System Description
Switch
Function
ON
To turn on UPS system: press the ON-Switch “I”.
To deactivate the audible alarm: press the ON-Switch “I”.
OFF
When mains power is normal, the UPS system switches to Bypass and the inverter is off.
The output outlets are supplied with voltage via the bypass if the mains power is available.
LEDs
Function
LINE LED
The green “LINE” led lights up if mains voltage is applied to the UPS input.
“LINE” led blinks when the line and neutral conductor have been reversed at the input of the UPS
system.
If “LINE” led and “BATTERY” led light up, the mains power supply is out of tolerance.
BATTERY LED
The orange-coloured “BATTERY” led lights up when the mains power has failed and the inverter is
being powered by the batteries.
BYPASS LED
The orange-coloured “BYPASS” led lights up when the UPS system is supplying voltage provided by
the mains power via the bypass.
INVERTER LED
The green-coloured “INVERTER” led lights up if the UPS system is supplying voltage provided by the
mains power via the inverter.
FAULT LED
The red “FAULT” led lights up and an audible alarm beeps continuously when the UPS system is in
fault condition. Press the “OFF” switch in order to turn off the alarm.
LOAD and
BATTERY
CAPACITY LEDs
These leds show the load of the UPS system if the mains power is available (normal operation) :
2nd LED
= 96%-105 % -
3rd
LED
= 76%-95 % -
4th
LED
= 56%-75 % -
5th
LED
= 36%-55 % -
6th
LED
= 1-35 %
In the battery operation, the LEDs indicate the capacity of the batteries :
2nd
LED
= 1-35 % -
3rd
LED
= 36%-55 % -
4th
LED
= 56%-75 % -
5th
LED
= 76%-95 % -
6th
LED
= 96%-100 %