 M2M Control CX320  Technical Manual V1.01

 

 

 

 

Page 40 of 42 

 

 

Appendix B – Installing the SIM-Card 

Please refer to Appendix A to get inside access to the device. 

 
The SIM card reader is a lid-based type with a mechanical lock for the insertion of a mini-SIM card. 

Open the hinged lid on the SIM card reader, orientate the card as shown below, and insert it into the 
card reader's lid. Close the lid and slide the metal locking mechanism to the locked position, as shown 
with an arrow and text on the lid until a click is heard.  

To remove the card, slide the metal locking mechanism to the unlocked position as shown with an 
arrow and test on the lid, and open the lid. The SIM card can now be removed. 

 

 

 

SIM card orientation 

 

 

SIM card inserted and locked 

 

 

Close

Open

Содержание M2M CONTROL CX320

Страница 1: ...Infranet Technologies GmbH Tempowerkring 19 21079 Hamburg Germany Fon 49 40 696 47 260 support m2mcontrol de M2M CONTROL CX320 Technical Manual Version 1 01 ...

Страница 2: ...ady implemented and tested NX32 applications can execute without changes The M2M Control CX320 device has been designed to meet the ever increasing security challenges It offers full TLS on all major protocols and includes a hardened protected execution environment with dual boot and automatic fallback and recovery The M2M Control CX320 can also operate as a secure and intelligent industrial route...

Страница 3: ...re bus 23 Wired M Bus 24 Wireless M Bus optional 24 User interface 25 Graphical LCD display 25 Keypad 27 System Menu 27 LED Indicators 29 User LED A and B 29 System LED S1 and S2 29 Switches 31 DIP switch 31 System switch RST 31 Rechargeable Li Ion Backup Battery 32 LTE Worldwide Cat 4 Cellular Engine 33 SIM Card 33 Antennas 33 Cellular Antenna 33 Wireless M Bus Antenna optional 33 SD CARD reader ...

Страница 4: ...quired to honor a warranty claim even during the warranty period and shall be exempted from the statutory accident liability obligation Any attempts to repair or modify the product also voids all warranty claims Do not open the product There is no user serviceable part inside Defects Liability Terms A usage not according to the intended purpose an ignorance of this documentation the use of insuffi...

Страница 5: ...regulations for the operating conditions of the device are effective An optimum protection of the personnel and the environment from hazards as well as a safe and fault free operation of the product is only possible if all safety instructions are observed Intended use This product may only be used for the purposes specified in the function overview In addition it may be used for the following purp...

Страница 6: ...med by trained expert personnel which has been authorized by the plant opera tor The expert personnel must have read and understood this documentation and observe the instructions Electrical connection and commissioning must only be performed by a qualified person who is able to work on electrical installations and identify and avoid possible hazards in dependently based on professional training k...

Страница 7: ...ts of VDE T 101 Basic requirements for safe disconnection The supply lines are to be routed apart from circuits which are hazardous when touched or isolated additionally for a safe disconnection An easily accessible isolation device that disconnects all lines must be installed prior to commissioning of the device to be able to isolate it completely from power supply General Safety Instructions Cau...

Страница 8: ...ervoltage Install suitable overvoltage protection Caution Damage due to chemicals Ketones and chlorinated hydrocarbons dissolve the plastic housing and damage the surface of the device Never let the device come into contact with ketones e g acetone or chlorinated hydrocarbons such as dichloromethane Caution Distance from antennas to persons A too low distance from cellular antennas to persons can ...

Страница 9: ... SSL supporting all significant TCP protocols such as RCH FTP SMTP MQTT and sockets Hardware assisted encryption authentication AES 128 AES 192 AES 256 DES TripleDES HASH RND and RSA signature Wireless Communication LTE Cat 4 Worldwide Multi Band Cellular Engine Internal SIM card reader with support for eSIM Optional Wireless M Bus EN 13757 4 7 OMS EU CE Wired Communication 100 Mbps Ethernet LAN i...

Страница 10: ...F support for Interactive Voice Response applications Storage Internal flash drive with up to 64 MByte capacity Persistent memory and circular datalogger Standard SD Card reader Power and Battery Operating voltage from 8 to 36VDC On board 2 Ah Li Ion battery with intelligent charging Encapsulation Housed in an industry standard M36 DIN compliant encapsulation Two part pluggable connectors for easy...

Страница 11: ...M2M Control CX320 Technical Manual V1 01 Page 11 of 42 M2M Control CX320 Overview ...

Страница 12: ...er interact with the LX4 pro and access the system menu Front side view The pluggable screw terminals on the top and bottom sides of the LX4 pro are used to make connections to external equipment All the connectors are available externally for easy access and maintenance The bottom side of the M2M Control CX320 has connectors for the following communication interfaces Ethernet 1 Wire RS232 RS485 P...

Страница 13: ...ctor for an external cellular antenna The SD card reader four DIP switches and the mini B USB connector used as a programming service interface are also found on this side Inside the encapsulation the SIM card and various configuration termination jumpers are located Follow the instructions described in Appendix A Pin 49 Pin 27 Cellular Antenna DIP 1 4 Mini USB B SD Card ...

Страница 14: ... 41 DIN1 S0IN1 RS232 RTS 16 42 DIN2 S0IN2 RS232 CTS 17 43 DIN3 S0IN3 M Bus 18 44 DIN4 S0IN4 M Bus 19 45 DIN5 IGN AOUT 1 20 46 DIN6 AOUT2 21 47 DIN7 AIN1 22 48 DIN8 AIN2 23 49 SGND AIN3 24 50 Cellular antenna AIN4 25 51 AGND 26 52 Pin 5 26 overview Pin Name Description 5 SGND Signal ground 6 1 Wire 1 Wire bus for accessories such as ID Button temperature sensor 7 1 Wire LED 1 Wire ID Button LED 8 S...

Страница 15: ...26 AGND Analog Ground Pin 27 49 overview Pin Name Description 27 PGND Power ground negative connection 28 SUPP Power supply positive connection 29 SUPP Power supply positive connection 30 DOUT SUPP Power supply for the digital outputs 31 DOUT1 Digital output 1 32 DOUT2 Digital output 2 33 DOUT3 Digital output 3 34 DOUT4 Digital output 4 35 DOUT5 Digital output 5 36 DOUT6 Digital output 6 37 DOUT7 ...

Страница 16: ...ply ground PGND signal ground SGND and analog ground AGND The signal and the analog grounds are filtered from the power ground Power ground must only be used as a power supply return path The M2M Control CX320 is protected against wrong polarity If a chassis or system ground is connected to either SGND or AGND a wrong polarity on the supply lines will destroy the internal GND connection The M2M Co...

Страница 17: ...ected with the system GND internally The CX320 unit offers advanced power management that can enable one or more outputs while the device is in low power mode Please consult the M2M Control IDE documentation for additional information Digital output pins Pin Name Description 30 DOUT SUPP Digital output supply positive connector 31 DOUT 1 Digital output 1 32 DOUT 2 Digital output 2 33 DOUT 3 Digita...

Страница 18: ...de with power apply and or ignition selected for wakeup Please note Digital inputs 6 8 do not work as high speed IO so PCT is limited to 400Hz and incremental encoders are not supported The power management allows the possibility to configure a wakeup on one or more digital inputs with individually configured falling or rising edge detection Please consult the M2M Control IDE documentation for add...

Страница 19: ...S0 input 3 Digital input 3 Row 3 Position S Row 3 Position N default 44 DIN4 S0IN4 S0 input 4 Digital input 4 Row 4 Position S Row 4 Position N default 45 DIN5 IGN Digital input 5 46 DIN6 Digital input 6 47 DIN7 Digital input 7 48 DIN8 Digital input 8 49 SGND Signal Ground Specification for each digital input Min Typ Max Unit Logic High 8 12 40 VDC Protected against transients and low pass filtere...

Страница 20: ...nals The inputs are low pass filtered ESD and transient protected By default the inputs are configured as voltage inputs For replacement and configuration of the hardware jumpers inside the device please refer to the device configuration guide in Appendix D Analog input pins Pin Name Description 22 AIN1 Analog input 1 23 AIN2 Analog input 2 24 AIN3 Analog input 3 25 AIN4 Analog input 4 26 AGND Ana...

Страница 21: ...ode the specifications for the analog output are only valid for a maximum load is maximum of 250Ω The inputs are low pass filtered ESD and transient protected Please notice The M2M Control CX320 unit must be supplied with a minimum of 12VDC in order for the analog outputs to work according to the specifications By default the outputs are configured as voltage outputs For replacement and configurat...

Страница 22: ...he EIA TIA 485 A standard max 1000m 100kbit this limit is highly influenced by the quality of the cable signaling rate noise etc At longer cable lengths noisy environments or high communication speeds it might be necessary to terminate the transmission line with a 1201 ohm resistor at each end of the transmission line to terminate it and avoid signal reflections If the M2M Control CX320 is used as...

Страница 23: ... 1 Wire bus is available on the pluggable screw terminals All 1 Wire communication goes through a single connection and all 1 Wire devices connected can retrieve power directly from the bus called parasitic power For this only two wires are needed the 1 wire signal and the ground reference allowing minimal cable installations For 1 Wire ID Button readers which include a built in LED a dedicated ou...

Страница 24: ...the M Bus Min Typ Max Unit Bus idle voltage 36 VDC Protected against short circuiting Slave devices 20 Speed 300 9600 bps Wireless M Bus optional The M2M Control CX320 supports an optional onboard wireless M Bus interface compliant with EN 13757 4 7 and offers a comprehensive API for collecting data from wireless M Bus slaves The Wireless M Bus interface is designed for OMS EU CE applications but ...

Страница 25: ... available for making graphical and alphanumerical presentations of the data user interaction with menus etc By default the display is powered on at start up and shows I O status battery level and cellular status as shown in the following picture The top half of the display shows the status of the 2 analog and the 8 digital outputs in groups of 4 the bottom half shows the status of the 4 analog an...

Страница 26: ...nal strength bars indicate that the cellular interface is powered up but is not connected to the network Similarly the battery level is indicated with six levels the fully charged battery icon means fully charged and the empty battery icon means low battery level While charging the battery the battery icon is animated to show the charging progress Status Icon Battery level If LAN is enabled the up...

Страница 27: ...view the status of the device To access the system menu it must be enabled either by using displaySysMenuEnable to open it immediately or by using displaySysMenuSetPassword API to enable access to it from the keypad To access the system menu using the keypad keep the OK key pressed for at least 6 seconds and then a dialog will appear asking for the password If an empty password is used this dialog...

Страница 28: ...to show the entire name Mobile network status The arrows in the upper right corner show that this menu has submenus available using the down arrow The sub menus include signal status PLMN network type IMEI and IP address LAN Status The submenus include IP address and MAC address RCH Status The submenus include the RCH server address the used network interface and security settings Power status The...

Страница 29: ...D named A on the front consists of LED 1 green and LED 2 red LED named B on the front consists of LED 3 green and LED 4 red The LEDs are easily accessed from within the application program and it is possible to mix the LEDs to obtain a third color yellow Please consult the M2M Control IDE documentation for more information System LED S1 and S2 The CX320 is equipped with two system LEDs which show ...

Страница 30: ...lost its firmware This can only happen if during a firmware upgrade the CX320 device loses power or the communication is lost completely In this case simply upload the firmware to the device again 75ms On 925ms Off green Execution speed is different from full speed On yellow All other Leds OFF The device is booting initializing the system S2 System LED2 pattern overview Cellular activity and Power...

Страница 31: ...aper clip for this purpose By activating the switch shortly the CX320 device will perform a full reset If the reset switch is held down for approx 3 seconds1 the device will instead enter recovery mode2 and the application will not be started The system will automatically turn on the cellular engine in recovery mode to connect to the network and M2M Control Communication Hub formerly M2M Control G...

Страница 32: ...ower failure has occurred the battery will be charged to establish the capacity thus making the battery ready for the next power failure By default the battery cannot be charged above 45 C or below 0 C The CX320 offers to charge down to 10 C using a specialized algorithm to protect the battery If the temperature is above 45 C the charging will not start and will be postponed until it is below this...

Страница 33: ...or the SIM card installation guide If the SIM card is removed during the cellular operation the device will be rejected from the network shortly after Antennas Cellular Antenna The M2M Control CX320 device contains an SMA female connector for connecting a suitable LTE compliant antenna When installing the antenna please ensure that the antenna is not in close proximity to metallic parts or anythin...

Страница 34: ... use the SD CARD media and where a failure is critical it is recommended to use approved Industrial Grade SD CARDs Infranet Technologies has approved and recommends industrial grade SD CARDs from ATP available in capacities from 512 MB to 32 GB ATP Industrial Grade SD SDHC Cards are optimized for demanding industrial applications with consistent performance in all conditions ATP uses reliable SLC ...

Страница 35: ...l CX320 product identification is found on the device s exterior and contains a unique serial number in readable form and barcode The first three digits in the serial number identify the device type and for the M2M Control CX320 this unique code is 360 or 361 Barcode format used 2 5 Interleaved with check digit ...

Страница 36: ...ry depending on the cellular signal strength Note Power consumption from the battery 3 8V The table below shows detailed information about the M2M Control CX320 device s typical power consumption in power saving modes The following power saving modes are used Mode 1 LED blinks every 10 s resumes the application when it is awoken Power down The device is powered down See the M2M Control IDE online ...

Страница 37: ... out on the top part of the encapsulation below the tap e g using a screwdriver and begin lifting the right side Carefully open the encapsulation taking care to not pull on the flexible flat cable on the left side The cable is long enough to allow the top part to be placed on its end or on the front next to the bottom part Closing the device The assembly process of the encapsulation is in the reve...

Страница 38: ...ing figure shows the location of the jumpers when the lid is removed The blue shaded boxes show the default state of the jumpers Analog output mode selection jumpers Analog input mode selection jumpers Digital input mode selection jumpers SIM card reader RS485 termination jumpers ...

Страница 39: ... N Din 2 S0 mode selected Din 2 normal mode selected Din 3 Position S Position N Din 3 S0 mode selected Din 3 normal mode selected Din 4 Position S Position N Din 4 S0 mode selected Din 4 normal mode selected RS485 TERM1 RS485 TERM2 Enables disables the onboard 120 Ω line termination resistors according to the standards RS485 communication requires a proper line termination value 120 Ω assuming a ...

Страница 40: ...d on the SIM card reader orientate the card as shown below and insert it into the card reader s lid Close the lid and slide the metal locking mechanism to the locked position as shown with an arrow and text on the lid until a click is heard To remove the card slide the metal locking mechanism to the unlocked position as shown with an arrow and test on the lid and open the lid The SIM card can now ...

Страница 41: ...software is governed by the terms and conditions of the applicable open source license You are bound by the terms and conditions of the appropriate open source license in connection with your use and distribution of the open source software in this product Please refer to the separate document ʺM2M Control Open Source Licenses pdfʺ for detailed information about the packages used ...