Sequence of Operation

ReliaTel Controls

The master module is the ReliaTel Refrigeration 
Module (RTRM).

The RTRM provides compressor anti-short cycle 
timing functions through minimum "Off" and "On" 
timing to increase reliability, performance and to 
maximize unit efficiency.

Upon power initialization, the RTRM performs self-
diagnostic checks to insure that all internal controls are 
functioning. It checks the configuration parameters 
against the components connected to the system.

The LED located on the RTRM module is turned "On" 
within one second after power-up if all internal 
operations are okay.

The RTRM in conjunction with the Variable Speed 
Module (VSM) will provide capability to control of a 
modulating eFlex™ compressor, and two multispeed 
outdoor motors (ODM).

The ReliaTel Options Module (RTOM) is utilized in 
conjunction with the RTRM for control of a variable 
speed indoor motor (IDM) and optional accessories.

All units employ a Phase Monitor to ensure proper 
power supply connection of phases for compressor 
operation. If the monitor senses incorrect phase 
connection (phase reversal), a loss of phase, or large 
voltage imbalance between phases, all unit operation 
will be prevented until the condition is corrected. The 
Phase Monitor has green (Ok) and red (Phase Fault) 
status LEDs on the face of the monitor. All units are 
functional tested to ensure correct factory wiring. A red 
status LED is an indication of a serious problem that 
can only be resolved by isolating and repairing the 
Supply Power fault.

ReliaTel Control Cooling without 

 

an Economizer

When the system switch is set to the "Cool" position and 
the zone temperature rises above the cooling setpoint 
controlband, the RTRM energizes the modulating eFlex 
compressor starting with the minimum compressor motor 
speed and runs through a start-up sequence for that 
compressor, provided the low pressure control (LPC4), 
high pressure control (HPC3), and the discharge line 
thermostat (DLT3) are closed. When the eFlex compressor 
and the outdoor fan motor are energized, they adjust 
motor speeds in order to maintain the zone temperature 
(Single Zone VAV) to /-0.5°F or Supply Air 
Temperature (Multi Zone VAV) to within ±1°F of the sensor 
setpoint at the sensed location. If the modulating 
compressor at its maximum capacity cannot satisfy the 
cooling requirement, the RTRM energizes the first fixed 
speed compressor, provided the low pressure control 

(LPC1), the high pressure control (HPC1), and the 
discharge line thermostat (DLT1) are closed, while 
simultaneously reducing the modulating compressor 
motor speed to allow a smooth transition in system 
capacity. When the fixed speed compressor is energized, 
the ReliaTel control starts to maintain the zone 
temperature (Single Zone VAV) to /-0.5°F or Supply 
Air Temperature (Multi Zone VAV) to within ±1°F of the 
sensor setpoint at the sensed location by modulating the 
eFlex compressor speed and both ODM. If the first two 
compressors cannot satisfy the load, the second fixed 
speed compressor is energized in addition to the first fixed 
speed compressor, provided the low pressure control 
(LPC1), the high pressure control (HPC2), and the 
discharge line thermostat (DLT2) are closed. 
Simultaneously, the modulating compressor speed is 
reduced for a smooth transition to the higher system 
capacity. When the third compressor is energized, the 
ReliaTel control starts to maintain the zone temperature 
(Single Zone VAV) to /-0.5°F or Supply Air 
Temperature (Multi Zone VAV) to /-1°F of the 
sensor setpoint at the sensed location by modulating the 
eFlex compressor motor speed and both ODM.

ReliaTel Control Evaporator Fan 

 

Operation

With the indoor fan in "Auto" mode, the RTRM energizes 
the indoor fan motor for approximately 1 second after 
energizing the modulating compressor in the cooling 
mode. In the heating mode, the RTRM energizes the indoor 
fan motor approximately 45 seconds after gas ignition (gas 
heat unit) or 1 second before energizing electric heat 
(electric heat unit). With the indoor fan in "On" mode, the 
RTRM keeps the indoor fan energized for continuous fan 
motor operation. When the unit is equipped with the 
optional clogged filter switch, wired to the ReliaTel Options 
Module (RTOM), the RTRM produces an analog signal 
output if the clogged filter switch closes for two minutes 
after a request for fan operation. When the system is 
connected to a remote panel, the "SERVICE" LED will be 
turned on when this failure occurs.

Drain Pan Condensate Overflow Switch 
(Optional)

This input incorporates the Condensate Overflow Switch 
(COF) mounted on the drain pan and the ReliaTel Options 
Module (RTOM). When the condensate level reaches the 
trip point for 6 continuous seconds, the RTOM will shut 
down all unit function until the overflow condition has 
cleared. The unit will return to normal operation after 6 
continuous seconds with the COF in a non-tripped 
condition. If the condensate level causes the unit to 
shutdown more than 2 times in a 3 day period, the unit will 
be locked-out of operation. A manual reset of the 

Содержание Voyager TZ 150F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ion which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage...

