Overload 3 times in 30min 

 

Beeping every second 

4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

 

Symptom 

Possible cause 

Remedy 

No indication and alarm in the front 
display panel even though the mains 
is normal.   

The AC input power is not 
connected properly. 

Check that the input cable is 
firmly connected to the mains.   

The icon 

and the warning code 

  flashes on the LCD display and 

the alarm beeps every second. 

EPO function is enabled. 

Set the circuit to closed 
position to disable the EPO 
function.   

The icons 

and 

  flashes 

on the LCD display and the alarm 
beeps every second. 

The external or internal battery 
is incorrectly connected. 

Check that all the batteries are 
connected properly. 

The icons 

  and

  flashes 

on the LCD display and the alarm 
beeps twice every second. 

The UPS is overloaded.   

Remove excess loads from the 
UPS output. 

The UPS is overloaded. 
Devices connected to the UPS 
are fed directly by the 
electrical network through the 
Bypass. 

Remove excess loads from the 
UPS output. 

After repetitive overloads, the 
UPS is locked on Bypass 
mode. Connected devices are 
fed directly by the mains. 

Remove excess loads from the 
UPS output first. Then shut 
down the UPS and restart it. 

Fault code is shown as 43. The icon 

  lights on LCD display and 

alarm beeps continuously. 

The UPS has been in overload 
too long and becomes faulty. 
The UPS shuts down 
automatically.

 

Remove excess loads from 
UPS output and restart it. 

Fault code is shown as 14, the icon 

  lights on the LCD display, 

and the alarm beeps continuously. 

The UPS shuts down 
automatically because a short 
circuit occurred on the UPS 
output. 

Check the output

’s wiring and 

that connected devices are in 
short circuit status. 

Other fault codes are displayed and 
the alarm sounds continuously. 

A UPS internal fault has 
occurred.   

Contact your dealer 

Battery backup time is shorter than 
nominal value 

Batteries are not fully charged 

Charge the batteries for at 
least 7 hours and then check 
their capacity. If the problem 
persists, consult your dealer.   

Battery defect 

Contact your dealer to replace 
the battery. 

The icons 

and 

  flash on the 

LCD display and the alarm beeps 
every second. 

Fan is locked or not working; 
or the UPS temperature is too 
high. 

Check the fans and notify your 
dealer.   

 

 

 

 

 

Содержание E4 LCD Pro 10 000

Страница 1: ...MANUEL UTILISATEUR USER MANUAL MANUAL DE USUARIO 5000 S 6000 S 8000 S 10k S...

Страница 2: ...0 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 V Ve er rs si io on n F Fr ra an n a ai is se e p p2 2 E En ng gl li i...

Страница 3: ...INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 2 Version Fran aise...

Страница 4: ...DU LOGICIEL 10 3 UTILISATION 11 3 1 FONCTIONS DES BOUTONS 11 3 2 VOYANTS DEL ET ECRAN LCD 12 3 3 UTILISATION D UN ONDULEUR SEUL 14 1 Allumer l onduleur en alimentation secteur en mode AC 14 2 Connexi...

Страница 5: ...ronnements humides ou pr s d eaux courantes Prot ger l onduleur contre toutes projections de liquides et ou d objets divers Ne pas installer l onduleur dans un endroit o il sera expos au rayonnement d...

Страница 6: ...sion et d fauts L onduleur fonctionne avec des tensions dangereuses Les r parations ne doivent tre faites que par du personnel d entretien qualifi Attention risque d lectrocution M me apr s avoir t d...

Страница 7: ...it Une batterie peut causer un choc lectrique ou un intense court circuit Les pr cautions suivantes doivent tre observ es par le technicien lors de l intervention Retirer montres bagues Utiliser des o...

Страница 8: ...enu de l emballage L emballage d exp dition contient Un onduleur Un manuel utilisateur Un CD de logiciel de surveillance Un c ble RS 232 en option Un c ble USB Un c ble batterie livr seulement avec le...

Страница 9: ...INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 8...

Страница 10: ...les indications du tableau suivant Mod le Sp cifications de c blage mm AWG Entr e Sortie Batteries Terre E4 LCD 5K 6K 6 10 6 10 6 10 E4 LCD 5K S 6K S 6 10 6 10 6 10 6 10 E4 LCD 8K 10K 10 8 10 8 10 8...

Страница 11: ...tre sans surveillance l arr t le d marrage et la surveillance d tat connecter une extr mit du c ble de communication au port USB RS 232 et l autre extr mit au port de communication de l ordinateur Le...

Страница 12: ...figuration Bouton Test Up Essai des batteries Tout en tant en mode AC ou CVCF appuyer sur ce bouton Test Essai pendant plus de 0 5 s pour faire un test batterie Touche UP Appuyer sur le bouton UP fl c...

Страница 13: ...trouvent en face avant et indiquent les tats de fonctionnement de l onduleur Mode DEL BYPASS LINE BAT FAULT D marrage onduleur Mode By pass Mode Secteur Mode Batterie Mode CVCF Test de batteries D fau...

