2.8. Residual current device
These units include a residual current device as standard, in order to isolate the unit in the event of an
instantaneous differential current of 30 mA or an accumulated current of 300 mA.
This residual current device exclusively protects the unit. You must install a residual current device to
protect the installation according to the country’s legislation.
2.9. Description of cable inlets
A
B
C
D
E
F
G
H
I
K
J
L
A. DC connection, MPPT1+. Quick connector.
B. DC connection, MPPT1–. Quick connector.
C. DC connection, MPPT2+. Quick connector.
D. DC connection, MPPT2–. Quick connector.
E. DC switch.
F. Digital inputs. 16 mm cable grommets
(accepted cable diameter 4
~
10 mm).
G. Communications. 20 mm cable grommets
(accepted cable diameter 6
~
13 mm).
H. Communications. 16 mm cable grommets
(accepted cable diameter 4
~
10 mm).
I.
Potential-free relay. 16 mm cable grommets
(accepted cable diameter 4
~
10 mm).
J. SD card reader.
K. USB Type-B input.
L. AC connection. Quick connector.
2.10. Insulation resistance of the PV array
The minimum insulation resistance of the PV array permitted for connection to the inverter grid will depend on
applicable regulations. Where it is not specified, it will be 50 kOhm.
58
Unit description
Ingeteam
ABE2011IQM01_B - Installation and Operation Manual
Содержание INGECON SUN 1Play 2.5TL
Страница 3: ...iii Ingeteam ABE2011IQM01_B Deutsch DE English EN Espa ol ES Fran ais FR Italiano IT Portugu s PT...
Страница 48: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 90: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 132: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 258: ...Anmerkungen Notes Notas Remarques Note Notas...
Страница 260: ...Ingeteam Power Technology S A www ingeteam com ABE2011IQM01_B 04 2015...