Installation Instructions
9 of 16
© 2012 Schneider Electric. All Rights Reserved.
9.0
Wiring Diagrams - 753 2-Wire Infrascan
1(a) Automatic operation
1(b) Automatic with manual override ON or OFF
1(c) ON, OFF or AUTOMATIC operation using a three position switch
Note
• When switching to AUTO for any of the above configurations the Infrascan will
turn on. Allow 30 seconds plus Time-On period for the sensor to stabilise for
normal operation. Wiring diagram 1(a), without override switches is preferred as
there is no settling period.
• More than one 753 CANNOT be connected in parallel to a common load.
If parallel connection of multiple devices to control a common load is required,
use Cat. No. 753R.
Load
Active/Line
10A Fuse or MCB
753
Black/White
A
N
Red/Brown
Load
Active/Line
10A Fuse or MCB
753
Black/White 2x30M or 30MAM
Off
Auto
On
Auto
A
N
Load
Red/Brown
Load
Active/Line
753
Black/White 39MAOM
On
Auto
10A Fuse or MCB
Off
A
N
Load
Red/Brown
Load