INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - [email protected] – 12 18 AA 59 205 19
55
7 . S p e c i f i c a t i o n s
E3 Performance 5000 RT
GENERAL CHARACTERISTICS
CAPACITY*
3000 VA / 2700 W
Dimension,
DXWXH (mm)
645 x 438 x 88 (2U)
Net Weight (kg)
39.8
INPUT
Acceptable Voltage
Range
75-117/81-134/86-139/89-145/102-152 VAC for models 120VAC
150-234/156-243/162-268/170-280/177-290 VAC for models 230VAC
Frequency Range
60/50 Hz (auto sensing)
OUTPUT
Voltage Regulation
(normal Mode)
100*(-13%/+10%)/110(-15%/+10%)/115(-14%/+10%)/120(-14%/+10%)/125(-11%/+11%) VAC
for models 120VAC
200*(-13%/+10%)/208*(-13%/+10%)/220(-15%/+10%)/230(-15%/+10%)/240(-15%/+10%) VAC
for models 208VAC
Voltage Regulation
(Batt. Mode)
100/110/115/120/125 VAC ±1.5%(before low battery alarm) for models 120VAC
200/208/220/230/240 VAC ±1.5% (before low battery alarm) for models 230VAC
Frequency Range
(Batt. Mode)
50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
Over load capacity
103% to 120% Alarm warning with shutdown after 5 minutes (1minutes @ battery mode)
120% to 150% Alarm warning with shutdown after 10 seconds
150% and greater Shutdown UPS Immediately
Waveform
(Batt. Mode)
Pure Sine Wave
EFFICIENCY
Normal Mode
97%
AVR Mode
95%
Battery Mode
92%
BATTERY
Battery Type &
Number
12 V/10 Ahx6
Charging Voltage
82.1 VDC ± 1%
Recharge Time
4 hours recover to 90% capacity
PROTECTION
Full Protection
Overload, short, discharge, and overcharge protection
INDICATORS & ALARM
Indicator
LCD screen
Alarms
Battery Mode, Low Battery, Overload, Battery Replacement, Fault
ENVIRONMENT
Operating Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Elevation
Up to 3,000m @ 0-40°C without derating.
Ambient temperature will require derating of 5 °C for each additional 500 m in altitude.
Noise Level
Less than 45dB at 1 meter
MANAGEMENT/COMMUNICATION
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, 7/8/10, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP (VMWare
©
compatible) manager and web browser
NORMS
Standards
CE RoHS
EMC
EN62040-2: 2006+AC: 2006
LVD
EN62040-1:2008+A1:2013
SALES INFORMATION
Warranty
2 years
PN IEC (HV)
67035
PN NEMA (HV)
68248
HV : 230V models: 200/208/220/230/240V / LV : 120V models : 100/110/115/120/125V
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC.