![INFOSEC UPS SYSTEM E3 PRO RT 1000 VA Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/infosec-ups-system/e3-pro-rt-1000-va/e3-pro-rt-1000-va_user-manual_2058268018.webp)
INFOSEC UPS SYSTEM
– 15, Rue du Moulin – 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line
– Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - [email protected] – 11 17 AA 59 204 17
18
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass function. You
may choose the following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 1 & 2:
Set the acceptable high voltage
point and acceptable low voltage point for Bypass
mode by pressing the Down key or Up key.
HS:
Bypass high voltage point
For 208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
For 110/115/120/127 VAC models:
120-140:
setting the high voltage point in parameter 3
from 120Vac to 140Vac(Default: 132Vac)
LS:
Bypass low voltage point
For 208/220/230/240 VAC models:
170-220:
setting the low voltage point in parameter 3
from 170Vac to 220Vac (Default: 170Vac)
For 110/115/120/127 VAC models:
85-115:
setting the low voltage point in parameter 3
from 85Vac to 115Vac. (Default: 85Vac)