdc
Voltage delivered by the solar panels to the inverter.
Idc
Current delivered by the solar panels to the inverter.
Screen 3
Alarm
Inverter alarm status. The installer has all the instructions for how to act for each specific alarm. Only
the alarms mentioned in this manual can be of use to the user.
0000H
No alarms.
0001H
Insufficient input voltage.
0002H
Grid frequency out of range.
0004H
Grid voltage out of range.
0008H
Overcurrent at the Inverter Bridge.
0010H
Overcurrent at the DC/DC converter.
0020H
Insulation failure.
0040H
Grid overcurrent.
0080H
Over heating
0100H
Bus over voltage.
0200H
Configuration change.
0400H
Manual Stop.
0800H
HW bug.
1000H
Grid instantaneous over-current.
2000H
Detection of islanding.
4000H
Grid impedance out of range.
8000H
Hardware Failure Alert.
The value displayed for this inverter alarm variable can be the result of the (hexadecimal) sum of two
or more of the variables listed above.
For example: alarm inverter 0006H means that the Grid Frequency and Voltage are out of range
(0002H + 0004H).
InvNum
The number assigned to the inverter through the menu that can be accessed from the display in order
to identify the communications.
Code1
The equipment operating code. It may be requested by the Ingeteam customer service.
Code2
The equipment operating code. It may be requested by the Ingeteam customer service.
SN
The serial number.
Screen 4
TotE
Total energy (kWh) delivered by the inverter to the Power grid since it was shipped from the factory. The
recording of the inverter serial number marks the start of the energy log.
T con
The number of hours that the inverter has been connected to the Power grid.
NumCon
The number of grid connections made during operating hours.
58
Ingeteam Inc
Installation manual
AAY2000IKI02