background image

www.austin-hughes.com

UM-CMS-03-S-Q421V2

Content

Part I.   Installation

< 1.1 >   1U Fan Tray 

< 1.2 >   33U Door Mount Fan Panel

Part II.   Hardware

< 2.1 >   Key  Features 

< 2.2 >   Fan  Kit  Speci

fi

 cation

< 2.3 >   Master  IP  Fan  Unit  Model  &  Speci

fi

 cation

              MRF-1.6     

(  1U  Fan  Tray  with  6 fans )

              MRF-1.9     

(  1U  Fan  Tray  with  9 fans )

              MRF-33.9   

(  33U  Door  Mount  Fan  Panel  with  9 fans )

              

Speci

fi

 cation Table

            

< 2.4 >   Expansion Serial  Fan  Unit  Model  &  Speci

fi

 cation 

              RF-1.6     

(  1U  Fan  Tray  with  6 fans )

              RF-1.9     

(  1U  Fan  Tray  with  9 fans )

              RF-33.9  

 (  33U  Door  Mount  Fan  Panel  with  9 fans )

              

Speci

fi

 cation Table

 

< 2.5 >   Daisy  Chain  Connection  

< 2.6 >   Audio  Temperature  Alarm  Setting 

< 2.7 >   Temperature  Sensor   

< 2.8 >   Alarm  Temperature  Setting  

< 2.9 >   Fan Unit CFM  Setting

P.1

P.6

Содержание CMS-03-S

Страница 1: ...www austin hughes com UM CMS 03 S Q421V2 Rack Airflow Control User Manual CMS 03 S Master IP Fan unit GUI SNMP Designed and manufactured by Austin Hughes ...

Страница 2: ...vice personnel should open the chassis Opening it yourself could damage the equipment and invalidate its warranty If any part of the equipment becomes damaged or stops functioning have it checked by qualified service personnel What the warranty does not cover Any product on which the serial number has been defaced modified or removed Damage deterioration or malfunction resulting from Accident misu...

Страница 3: ... CMS 03 S Q421V2 The equipment comes with the standard parts shown on the package contents Check and make sure they are included and in good condition If anything is missing or damage contact the supplier immediately Unpacking ...

Страница 4: ...y with 6 fans MRF 1 9 1U Fan Tray with 9 fans MRF 33 9 33U Door Mount Fan Panel with 9 fans Specification Table 2 4 Expansion Serial Fan Unit Model Specification RF 1 6 1U Fan Tray with 6 fans RF 1 9 1U Fan Tray with 9 fans RF 33 9 33U Door Mount Fan Panel with 9 fans Specification Table 2 5 Daisy Chain Connection 2 6 Audio Temperature Alarm Setting 2 7 Temperature Sensor 2 8 Alarm Temperature Set...

Страница 5: ...tin hughes com UM CMS 03 S Q421V2 P 21 Part III Software 3 1 Key Features 3 2 Master IP Configuration 3 3 CMS 03 S Master IP Fan Unit GUI 3 4 SNMP Setup 3 5 Master IP Fan Unit Firmware Upgrade 3 6 DHCP Setting ...

Страница 6: ...n 1U rackmount fan tray x 1 pc Temp sensor x 1 pc 6 ft power cord x 1 pc Rear mounting bracket x 1 pair M6 screws for fixing are not included MRF 1 6 RF 1 6 MRF 1 9 RF 1 9 M6 screws M6 screws Rear mounting brackets Rear mounting brackets 1 1 1U Fan Tray Part I Installation ...

Страница 7: ...latively narrow for exterior mounting the unit may be installed on the inside of the perforated door For details please refer to the model table below Front Door Cool Air In Rear Door Hot Air Out Model Installation Airflow Purpose MRF 33 9A RF 33 9A Rear door outside Extract airflow Exhaust air out from rack Front door inside Intake airflow Cool air in from aisle MRF 33 9B RF 33 9B Front door outs...

Страница 8: ...ht of the unit is less than 5 5 kg so in most cases holes in perforated rack doors can be used to mount the unit Lift the unit to the desired position Place attached 6 screws then through the door and tighten them Connect the power cord to the PDU of the rack through the cable entry hole on the rear top of the rack If no cable entry on the top the unit may be installed on the inside but the model ...

Страница 9: ...the air blocking material to the size necessary with cutter or scissors and then apply the material to the inside surface of the door with magnets or double sided adhesive tapes Ensure all open perforations are covered by the material Fix the air blocking material with magnets or double sided adhesive tapes Perforated Rack Door Magnets adhesive tapes not provided ...

