INFOSEC UPS SYSTEM - 4, rue de la Rigotière – 44700 Orvault – FRANCE - www.infosec.fr
Hot Line : tel : + 33 (0)2 40 76 15 82 - fax : + 33 (0)2 40 94 29 51 - [email protected] – 02 06 04 206 12
8
13. TECHNICAL SPECIFICATIONS
1000 XP PRO 1250 XP PRO 1600 XP PRO 2000 XP PRO
Technology
Line Interactive with Automatic Voltage Regulation (AVR)
Output form
Modified sine wave
Protection
Discharge / Overcharge and overload protection
+ fax modem line protection
Power
1000 VA
1250 VA
1600 VA
2000 VA
TECHNOLOGY
Power factor
0.6 0.5 0.5 0.5
Dimensions
W x D x H
140 x 368,3 x 180,4
(mm)
Weight kg
13.5 13.8 14.2 16
PHYSICAL
Output connectors
2 surge protected outlets
4 IEC protected UPS outlets
2 surge protected RJ45
6 IEC protected UPS outlets
2 surge protected RJ45
Voltage
[110-115-120 V ] or [220 - 230 - 240 V]
Voltage range
[85 - 140 V] or [162 - 290 V]
INPUT
Frequency
50 - 60 Hz auto detection
Voltage
[115 V ] or [220 - 230 - 240 V]
Regulation
+/- 15 % (line mode)
OUTPUT
Frequency
50 or 60 Hz
Type
12V/7AH x 2pcs
12V/9AH x 2pcs
Backup time
(depending on the
load)
35 mins
23 mins
25 mins
26 mins
BATTERY
Recharge time
8 hours to 90 % after complete discharge
10 hours for a complete charge
Spike protection
225 Joules, 2 ms
FILTER
EMI/RFI
10 dB to 0.15 MHz, 50 dB to 30 MHz (EN55022 CLASS A)
Noise level
AC Mode: < 40 dB at 1 meter
Backup mode: < 45 dB at 1 meter
ENVIRONMENT
Operating
environment
0° C - 40° C, 0 to 90 % humidity rate
(non condensing)
AC Mode
Green led on
Battery Mode
Green leds come on gradually
INDICATOR
Fault
Red led on
On battery
Sounding every 10 seconds
Low battery
Sounding every second until automatic stop
Defect
Continuously sounding
AUDIBLE
ARLARM
Overload
Sounding every ½ second
SOFTWARE
Auto shut down
software
UPSurf Control
INTERFACE
Communication
port
Smart RS232
USB compatible with Windows and Mac
STANDARDS
Security / Standard
CE - ISO 9001