753
Series
360° Infrascan
Installation Instructions
8 of 16
© 2012 Schneider Electric. All Rights Reserved.
Note
• When mounting in suspended ceilings there should be at least 140mm between
the lower surface of the tile and the hard surface above.
• Do not apply any pressure on the actual sensor lens itself as this may damage
the lens.
Next Level/Roof
Terminal Cover
Spring Clips
Minimum Ceiling
Thickness 8mm
Surround
Lens
Cut a 50mm Circular Hole
in Ceiling (or Ceiling Tile)
140mm Minimum
126.5mm
90mm
Figure 5
A
C
B
D E
F
A
72mm (2.83")
B
15mm (0.59")
C
89mm (3.50")
D
47mm (1.85")
E
50mm (1.97")
F
126.5mm (4.98")
Figure 6