12
X8I INfORMATION DISPLAyS
To view detailed information applicable to the
selected User menu display item press Enter.
Press Escape to return to the normal user menu
display items.
Real Time Clock:
P00
#1 18:30
T2
3
4
1
1
2
Shows the next Pressure Schedule event.
The Current Active Table
Day (#1=Monday, #7=Sunday)
Time (24hr system)
Table
Items 2 and 3 show the day and time that the unit
will change to use the ‘Table’ shown in item 4.
Compressor Status:
P00
IRV-485
100 %
1
4
20 %
30 %
5
6
7
1
1
1
3
2
Compressor Number
Priority Setting
Zone Allocation Setting
Compressor/Connection Type
Maximum Capacity % Setting
Minimum Capacity % Setting
Minimum Efficiency % Setting
Item values 6 and 7 are only shown if compressor
type is IRv-485 (variable capacity/speed).
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
Primary Detected Pressure:
P00
1
102
98
80
psi
psi
psi
2
3
4
1
Active Table
Upper (Unload) Pressure Set Point
Lower (Load) Pressure Set Point
Minimum Pressure Alarm (Warning)
Sequence Rotation:
P00
#4
18:00
18 / 05 / 2006
A B C D
Day of the week (#4: Thursday), the time of day
(18:00) and the date (18/05/2006) of the next automated
sequence rotation event.
The active ‘mode’ of operation
“
AbCD
” The current active rotation sequence assignment.
Manual Sequence Rotation:
The sequence assignment can be manually rotated at any
time. When viewing the ‘Sequence Rotation’ information
screen press Enter:
The manual rotation symbols will appear and
flash. Press Enter again to execute a manual rotation or
Escape to abandon the manual rotation.
Automated sequence rotation is not disrupted by
a manual rotation; the next scheduled automated
sequence rotation event will still occur.