04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO function. You
may choose the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
05: ECO voltage range setting
Interface
Setting
Parameter 1 & 2:
Set the acceptable high voltage
point and low voltage point for ECO mode by pressing
Down key or Up key.
HS:
High loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range
in parameter 3 is from +7V to +24V of the nominal
voltage. (Default: +12V)
For 110/115/120/127 VAC models, the setting range
in parameter 3 is from +3V to +12V of the nominal
voltage.
(Default: +6V)
LS:
Low loss voltage in ECO mode in parameter 2.
For 208/220/230/240 VAC models, the setting range
in parameter 3 is from -7V to -24V of the nominal
voltage.
(Default: -12V)
For 110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal
voltage.
(Default: -6V)