Страница 3: ...rademarks of their respective owners Revision History Updated Performance Data section WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Inge...

Страница 4: ...Heating 15 Low Ambient Operation 15 Clogged Filter Option 15 Ventilation Override 16 Emergency Stop 16 Phase Monitor 16 Low Pressure Control 16 High Pressure Cutout and Temperature Dis charge Limit 1...

Страница 5: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F3 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Страница 6: ...Oversized 1 740 3 450 Motor Frame Size Standard Oversized 145T 145T 12 5 Tons Downflow Horizontal Units T YZ 150F4 Filters Type Furnished e Throwaway Number Size Recommended Downflow 8 20x20x2 4 20x1...

Страница 7: ...0 81 0 80 7 79 9 80 1 79 1 Steady State Efficiency 81 81 81 No Burners 1 1 1 No Stages 2 2 N A Gas Supply Line Pressure in wc 2 5 14 0 2 5 14 0 2 5 14 0 Natural Only Natural or LP minimum maximum Gas...

Страница 8: ...43 2 08 762 2 22 779 2 37 796 2 52 813 2 67 4000 649 1 64 673 1 78 696 1 92 717 2 06 738 2 21 758 2 36 778 2 51 796 2 66 815 2 81 832 2 96 4500 662 1 87 686 2 02 709 2 18 731 2 33 752 2 49 772 2 65 79...

Страница 9: ...98 747 2 11 766 2 25 783 2 40 800 2 55 816 2 70 4000 656 1 68 679 1 82 702 1 96 723 2 10 744 2 25 764 2 40 783 2 55 802 2 70 820 2 85 837 3 01 4500 670 1 92 694 2 08 717 2 23 738 2 39 759 2 55 780 2...

Страница 10: ...ters a 2 MERV 8 Filter b 2 MERV 13 Filter b Std Economizer with OA RA Dampers c Low Leak Economizer with OA RA Dampers d Electric Heater Accessory kW e 100 OA 100 RA 100 OA 100 RA 5 12 14 27 36 54 72...

Страница 11: ...control LPC1 the high pressure control HPC1 and the discharge line thermostat DLT1 are closed while simultaneously reducing the modulating compressor motor speed to allow a smooth transition in system...

Страница 12: ...is running at its maximum capacity and the zone temperature continues to rise above the zone temperature setpoint controlband and the economizer damper is fully open the RTRM energizes the second fix...

Страница 13: ...r compartment protects against abnormally high leaving air temperatures The automatic reset fan fail limit located in the upper middle section of the indoor fan board protects against abnormally high...

Страница 14: ...e a new control scheme comprised of 2 existing schemes that have been traditionally mutually exclusive DCV and OA CFM Compensation Units configured with DCV will invoke the new Demand Controlled Venti...

Страница 15: ...heat units the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpo...

Страница 16: ...rse rotation It has an operating input voltage range of 190 600 VAC and LED indicators for ON and FAULT There are no field adjustments and the module will automatically reset from a fault condition Lo...

Страница 17: ...to set the supply air temperature below 50 F In cooling if supply air temperature is more than 3 5 degrees warmer than the selected temperature a stage of cooling will be turned On if available Then...

Страница 18: ...ode or switched to the Cooling Mode the unit will revert to the cooling operation If an Occupied Heating Mode is selected the unit will only function within the DWU perimeters until the system is swit...

Страница 19: ...l temperature swing of the discharge air will likely be greater Zone Temperature Unoccupied Heating While a building is in an unoccupied period as designated by a remote panel with night setback or IC...

Страница 20: ...g mode Allow all compressors to run long enough for the pressures to stabilize 2 Measure the liquid line temperature of each circuit near the condenser coil after pressures stabilize 3 Measure the liq...

Страница 21: ...105F OD Ambient 95 F OD Ambient 85 F OD Ambient 74 62 F ID WB DB 86 72 F ID WB DB 120F OD Ambient 115F OD Ambient Figure 2 Cooling cycle pressure curve system 2 100 200 300 400 500 600 700 100 120 14...

Страница 22: ...ve curve value c OK if the sub cooling is within 5 F of the curve value 4 The standard superheat operating range for units with the standard offering thermal expansion valves is 16 F 24 F These superh...

Страница 23: ...RT SVF69C EN 23 Refrigerant Circuit Figure 4 12 5 tons eFlex system schematic...

Страница 24: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Отзывы: