IR-485 GATEWAy SWITCH SETTINGS
Compressor Identification Number
Each compressor connected to the x8I or x12I will have
a unique assigned compressor identification number;
starting at compressor 1 increasing sequentially to the
number of compressors connected to the x8I or x12I.
Switch SW1 is used to assign this unique address on the
ir-485 Gateway.
SW1
SW2
SW3
System Network Address
1
7
2
8
3
9 (for X12I only)
4
10 (for X12I only)
5
11 (for X12I only)
6
12 (for X12I only)
Function Selections
SW1
SW2
SW3
SW3-2 to 4 are not used.
SW3-1: Software Version Display
Compressor Type
Each compressor connected to the x8I or x12I must
be matched to a specific type and functionality. This is
unique to every compressor and the associated controller
used on it. Switch SW2 is used to assign this unique type
and functionality on the ir-485 Gateway.
SW1
SW2
SW3
IR-BUS (9600 N-8-2)
0: SSR
1: SE_15_100
2: SE_PEGASUS (UP Series)
3: SE_ESA_22_150
4:
not used
5:
not used
6:
not used
7:
not used
8: SSR_PHASE_1 (
status register only
)
10: SIERRA_SE_50_100
11: SIERRA_125_200
MODBUS (9600 N-8-1)
9: SSR_SG
12: SIERRA_125_400
13: SIERRA_SG_BOOSTER
14: not used
15: not used