Страница 10: ...an Panel Assemble adjust the hanging bracket with M4 6mm screw nut to fit the thickness of the door Install the hanging bracket kit on the rear side of the fan panel with M4 10mm screw Hang the unit on the door Place attached 4 screws then through the door and tighten them Follow steps on P 3 and P 4 1 2 3 4 3 4 5 M4 10mm screws Hanging bracket with M4 6mm screw nut ...

Страница 11: ...ion Serial Fan Unit Daisy Chain Position 1st Level 2nd 16th Level IP Port Daisy Chain Port LINK Daisy Chain Port OUT Temp Port Temp Sensor Control Panel Individual Fan On Off Alarm Temp Setting Unit CFM fan speed Setting Temperature LED Fan Status LED CFM Status LED 1U Fan Tray 6 9 fans 6 9 fans Door Mount Fan Panel 9 fans 9 fans ...

Страница 12: ... com UM CMS 03 S Q421V2 P 7 Air Delivery Rated Speed Rated Voltage Rated Current Noise Level Dimension Bearing System 108 CFM 3000 rpm 10 12V DC 350 mA 41 dB 120 x 120 x 25 mm Dual ball bearing 2 2 Fan Kit Specification ...

Страница 13: ... sensor Daisy chain port for connecting to the Out port of the 2nd level fan unit 1000Base T Gigabit IP port for remote access Enterprise level IP authentication AD LDAPv3 LDAPS Only Master IP fan unit provides an IP port 1 x IP port allows access to 16 levels Press the reset button and release instantly to reboot build in IP dongle Press and hold the reset button until Orange LED off to reset buil...

Страница 14: ...p port bundled w a temp sensor Daisy chain port for connecting to the Out port of the 2nd level fan unit 1000Base T Gigabit IP port for remote access Enterprise level IP authentication AD LDAPv3 LDAPS Only Master IP fan unit provides an IP port 1 x IP port allows access to 16 levels Press the reset button and release instantly to reboot build in IP dongle Press and hold the reset button until Oran...

Страница 15: ...m Top View 4 5 6 Temp port bundled w a temp sensor Daisy chain port for connecting to the Out port of the 2nd level fan unit 1000Base T Gigabit IP port for remote access Enterprise level IP authentication AD LDAPv3 LDAPS Only Master IP fan unit provides an IP port 1 x IP port allows access to 16 levels Press the reset button and release instantly to reboot build in IP dongle Press and hold the res...

Страница 16: ...33 9 No of Fan 6 9 9 Mounting 1U Door mount CFM Level Normal High Max Individual Fan ON OFF Yes Individual Fan CFM 108 CFM Unit CFM Approximately 324 648 972 CFM 972 CFM IP Remote Access Yes Daisy Chain Level 1st level Expansion Serial fan for level 2 16 MTBF 50 000 hrs Individual Fan Noise Level 41 dB Regulatory FCC CE Temperature Sensor Temperature Port 1 x temperature sensor port sensor bundled...

Страница 17: ...Setting 1 2 3 Individual fan status Individual fan On Off buttons Buttons for Alarm Temp Setting Temp LED display 4 5 6 TEMP Link Out 458 3 43 5 480 463 4 5 6 Temp port bundled w a temp sensor Daisy chain Link port for connecting to the Out port of the 2nd level fan unit Daisy chain Out port for connecting to the Link port of the next level fan unit ...

Страница 18: ...for Alarm Temp Setting Temp LED display 2 4 Expansion Serial Fan Unit Model Model RF 1 9 1U Fan Tray with 9 fans 623 3 43 5 480 463 4 5 6 TEMP Link Out 4 5 6 Temp port bundled w a temp sensor Daisy chain Link port for connecting to the Out port of the 2nd level fan unit Daisy chain Out port for connecting to the Link port of the next level fan unit ...

Страница 19: ...View 195 mm 1 2 3 Unit CFM Status LED Unit CFM fan speed Setting Individual fan status Individual fan On Off buttons Buttons for Alarm Temp Setting 4 5 6 TEMP Link Out Top View 4 5 6 Temp port bundled w a temp sensor Daisy chain Link port for connecting to the Out port of the 2nd level fan unit Daisy chain Out port for connecting to the Link port of the next level fan unit ...

Страница 20: ... Auto sensing 100V or 240V AC at 50 or 60Hz via IEC cord Consumption 20W 40W 60W 60W Environmental Conditions Operating 0 to 50 C Storage 5 to 60 C Relative Humidity 90 non condensing Shock 50G peak acceleration 11ms half sine wave Vibration 58 100Hz 0 98G 11ms cycle Dimensions Model Product Dimension Packing Dimension RF 1 6 480 x 458 3 x 43 5 mm 18 9 x 18 x 1 71 inch 550 x 550 x 120 mm 21 7 x 21...