Страница 14: ...AC tension de sortie VDC tension des batteries Hz fr quence Informations sur la charge Indique le niveau de charge 0 25 26 50 51 75 et 76 100 Indique une surcharge Indique que la charge ou la sortie e...

Страница 15: ...activer les appareils un par un l cran LCD affichera le niveau de charge total 2 S il est n cessaire de connecter des charges inductives une imprimante par exemple l intensit du courant d appel doit t...

Страница 16: ...types de charges 5 Lorsque la dur e de secours est configur e sur 16 5 heures valeur par d faut partir de l cran LCD l onduleur s arr te automatiquement apr s une d charge de 16 5 heures pour prot ge...

Страница 17: ...59 204 10 16 3 4 Index des abr viations de l cran LCD Abr viation Contenu de l affichage Signification ENA Activ DIS D sactiv ATO Automatique BAT Batteries NCF Mode Normal ce n est pas le mode CVCF T...

Страница 18: ...bles pour le param tre 1 Code Description By pass AC CVCF Batteries Test de batteries 01 Tension de sortie X 02 Fr quence de sortie X 03 Plage de tension pour le by pass X 04 Plage de fr quence pour l...

Страница 19: ...ns ce mode l onduleur continue de charger les batteries cran LCD Mode Batteries Description Lorsque la tension d entr e est au del de la plage acceptable ou lorsqu une panne de courant se produit l on...

Страница 20: ...Sous tension Bus DC 03 Aucun SCR batteries en court circuit 21 Aucun D s quilibre du bus 04 Aucun Relais onduleur en court circuit 24 Aucun D faillance d marrage logiciel onduleur 11 Aucun Temp ratur...

Страница 21: ...la sortie de l onduleur Apr s plusieurs d fauts de surcharge l onduleur est verrouill en mode By pass Les dispositifs connect s sont aliment s directement par le r seau D lester d abord les charges en...

Страница 22: ...famili res avec les batteries et prenant les mesures de pr caution requises peuvent remplacer les batteries et superviser le remplacement Les personnes non habilit es ne doivent pas rester proximit de...

Страница 23: ...THD Charge lin aire 6 THD Charge non lin aire Temps de transfert Mode AC mode Batt Z ro Onduleur By pass Z ro Forme d onde mode Batteries Sinuso dale pure Autonomie Selon la charge connect e RENDEMEN...

Страница 24: ...t navigateur internet Logiciel InfoPower NORMES Standard CE Compatibilit Electromagn tique EN62040 2 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN61000 4 5 EN61000 4 6 EN61000 4 8 EN61000 4 11 EN61000 2 2 S...

Страница 25: ...INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 24 English Version...

Страница 26: ...VIEW 29 2 3 SINGLE UPS INSTALLATION 30 2 4 SOFTWARE INSTALLATION 31 3 OPERATIONS 32 3 1 BUTTON OPERATION 32 3 2 LED INDICATORS AND LCD PANEL 33 3 4 SINGLE UPS OPERATION 35 1 Switch on the UPS with ut...

Страница 27: ...to the environment Do not install the UPS system near water or in a damp environment Do not install the UPS system where it could be exposed to direct sunlight or near a heater Do not block the air ve...

Страница 28: ...Maintenance servicing and faults The UPS system operates with hazardous voltages Repairs may only be carried out by qualified maintenance personnel Caution Risk of electric shock Even after the unit i...

Страница 29: ...electric shock and cause short circuits The following precautions should be followed the qualified technician Remove watches rings or other metal objects from your hands Use tools with insulated handl...

Страница 30: ...two different types of online UPS standard and long run models Please refer to the following model table Model Type Model Type E4 LCD Pro 5 000 Standard model E4 LCD Pro 5 000 S Long run model E4 LCD...

Страница 31: ...s less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all the devices that need...

Страница 32: ...or optimal computer system protection install the UPS monitoring software to fully configure UPS shutdown Communication ports USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown...

Страница 33: ...button to return to last menu in the setting menu Test Up Button Battery test Press and hold the button more than 0 5s to test the battery while in AC mode or CVCF mode UP key Press this button to di...

Страница 34: ...ttery mode CVCF mode Battery Test Fault Note means LED is ON and means LED is OFF LCD Panel Display Function Backup time information Indicates backup time in numbers when the UPS is in battery mode H...

Страница 35: ...dicates that the UPS is connected to the mains Indicates that the battery is working Indicates that the bypass circuit is working Indicates that the Inverter circuit is working Indicates that the outp...

Страница 36: ...ne by one the LCD panel will display the total load level 2 If it is necessary to connect inductive loads such as a printer the in rush current should be calculated carefully to see if it meets the ca...

Страница 37: ...value from LCD panel after discharging 16 5 hours UPS will shut down automatically to protect the battery This battery discharge protection can be enabled or disabled using the LCD panel control Refe...

