28
C950 PLANNING & INSTALLATION MANUAL
TP0029 Rev5
Ó
2000 Ingersoll-Rand Company
Date of Revision: 15 August, 2000
Standard Oil Cooler and Filter Data
Lube Oil Cooler
Water side design pressure
150 PSIG
1034 kPa
Shell side design pressure
150 PSIG
1034 kPa
Lube Oil Filter
Dual Element
10 Micron
Recommended Oil Temperatures
Minimum Oil Temperature for:
Starting
95°F
35°C
Operating Bearing Inlet Oil Temp.
100°F to 115°F
37.5°C to 46°C
Weights and Dimensions
Specific machine weights and dimensions will vary according to motor selected and any
additional special options purchased. The weights and dimensions provided are to be used
for estimating purposes only. Refer to the specific General Arrangement drawing for actual
dimensions.
Length (in/mm):
Width (in/mm):
Height (in/mm):
Weight (lb./Kg):
148/3759
89/2261
74/1880
17,000/7,711
Compressor Connections:
Inlet Air Connection:
10 in. 125# ANSI FF Flange
Discharge Air Connection:
6 in. 125# ANSI FF Flange
Bypass Air Connection:
4 in. 125# ANSI FF Flange
Air Cooler Connections:
2 in. 125# ANSI FF Flange
Oil Cooler Water Connections:
2 in. NPT
01_
36 of 41
90.10_Pre-Installation and Operation Manual