06: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
07: EPO logic setting
Interface
Setting
Parameter 2:
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as EPO logic, it
will activate EPO function with Pin 1 and Pin 2 in close
status.
08: Input Waveform Sensitivity setting
Interface
Setting
Parameter 2:
Set Input Waveform Sensitivity.
St1
: Input voltage waveform detection is highly sensitive.
(Default)
St2
: Input voltage waveform detection is middle sensitive.
St3
: Input voltage waveform detection is low sensitive.
(use with generators or Step wave input)