Страница 38: ...E Select Up3 or Down buttons to change the programs or parameters List of 20 programs available for parameter 1 Code Description Bypass AC CVCF Battery Battery Test 01 Output voltage Y 02 Output frequ...

Страница 39: ...to 64Hz the UPS can be set to a constant output frequency 50 Hz or 60 Hz The UPS will still charge the battery in this mode LCD display Battery mode Description When the input voltage is beyond the ac...

Страница 40: ...Negative power fault 1A None DC Bus under 03 None Battery SCR short circuited 21 None DC Bus unbalance 04 None Inverter relay short circuited 24 None Inverter soft start failure 11 None Over temperat...

Страница 41: ...ctly by the electrical network through the Bypass Remove excess loads from the UPS output After repetitive overloads the UPS is locked on Bypass mode Connected devices are fed directly by the mains Re...

Страница 42: ...BUS capacitors Only persons who are sufficiently familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept w...

Страница 43: ...rest ratio 3 1 max Harmonic distortion 3 100 Linear Load 6 100 Non linear Load Transfer time AC mode to battery mode 0 ms Inverter to Bypass 0 ms Waveform Pure Sinewave EFFICIENCY AC mode 89 90 Batter...

Страница 44: ...43 INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10...

Страница 45: ...3 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 44 1 CEM Infosec Communication 8 1 CE CEI LVD EMC 2 E4 LCD 5 10kVA E4 LCD Pro 5 000 E4 LCD Pro 5 000 S E4 LCD Pro 6 000 E...

Страница 46: ...France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 1 2 RS 232 USB S 2 2 1 2 RS232 3 AS 400 SNMP 4 USB 5 EPO 6 7 8 3 9 11 11 12 1 5k...

Страница 47: ...82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 46 2 3 1 2 Off 3 4 AWG E4 LCD 5K 6K 6 10 6 10 6 10 E4 LCD 5K S 6K S 6 10 6 10 6 10 6 10 E4 LCD 8K 10K 10 8 10 8 10 8 E4 LCD 8K S 10K S 1...

Страница 48: ...Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 1 2 6 4 2 USB RS 232 USB RS 232 1 CD ROM 2 3 SNMP AS...

Страница 49: ...com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 48 3 1 3 ON Enter ON Enter Enter ESC OFF OFF ESC ESC Test Up AC CVCF Test UP UP Mute Down Mute 9 4 3 D...

Страница 50: ...49 INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 CVCF...

Страница 51: ...15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 50 2 3 DEL LCD DEL DEL LED BYPASS LINE BAT FAULT...

Страница 52: ...ue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 H M S 3 9 VAC VDC Hz 0 25 26 50 51 75 76 100 0 25 26...

Страница 53: ...Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 52 3 4 1 AC 1 ON ON 1 2 ON 3 AC 2 1 LCD 2 3 4 80 5 AC AC 3...

Страница 54: ...in 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 4 1 25 4 2 Mute 3 4 5 16 5 LCD 16 5 LCD 3 7 LCD 5 1 AC CVCF ECO...

Страница 55: ...5 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 54 5 3 LCD ENA DIS ATO BAT NCF CVCF CF CVCF SUB AD...

Страница 56: ...t Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 6 3 1 14 2 3 Up Down 15 1 By pass AC CVCF 01 X 02 X 03 X 04 X 05 06 07 08 X X 09 X X X X X 10 11 12 13 X X X...

Страница 57: ...15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 56 3 7 AC AC AC LCD CVCF 46 64 50 60 LCD 4 LCD LC...

Страница 58: ...57 INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 LCD LCD LCD...

Страница 59: ...44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 58 8 3 BUS DC 01 14 BUC DC 02 1 A BUC DC 03 SCR 21 Bus 04 24 11 4...

Страница 60: ...UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 4 AC LCD EPO EPO LCD LCD 43 LCD 14 LCD...

Страница 61: ...NFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 60 5 1 5 7 25 40 3 40 45 2 5 BU...

Страница 62: ...LCD Pro 8 000 S E4 LCD Pro 10 000 S 5000 VA 4500 W 6000 VA 5400 W 8000 VA 7200 W 10000 VA 9000 W 176VAC 100 110VAC 50 186VAC 100 120VAC 50 300VAC 3 290 VAC 46 54 50 56 64 60 0 99 100 208 220 230 240...

Страница 63: ...INFOSEC UPS SYSTEM 15 Rue du Moulin 44880 Sautron France www infosec ups com Hot Line Tel 33 0 2 40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 62 55dB 58dB...

Страница 64: ...40 76 15 82 fax 33 0 2 40 94 29 51 hotline infosec fr 03 17 AA 59 204 10 RS 232 USB Windows familial Novell Linux Mac et FreeBSD SNMP SNMP InfoPower CE EN62040 2 EN61000 4 2 EN61000 4 3 EN61000 4 4 EN...

Отзывы: