 RT-SVF69C-EN

Sequence of Operation

zone sensor or remote panel when the clogged filter switch 
has been closed for at least 2 minutes during supply fan 
operation. The system will continue to operate regardless 
of the status of the clogged filter switch.

Ventilation Override

Note:

Applying 24 volts to one of the three Ventilation 
Override inputs manually activates ventilation 
override. One input is provided to request the 
Pressurize Mode, the second input the Purge Mode, 
and the third input the Exhaust Mode.

When the Pressurize Mode is selected, activating 
Ventilation Override will cause the supply fan to run, the 
economizer to open to 100%, the exhaust fan to turn 
(remain) off, or the VFD to run at full speed, and the VAV 
boxes to fully open.

When Purge is selected, activating Ventilation Override 
will cause the supply fan to run, the economizer to open to 
100%, the exhaust fan to run, or the VFD to run at full 
speed, and the VAV boxes to fully open. 

When Exhaust is selected, activating Ventilation Override 
will cause the supply fan to turn off, the economizer to 
close to 0%, the exhaust fan to run (exhaust damper at 
100% if configured for Statitrac), or the VFD to stop, and 
the VAV boxes to operate normally.

If more than one mode is requested at the same time, the 
Pressurize request will have priority followed by Purge. 
When any Ventilation Override Mode is active, all heating 
and cooling is turned off. For the case where the unit is 
required to turn off, the Emergency Stop input is used. The 
ICS can also initiate any ventilation override mode. 

Table 13

 lists the sequence of events within the system for 

each ventilation mode. Refer to the unit wiring diagram for 
contact switching and wiring. 

Note:

Fresh air tracking will not work with VOM.

Emergency Stop

When this binary input is opened, all outputs are 
immediately turned off and the system will not be allowed 

to restart until the binary input is closed for approximately 
5 seconds minimum. The shutdown is communicated to 
Tracer™ if applicable and the Heat and Cool LED outputs 
(RTRM J6-7 and J6-8) will blink at a nominal rate of 1 blink 
per second. 

Phase Monitor

The Phase Monitor is a 3 phase line monitor module that 
protects against phase loss, phase reversal and phase 
unbalance. It is intended to protect compressors from 
reverse rotation. It has an operating input voltage range of 
190-600 VAC, and LED indicators for ON and FAULT. There 
are no field adjustments and the module will automatically 
reset from a fault condition.

Low Pressure Control

This input incorporates the low pressure cutout of each 
refrigeration circuit and can be activated by opening a field 
supplied contact. 

If this circuit is open before a compressor(s) is started, the 
compressor(s) in that circuit will not be allowed to operate. 

Anytime this circuit is opened for 5 continuous seconds, 
the compressor(s) in that circuit are turned off 
immediately. The compressor(s) will not be allowed to 
restart for a minimum of 3 minutes. 

If four consecutive open conditions occur during the first 
three minutes of operation, the compressor(s) in that 
circuit will be locked out, a diagnostic communicated to 
Tracer, and a manual reset will be required to restart the 
compressor(s).

High Pressure Cutout and Temperature 
Discharge Limit

The high pressure controls and temperature discharge 
limit are wired in series between the compressor outputs 
on the RTRM and the compressor contactors. If the high 
pressure safety or temperature discharge limit opens, the 
compressor(s) on the affected circuit is locked out. If the 
compressor output circuit is opened four consecutive 
times during compressor operation, the RTRM will 
generate a manual reset lockout.

Coil Frost Protection

The Frostat™ control monitors the evaporator coil 
temperature to prevent the evaporator from freezing due 
to low operating temperatures whenever there is a 
demand for cooling. When a closed circuit has occurred for 
5 seconds minimum, the RTRM turns off all of the cooling 
outputs. The Supply Fan will be held “On” until the Frostat 
has been opened for 5 continuous seconds or for 60 
seconds after the last compressor was shut “Off”, 
whichever is the longest. The compressor shutdown is 
communicated to Tracer, if applicable. There is no local 
diagnostic for this condition.

Table 13. Ventilation override sequence

Mode and Priority

Affected Function

Pressurize

Purge

Exhaust

(a)

(a) Exhaust mode 3 is not available with the tracking power exhaust option.

1

2

3

Heat/Cool

off

off

off

VFD

full speed

full speed

full speed

Supply  Fan

on

on

off

Exhaust Fan

off

on

(b)

(b) For units configured with the Statitrac option, the Exhaust Damper will 

open during Ventilation Override modes that request the exhaust fan to 

operate.

on

Economizer

open

open

closed

VAV Boxes

forced open

forced open

normal 
operation

Содержание Voyager TZ 150F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Страница 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Страница 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Страница 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Страница 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Страница 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Страница 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Страница 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Страница 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Страница 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Страница 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Страница 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Страница 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Страница 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Страница 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Страница 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Страница 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Страница 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Страница 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Страница 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Страница 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Страница 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Страница 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Отзывы: