54
Battery backup time is shorter than nominal
value
Batteries are not fully
charged.
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Batteries defect.
Contact your dealer to
replace the battery.
Fault code is shown as 45 on LCD display.
At the same time, alarm is continuously
sounding.
The charger does not
have output and battery
voltage is less than
10V/PC.
Contact your dealer.
5 . S T O R A G E A N D M A I N T E N A N C E
5.1 Warning indicator
The UPS system contains no user-serviceable parts. If the battery service life (3~5
years at 25°C ambient temperature) has been exceeded, the batteries must be
replaced. In this case, please contact your dealer.
5.2 Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
6 . A v a i l a b l e o p t i o n s
Here are the options available :
Designation
Ref.
SNMP I Pro communication card
61156
SNMP vm Minislot card (Virtual environment)
61142
RS485 protocol card
61439
Kit Rack
61429
Dry contact card
61454
External Bypass RM (External Bypass manual)
61444