Страница 21: ...odule Master IP Fan unit MUST be set on the 1st daisy chain level Please follow the steps below the set the daisy chain level for Master IP Fan unit expansion fan units For the cabling connection please refer to next page Step 1 Press and hold the button for 5 seconds Step 2 Press or arrow button to set the daisy chain level ...

Страница 22: ...Access via WAN 1st level Master IP fan unit model 3rd level Expansion Serial fan unit model 2nd level Expansion Serial fan unit model Remarks Each Master IP group supports 16 daisy chain levels The 1st level fan unit must be one of the Master IP fan unit models 1 x Master IP fan unit allows access to 16 levels For IP fan unit access simply connect 1 x Master IP fan unit The 2nd 16th level fan unit...

Страница 23: ...r easy affixing to the rack Optional 4M cord for Temp Sensor TEMP 2 6 Audio Temperature Alarm Setting If enable the audio alarm the buzzer will sound when the outside temperature is over the preset alarm temperature Please follow the steps below to setup each FAN unit audio alarm Step 1 Press and hold the button for 5 seconds Step 2 Press or arrow button to enable disable the audio alarm ...

Страница 24: ... for unrestricted installation Connection Cable Length T sensor w 2m cable standard T sensor w 4m cable option Cable Specification 4 wired 3 5mm to RJ11 Cable Color Beige Environmental Operating 0 to 80 C Degree Storage 5 to 80 C Degree Humidity 0 100 non condensing Dimensions Product 30L x 25W x 18H mm Weight Net 66g Supply includes 1 Temperature Sensor 2 4 wired 3 5mm to RJ11 cable 2m black colo...

Страница 25: ...perature is over alarm temperature the unit CFM will be automatically changed to Max level Under this condition all fan kits will be turned on How to set temp unit Celsius or Fahrenheit Hold for 5 seconds Press button to set the temp unit How to set alarm temperature Hold for 5 seconds Press button to set the alaram temperature 2 8 Alarm Temperature Setting 2 9 Fan Unit CFM Setting The alarm temp ...

Страница 26: ...eatures InfraCool Manager CMS 03 S Features Capacity Master IP group Just 1 IP for 16 fan unit levels 1 Expansion Serial Fan unit number 16 Concurrent User 1 Features Unit CFM fan speed setting Auto CFM Control Setting Individual Fan ON OFF Temp Monitoring Alarm Temp Setting Graphical User Interface Remote Access via Web Browser Fan Unit Models Support Master IP Fan Unit IP dongle built in Expansi...

Страница 27: ...nected Master IP fan unit 5 Enter the device name in the name field min 4 char max 16 char The default is default_cms_name 6 Enter the location in the location field min 4 char max 16 char The default is default_cms_loc 7 Enter the password in the password field for authentication min 8 char max 16 char The default is 00000000 8 Enter the new password in the new password field min 8 char max 16 ch...

Страница 28: ...lls more Master IP Fan Unit multi windows will be required CMS 03 S is a management software with very limited features User can use more advanced software InfraCool Manager ICM 02 Step 1 Open Internet Explorer I E version 11 0 Step 2 Enter the configured IP address of the Master IP Fan Unit into the I E address bar Please refer to 3 2 Master IP Configuration Step 3 Enter Login name Password Click...

Страница 29: ...21V2 P 24 3 3 CMS 03 S Master IP Fan Unit GUI In Details Change Rack and Position of Fan Unit and Click Apply to finish the settings Switch ON OFF Fan Unit Switch ON OFF individual Fan Change Fan Unit CFM Click to enter Temp Setting page ...

Страница 30: ...rm Setting R alert setting of Temp sensor Enable or Disable auto CFM Control Click Apply to finish the above settings The default Temp setting is Deactivate When install Temp sensor please tick Activate Otherwise no reading display DON T activate Temp sensor if no sensor installed 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 31: ... Unit name location Change temperature unit displayed in UI Set the Date Time of the Master IP Fan unit by Manually or NTP server Default is Manually Select Web Access by HTTP or HTTPS Default is HTTP Click Apply to finish the above settings 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 32: ...d allows changing of these parameters LAN settings Enter IPv4 address IPv6 address Subnet mask Gateway For static IP setting only Enter the IP address of Primary DNS Default is 8 8 8 8 Enter the IP address of Secondary DNS Default is 0 0 0 0 Click Apply to finish the above settings 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 33: ...ge Password Re enter password in Confirm password if you change the login password Click Apply and OK on the pop up window to make changes effective Domain LDAP Default Join Domain is Disable Enable Join Domain only when you want to login the Master IP Fan unit by AD server Enter AD server Account Login Password Click Apply and OK on the pop up window to make changes effective You can now go to Doma...

Страница 34: ...ccess Enter Password of administrator Click Update user list to update domain user list Assign access right No access Allow Deny to User and Click Apply The user assigned Allow access right can login the Master IP Fan unit WEBUI 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 35: ...cess Enter Password of administrator Click Update User list to update domain group list Assign access right No access Allow Deny to Group and Click Apply The group assigned Allow access right can login the Master IP Fan unit WEBUI 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 36: ...t by LDAP server Enter LDAP Server Select Protocol LDAP LDAPS Default is LDAP Enter Port Default is 389 Select Encrytion None SSL Default is None Enter Base DN Enter Account Login Password Click Apply and OK on the pop up window to make changes effective You can now go to LDAP user access to assign access right to LDAP User or LDAP Group 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 37: ...cess Enter Password of administrator Click Update user list to update LDAP user list Assign access right No access Allow Deny to User and Click Apply The user s assigned Allow access right can login the Master IP Fan unit WEBUI 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 38: ...ss Enter Password of administrator Click Update user list to update LDAP group list Assign access right No access Allow Deny to Group and Click Apply The group s assigned Allow access right can login the Master IP Fan unit WEBUI 3 3 CMS 03 S Master IP Fan Unit GUI ...

Страница 39: ...are infracool Step 2 Select the appropriate MIB file of the Fan Unit series II Enabling SNMP Support i The following steps summarize how to enable the Master IP Fan Unit for SNMP v1 v2 support Step 1 Connect the Master IP Fan Unit to a computer Please refer to 3 2 Master IP Configuration Step 2 Open the Internet Explorer I E version 11 0 Step 3 Enter the configured Master IP Fan Unit address into ...

Страница 40: ...put sysLocation Default is Earth Step 12 Input sysName Default is CMS 03 S Step 13 Input Read Community Default is public Step 14 Input Write Community Default is private Step 15 Click Activate in Station 1 to enable the trap service Step 16 Input Trap Station IP Trap Port Trap Community of Station 1 Step 17 Repeat Step 15 16 for Station 2 3 Step 18 Click Apply to finish the SNMP v1 v2 settings 3 ...

Страница 41: ...v3 support Step 1 Connect the Master IP Fan Unit to a computer Please refer to 3 2 Master IP Configuration Step 2 Open Internet Explorer I E version 11 0 Step 3 Enter the configured Master IP Fan Unit address into the I E address bar Default IP address is 192 168 0 1 Step 4 Enter Login name Password Default login name password are 00000000 Step 5 Select SNMP from the left navigation pane ...

Страница 42: ... or Read Write in User role Step 15 Input the name of USM user Default is usm_user1 Step 16 Select None MD5 SHA in Auth algorithm If you select Read Write in User role you MUST select MD5 SHA in Auth algorithm Step 17 Input the Auth password Default is 00000000 Step 18 Select None DES AES in Privacy algorithm If the Auth algorithm is NONE NO privacy algorithm can be selected Step 19 Input the Priv...

Страница 43: ...ol software Step 2 Select the appropriate Master IP Fan Unit firmware file of the Fan Unit series Step 3 Connect the Master IP Fan Unit to the computer Please refer to 3 2 Master IP Configuration Step 4 Open the Internet Explorer I E version 11 0 Step 5 Enter the configured Master IP Fan Unit address into the I E address bar Default IP address is 192 168 0 1 Step 6 Enter Login name Password Defaul...

Страница 44: ...ppears as below Step 9 Click Browse and select the firmware file xxx enc from the specific path in the pop up window and Click Open Step 10 Click Upgrade to start the upgrade process It takes a few minutes to complete Do NOT close the Browser during the upgrade process Step 11 Once complete UI will return to the login page ...

Страница 45: ...r to 3 2 Master IP Configuration Step 2 Open the Internet Explorer I E version 11 0 Step 3 Enter the configured Master IP Fan Unit address into the I E address bar Default IP address is is 192 168 0 1 Step 4 Enter the Login name Password Default login name password are 00000000 Step 5 Select Network from the left navigation pane ...

Страница 46: ...www austin hughes com UM CMS 03 S Q421V2 P 41 3 6 DHCP Setting Step 6 Select ON from DHCP click Apply to save the settings Step 7 Select Firmware from the left navigation pane ...

Страница 47: ...www austin hughes com UM CMS 03 S Q421V2 P 42 3 6 DHCP Setting Step 8 Record the MAC address Step 9 Assign an IP address to the Master IP Fan Unit from your DHCP server Complete ...

Страница 48: ...dify product specifications without prior notice and assumes no responsibility for any error which may appear in this publication All brand names logo and registered trademarks are properties of their respective owners Copyright 2021 Austin Hughes Electronics Ltd All rights reserved ...

Отзывы: